Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1140122 |
02/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris-Rags caused 128 gallons of sewage to spill from Lateral Clean Out (Private) at 445 MOLL CT to Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
Sonoma Valley County S.D. CS |
300361 |
2022-0103-DWQ |
N |
1140121 |
02/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 27353 gallons of sewage to spill from Manhole at SVCSD_M60-13 VAILETTI DR to Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
Sonoma Valley County S.D. CS |
300361 |
2022-0103-DWQ |
N |
1140120 |
02/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 4760 gallons of sewage to spill from Lateral Clean Out (Private) at 15561 BROOKVIEW DR to Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
Sonoma Valley County S.D. CS |
300361 |
2022-0103-DWQ |
N |
1137005 |
11/23/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 3565 gallons of sewage to spill from Manhole at RRCSD_M17-23 to Surface Water |
Violation |
None |
SSO |
SCWA Russian River CSD CS |
300283 |
2022-0103-DWQ |
N |
1133137 |
02/06/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance caused 7026 gallons of sewage to spill from Force Main at Minna St to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
SCWA Occidental CSD CS |
300111 |
2022-0103-DWQ |
N |
1131317 |
07/10/2024 |
Deficient Monitoring |
QA/QC criteria not met. GGA Reference sample low and out of compliance. QC result was 122 mg/L. Acceptance Range 167.5-238.5 mg/L. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1131316 |
07/10/2024 |
Deficient Monitoring |
QA/QC criteria not met. GGA Reference sample low and out of compliance. QC result was 122 mg/L. Acceptance Range 167.5-238.5 mg/L. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1126183 |
03/01/2024 |
Unauthorized Discharge |
The unauthorized discharge of approximately 276,078 gallons of undisinfected secondary treated wastewater to a drainage ditch which flowed to the Russian River. |
Violation |
None |
Complaint |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1126050 |
03/01/2024 |
Order Conditions |
During the late evening of Friday, March 1, 2024 and into the early morning of Saturday, March 2, 2024, the District's treatment plant experienced an unauthorized discharge with an estimated volume of up to 276,078 gallons of secondary treated wastewater. Time Occurred: 02/01/2024 10:57 to 02/02/2024 04:20. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1121938 |
11/17/2023 |
Order Conditions |
On October 17 at 16:00 hours and continuing through October 18 at 06:00 hours there was a communications failure for our secondary effluent turbidity readings. All other compliance data was captured and there were no fluctuations in flow patterns outside of the normal diurnal flows. The final effluent turbidity during this same timeframe was well within the required turbidity range with an average turbidity of 0.45 NTU's and a daily maximum of 0.85 NTU's. Given these factors we believe that the secondary effluent turbidity remained in compliance. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1114509 |
01/31/2023 |
Late Report |
Annual Report due January 30th received 2/03/23, 4 days late. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1112570 |
12/10/2022 |
Order Conditions |
Turbidity Other limit is 10 NTU and reported value was 12.529 NTU at INT-001A. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1112476 |
12/31/2022 |
OEV |
Enterococci Monthly 90th% limit is 110.0 CFU/100 mL and reported value was 784.23 CFU/100 mL at EFF-002. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1111580 |
11/03/2022 |
Deficient Monitoring |
No sample for Total Hardness was collected at the Russian River Upstream location RSW-001 for November. Upstream Hardness is a monthly requirement during discharge season while Effluent Hardness location EFF-002 is a grab once per discharge season requirement causing the confusion. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1109566 |
09/12/2022 |
Deficient Monitoring |
Samples for BOD & TSS were sent to contract lab for analysis for 09/12, 09/13, & 9/14. Alpha Labs only logged in the BOD's and not the TSS's. All three samples for TSS were run past hold time. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1109565 |
09/12/2022 |
Deficient Monitoring |
Samples for BOD & TSS were sent to contract lab for analysis for 09/12, 09/13, & 9/14. Alpha Labs only logged in the BOD's and not the TSS's. All three samples for TSS were run past hold time. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1108535 |
08/09/2022 |
Deficient Monitoring |
The well was dry and monitoring could not occur in August as the permit requires. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1107034 |
07/18/2022 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average limit is 30 mg/L and reported value was 36 mg/L. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1102226 |
03/02/2022 |
Late Report |
Annual SMR ( SUMRPT ) (Annual Summary Report) report for 2021 (2577311) was due on 01-MAR-22 |
Violation |
None |
Report |
SCWA Russian River CSD |
392149 |
R1-2014-0002 |
N |
1102117 |
03/02/2022 |
Late Report |
Annual SMR ( SUMRPT ) (Annual Summary Report) report for 2021 (2415980) was due on 01-MAR-22 |
Violation |
None |
Report |
SCWA Russian River CSD |
392149 |
R1-2014-0002 |
N |
1099499 |
12/07/2021 |
Deficient Monitoring |
The TDS sample for the upstream receiving waters (RSW-001) was not collected in December. There was some confusion in treading the new permit and TDS was mistakenly thought to be semi-annual not monthly. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1095955 |
09/13/2021 |
Deficient Monitoring |
For Chronic Toxicity: C. dubia - Three-Sample Median Trigger Maximum limit is 1 TUc and reported value was 4.6 TUc at EFF-001 |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1095954 |
09/30/2021 |
CAT2 |
Zinc, Total Monthly Average limit is 58 ug/L and reported value was 59.3 ug/L at EFF-001. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1095872 |
09/30/2021 |
CAT1 |
Sodium, Total Monthly Average limit is 60 mg/L and reported value was 63.5 mg/L at REC-001. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1095871 |
09/30/2021 |
CAT1 |
Sodium, Total Monthly Average limit is 60 mg/L and reported value was 63.5 mg/L at LND-001. |
Violation |
N |
eSMR |
SCWA Russian River CSD |
427524 |
R1-2021-0002 |
N |
1095592 |
09/08/2021 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 37 mg/L. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1094436 |
08/03/2021 |
Deficient Monitoring |
For Chronic Toxicity: C.dubia - (Reproduction) Single Sample Trigger Maximum limit is 2 TUc and reported value was 4.6 TUc at EFF-001. C.dubia - Three-Sample Trigger Maximum limit is 1 TUc and reported value was 4.6 TUc at EFF-001 |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1093623 |
07/12/2021 |
Deficient Monitoring |
Chronic Toxicity - C.dubia - Reproduction Single Sample Trigger Maximum limit is 2 TUc and reported value was 10.3 TUc at EFF-001. Chronic Toxicity - C.dubia -Survival for the same sample was < 1 TUc. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1092328 |
06/09/2021 |
Deficient Monitoring |
On June 9, 2021 at 01:07, the Post CL2 residual at the Sonoma Valley Treatment Plant dropped suddenly causing the plant to divert tertiary final effluent into EQ #3. During this time the Monthly Flow-Through Bioassay was in progress. The plant diverted into EQ #3 until 05:02 for a total of approximately 4 hours. During this time there was no flow to the bioassay unit. When the Operator arrived at the plant it was discovered the probe on the CL2 analyzer was fouled with debris. After cleaning the probe and re-calibrating the analyzers, discharge of tertiary final effluent was resumed to the R4 reservoir and flow to the bioassay unit was resumed. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1090162 |
04/30/2021 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 38 mg/L. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1088156 |
10/15/2020 |
Deficient Monitoring |
The A-8 Colilert sample set on Thur, Oct 15th was mistakenly read right after it was set on the 15th. This Colilert tray was never placed back into the incubator because the normal procedure is to toss the tray after reading. Basically the two samples were interchanged. We are reporting this as "Deficient Monitoring" |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088155 |
07/21/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 166.4 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088154 |
08/02/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 4.1 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088153 |
07/30/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 11 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088152 |
07/10/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088151 |
07/19/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088150 |
07/13/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 27.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088148 |
07/31/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 8.5 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088147 |
07/27/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 32.1 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088146 |
07/15/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 86 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088145 |
06/22/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 261 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088144 |
07/26/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 71.7 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088143 |
07/29/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 20.1 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088142 |
07/28/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 24.2 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088141 |
07/24/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 166.4 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088140 |
07/23/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 290.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088139 |
07/20/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 290.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088138 |
07/25/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 86 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088137 |
07/16/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088136 |
07/12/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 41 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088135 |
07/17/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 178.5 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088134 |
07/16/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 178.5 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088133 |
07/10/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 461 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088129 |
07/23/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 71.7 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088128 |
08/03/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 4.1 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088127 |
07/22/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088123 |
07/19/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 1732.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088122 |
07/18/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088121 |
07/17/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 410.6 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088120 |
07/14/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 186 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088119 |
07/13/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 178.5 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088118 |
07/11/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 27.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088117 |
08/01/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 6.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088115 |
07/25/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 74.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088114 |
07/20/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 290.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088113 |
10/16/2020 |
Deficient Monitoring |
he A-8 Colilert sample that was set on Wed, Oct 14th was not read after 24 hours. This was discovered on Fri, Oct 16th. The Colilert tray was clear. This will be documented as being read past required read time but still <1. We are reporting this as "Deficient Monitoring" |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088112 |
10/30/2020 |
Order Conditions |
A Recycled Water distribution line break was reported to our Mechanic on Friday The area was isolated and repairs are pending other scheduled work for the area affected, an estimated total of 690,000 gallons was released onto the ground and into the dry creek bed. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088111 |
10/27/2020 |
Order Conditions |
Repair work, and valve installation requiring the draining of the Transfer line. An estimated total of 20,000 gallons was released onto the ground and into the dry creek bed. The area affected did not leave the property line. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088110 |
07/24/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 32.1 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088109 |
07/25/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 24.2 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088108 |
07/18/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 178.5 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088107 |
07/17/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 410.6 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088103 |
07/10/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 461 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088102 |
07/21/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088101 |
07/22/2020 |
OEV |
Total Coliform Not to exceed a specific limit in any two consecutive samples limit is 23 MPN/100 mL and reported value was 74.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088100 |
07/18/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 387.3 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088097 |
07/14/2020 |
OEV |
Total Coliform 7-Day Median limit is 2 MPN/100 mL and reported value was 41 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088096 |
07/19/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 1732.9 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1088095 |
07/16/2020 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 387 MPN/100 mL. |
Violation |
N |
eSMR |
SCWA Airport-Larkfield-Wikiup Sanitation Zone Recycled Water |
437072 |
R1-2019-0007 |
N |
1085807 |
12/09/2020 |
OEV |
Total Coliform Daily Maximum limit is 230 MPN/100 mL and reported value was 1600 MPN/100 mL. |
Violation |
N |
Report |
SCWA Geyserville CSD |
433463 |
R1-2019-0013 |
N |
1083883 |
11/30/2020 |
OEV |
Total Coliform 30-Day Average limit is 23 MPN/100 mL and reported value was 49 MPN/100 mL. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1081637 |
10/17/2020 |
Deficient Monitoring |
The RR5 multiple tube Coliform test that was set on Sat, Oct 17th was marked completed on Sun, Oct 18th and discarded after 24 hours by mistake. It did not have the required 48 hours of incubation time. No result can be reported and this event will be documented as "Deficient Monitoring". |
Violation |
N |
eSMR |
SCWA Russian River CSD |
392149 |
R1-2014-0002 |
N |
1080748 |
09/16/2020 |
Deficient Monitoring |
No pH readings for minimum and maximum were recorded September 16 through 17. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1080747 |
09/15/2020 |
Deficient Monitoring |
Daily flow readings for Effluent Flow and Peak Flow were not recorded September 15 through 17. The reported flow readings are shown as 0. All effluent flow was diverted to EQ #3. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1080746 |
09/16/2020 |
Deficient Monitoring |
No Total Coliform sampled September 16 through 17. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1080745 |
09/16/2020 |
Deficient Monitoring |
No Total Residual Chlorine Instantaneous Maximum was recorded September 16 through 17. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1080744 |
09/15/2020 |
Deficient Monitoring |
Daily flow readings for Influent Flow and Peak Flow into the plant were not recorded September 15 through 17 while generator and PG&E power were unavailable. For these days, the reported influent flow readings were estimated using the average of five days prior and five days after the event. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
1080678 |
07/16/2020 |
Late Report |
REPORT WAS SUBMITTED PAST DUE DATE. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1080571 |
07/31/2020 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.00 mg/L and reported value was 39.00 mg/L. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1080388 |
08/31/2020 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average limit is 30 mg/L and reported value was 38 mg/L. |
Violation |
N |
Report |
SCWA Oceanic Properties Sea Ranch Central Plant |
138699 |
96-011 |
N |
1075047 |
04/12/2020 |
CTOX |
Chronic Toxicity-C.dubia-Reproduction Single Sample Maximum limit is 2 TUc and reported value was 4.6 TUc at EFF-001. |
Violation |
N |
eSMR |
Sonoma Valley County SD WWTP |
432957 |
R2-2019-0019 |
N |
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|