Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1061624 |
06/10/2019 |
Order Conditions |
Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30.0 Degrees C and reported value was 30.7 Degrees C at M-001. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1062054 |
07/18/2019 |
Order Conditions |
Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30 Degrees C and reported value was 33.2 Degrees C at M-001. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1123578 |
12/17/2023 |
Order Conditions |
Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30.0 Degrees C and reported value was 31.6 Degrees C at M-001. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1077555 |
06/02/2020 |
OEV |
pH Instantaneous Maximum limit is 9 SU and reported value was 9.23 SU at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1107764 |
07/25/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.95 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1093408 |
07/08/2021 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.69 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1111627 |
11/22/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.05 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1110872 |
10/31/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.08 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1061623 |
06/04/2019 |
OEV |
pH Instantaneous Maximum limit is 9 SU and reported value was 10.05 SU at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1104661 |
04/11/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.18 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1108791 |
08/16/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.36 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1091398 |
05/06/2021 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.48 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1116891 |
04/19/2023 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.50 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1106601 |
06/08/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.14 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1089334 |
03/02/2021 |
OEV |
pH 1-Hour Average (Mean) limit is 9.0 SU and reported value was 9.1 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1105847 |
05/12/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.4 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1120670 |
08/29/2023 |
OEV |
pH Instantaneous Maximum limit is 9 SU and reported value was 9.2 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1090695 |
04/14/2021 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.69 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1126586 |
03/04/2024 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.14 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1085131 |
12/07/2020 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.1 SU at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1119737 |
07/24/2023 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.24 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1110871 |
10/31/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.47 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1094709 |
08/03/2021 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.27 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1120669 |
08/29/2023 |
OEV |
pH Instantaneous Maximum limit is 9 SU and reported value was 9.96 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1092558 |
06/03/2021 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.7 SU at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1126587 |
03/04/2024 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.42 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1109495 |
09/15/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.13 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1111626 |
11/22/2022 |
OEV |
pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.13 SU at M-INTB2. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1067549 |
10/14/2019 |
Deficient Reporting |
pH hold time for the duplicate sample exceeded 15 minutes. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1104660 |
04/11/2022 |
Deficient Monitoring |
Circulating water flow was reversed at the time of sampling at M-001 sampling point. As a result, M-001 samples collected were representative of the facility intake. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1118246 |
05/08/2023 |
Deficient Monitoring |
Delta between duplicate samples was greater than 0.1 pH unit. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1121427 |
09/20/2023 |
Deficient Monitoring |
Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1121426 |
09/20/2023 |
Deficient Monitoring |
Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1067550 |
10/23/2019 |
Deficient Monitoring |
Flow meter power failure occurred at approximately 1:00 am on 10/23/2019. Confirmed valve was in closed position on 10/24/2019, at approximately 9:00 am. However, valve may have been open during this time without monitoring. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1076412 |
05/04/2020 |
Deficient Monitoring |
Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1069960 |
12/03/2019 |
Deficient Monitoring |
Intermittent flow meter and integrator failures occurred between December 3rd and December 18th. Manual logs were kept by the operators during this period. Reported daily flows during this period were estimated based on the manual logs. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1122294 |
10/30/2023 |
Deficient Monitoring |
pH measurements outside the acceptable range for relative percent difference (RPD) of 0.1 pH unit |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1121428 |
09/20/2023 |
Deficient Monitoring |
Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1067551 |
10/24/2019 |
Deficient Monitoring |
Flow meter power failure occurred at approximately 1:00 am on 10/23/2019. Confirmed valve was in closed position on 10/24/2019, at approximately 9:00 am. However, valve may have been open during this time without monitoring. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1075183 |
04/27/2020 |
Deficient Monitoring |
Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1076413 |
05/11/2020 |
Deficient Monitoring |
Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1068234 |
11/05/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0038 lb/day and reported value was 0.0067 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1067552 |
10/10/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0034 lb/day and reported value was 0.0066 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1066061 |
09/10/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0033 lb/day and reported value was 0.0078 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1061622 |
06/04/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0036 lb/day and reported value was 0.0083 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1064541 |
08/06/2019 |
CAT2 |
Copper, Total 6-Month Median limit is 0.0032 lb/day and reported value was 0.0084 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1062055 |
07/02/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0034 lb/day and reported value was 0.0081 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1069959 |
12/19/2019 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0056 lb/day and reported value was 0.0082 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1071427 |
01/13/2020 |
CAT2 |
Copper, Total Recoverable 6-Month Median limit is 0.0074 lb/day and reported value was 0.0083 lb/day at M-INTB. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
377497 |
R8-2014-0076 |
N |
1120668 |
08/29/2023 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 33.8 mg/L at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |
1094710 |
08/03/2021 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 35.5 mg/L at M-INTB1. |
Violation |
N |
eSMR |
Huntington Beach Generating Station |
422464 |
R8-2020-0040 |
N |