Party ID Party Name Party Classification Mailing Address Work Phone Email/Website
866 AES Huntington Beach LLC Privately-Owned Business 21730 Newland Way Huntington Beach, CA 92646 714-374-1476 None
  
  
  
  
Expand/Contract Related Places
Related Places
Place ID Place Name County Region Place Type Relationship to Party Relationship Start Date Relationship End Date
226995 Huntington Beach Generating Station Orange 8 Power Plant Owner 04/03/1998 None
Total Related Places: 1
  
  
  
  
Expand/Contract Related Parties
Related Parties
Party ID Party Name Party Type Role/Relationship Relationship Start Date Relationship End Date Classification
560019 Keith McGregor Person Data Submitter 10/18/2016 None None
534487 Weikko Wirta Person Legally Responsible Official 11/17/2014 None None
553155 Jose Perez Person Legally Responsible Official 09/08/2023 None None
598395 Benjamin Morgan Person Data Submitter 06/03/2019 None None
521000 William Stevens Person Legally Responsible Official 03/02/2010 11/15/2016 None
521000 William Stevens Person Data Submitter 02/24/2010 11/15/2016 None
525311 Katherine Balanza Person Data Submitter 09/26/2023 None None
550384 Kathryn Hubbard Person Data Submitter 03/13/2015 None None
549784 Jeffrey Miller Person Data Submitter 03/12/2015 None None
549784 Jeffrey Miller Person Data Submitter 03/02/2015 None None
149597 Paul Hurt Person Data Submitter 03/16/2006 11/16/2014 None
551233 Tyler Rowland Person Data Submitter 05/18/2015 05/19/2017 None
542223 Coury McKinlay Person Data Submitter 12/15/2014 None None
Total Related Parties: 13
  
  
  
  
Expand/Contract Regulatory Measures
Regulatory Measures (non-enforcement)
Reg. Measure ID Regulatory Measure Type Region WDID Status Program Order No. RM Effective Date RM Termination Date Relationship Relationship Start Date Relationship End Date Amended?
138905 NPDES Permit 8 8 302015004 Historical NPDESWW 87-093 09/11/1987 None Discharger 09/11/1987 None N
315519 NPDES Permit 8 8 302015004 Historical NPDINDLRG R8-2006-0011 10/14/2006 12/31/2014 Discharger 06/30/2000 None N
422464 NPDES Permit 8 8 302015004 Active NPDNONMUNIPRCS R8-2020-0040 01/01/2021 None Discharger 07/06/2018 None N
377497 NPDES Permit 8 8 302015004 Historical NPDNONMUNIPRCS R8-2014-0076 01/01/2015 12/31/2020 Discharger 06/30/2000 None N
141414 NPDES Permit 8 8 302015004 Historical NPDESWW 93-058 10/21/1993 06/30/2000 Discharger 10/21/1993 None N
137879 NPDES Permit 8 8 302015004 Historical NPDESWW 81-133 07/10/1981 None Discharger 07/10/1981 None N
140418 NPDES Permit 8 8 302015004 Historical NPDESWW R8-2000-0005 07/07/2000 None Discharger 06/30/2000 None N
Total Regulatory Measures: 7
  
  
  
  
Expand/Contract Violations
Violations within the past five years
Violation ID Occurrence Date Violation Type Violation Description(-) Violation Status Priority Source Facility Name Violated Reg. Meas. ID Violated Reg. Meas. Order No. Linked to Enf.
1107764 07/25/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.95 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1104660 04/11/2022 Deficient Monitoring Circulating water flow was reversed at the time of sampling at M-001 sampling point. As a result, M-001 samples collected were representative of the facility intake. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1069960 12/03/2019 Deficient Monitoring Intermittent flow meter and integrator failures occurred between December 3rd and December 18th. Manual logs were kept by the operators during this period. Reported daily flows during this period were estimated based on the manual logs. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1077555 06/02/2020 OEV pH Instantaneous Maximum limit is 9 SU and reported value was 9.23 SU at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1118246 05/08/2023 Deficient Monitoring Delta between duplicate samples was greater than 0.1 pH unit. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1061624 06/10/2019 Order Conditions Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30.0 Degrees C and reported value was 30.7 Degrees C at M-001. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1111626 11/22/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.13 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1121426 09/20/2023 Deficient Monitoring Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1067550 10/23/2019 Deficient Monitoring Flow meter power failure occurred at approximately 1:00 am on 10/23/2019. Confirmed valve was in closed position on 10/24/2019, at approximately 9:00 am. However, valve may have been open during this time without monitoring. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1109495 09/15/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.13 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1126587 03/04/2024 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.42 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1067552 10/10/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0034 lb/day and reported value was 0.0066 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1061622 06/04/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0036 lb/day and reported value was 0.0083 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1092558 06/03/2021 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.7 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1123578 12/17/2023 Order Conditions Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30.0 Degrees C and reported value was 31.6 Degrees C at M-001. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1120669 08/29/2023 OEV pH Instantaneous Maximum limit is 9 SU and reported value was 9.96 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1121428 09/20/2023 Deficient Monitoring Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1066061 09/10/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0033 lb/day and reported value was 0.0078 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1067551 10/24/2019 Deficient Monitoring Flow meter power failure occurred at approximately 1:00 am on 10/23/2019. Confirmed valve was in closed position on 10/24/2019, at approximately 9:00 am. However, valve may have been open during this time without monitoring. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1075183 04/27/2020 Deficient Monitoring Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1062055 07/02/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0034 lb/day and reported value was 0.0081 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1094709 08/03/2021 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.27 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1110871 10/31/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.47 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1119737 07/24/2023 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.24 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1085131 12/07/2020 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.1 SU at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1093408 07/08/2021 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.69 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1126586 03/04/2024 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.14 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1120668 08/29/2023 CAT1 Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 33.8 mg/L at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1062054 07/18/2019 Order Conditions Temp Diff b/n Intake and Discharge Instantaneous Maximum limit is 30 Degrees C and reported value was 33.2 Degrees C at M-001. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1090695 04/14/2021 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.69 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1120670 08/29/2023 OEV pH Instantaneous Maximum limit is 9 SU and reported value was 9.2 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1105847 05/12/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.4 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1089334 03/02/2021 OEV pH 1-Hour Average (Mean) limit is 9.0 SU and reported value was 9.1 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1094710 08/03/2021 CAT1 Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 35.5 mg/L at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1076413 05/11/2020 Deficient Monitoring Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1106601 06/08/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.14 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1116891 04/19/2023 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.50 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1091398 05/06/2021 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.48 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1071427 01/13/2020 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0074 lb/day and reported value was 0.0083 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1068234 11/05/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0038 lb/day and reported value was 0.0067 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1076412 05/04/2020 Deficient Monitoring Temperature probe was not connected properly at the time of pH probe calibration and measurement. Temperature default of 25.0 C was used. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1108791 08/16/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.36 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1067549 10/14/2019 Deficient Reporting pH hold time for the duplicate sample exceeded 15 minutes. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1104661 04/11/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.18 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1121427 09/20/2023 Deficient Monitoring Samples were collected per the NPDES permit requirement. Cross contamination occurred during the laboratory analysis and results of the analysis were received too late to conduct a second sample within the same month. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1122294 10/30/2023 Deficient Monitoring pH measurements outside the acceptable range for relative percent difference (RPD) of 0.1 pH unit Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1061623 06/04/2019 OEV pH Instantaneous Maximum limit is 9 SU and reported value was 10.05 SU at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1064541 08/06/2019 CAT2 Copper, Total 6-Month Median limit is 0.0032 lb/day and reported value was 0.0084 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
1110872 10/31/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.08 SU at M-INTB2. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1111627 11/22/2022 OEV pH Instantaneous Maximum limit is 9.0 SU and reported value was 9.05 SU at M-INTB1. Violation N eSMR Huntington Beach Generating Station 422464 R8-2020-0040 N
1069959 12/19/2019 CAT2 Copper, Total Recoverable 6-Month Median limit is 0.0056 lb/day and reported value was 0.0082 lb/day at M-INTB. Violation N eSMR Huntington Beach Generating Station 377497 R8-2014-0076 N
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 51
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
  
  
  
  
Expand/Contract Enforcement Actions
Enforcement Actions
Enforcement ID Enforcement Type Enf. Order No. Title Program Effective Date Status
238823 Oral Communication UNKNOWN Enforcement - 8 302015004 NPDESWW 09/14/2001 Historical
Total Enforcement Actions: 1
  
  
  
  
Expand/Contract Enforcement Actions
Regulatory Measures linked to Related Parties
Reg. Measure ID Organization Regulatory Measure Type Program Effective Date Status