Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1098114 |
11/30/2021 |
Order Conditions |
Violation of Board Order R3-2004-0153 Section E. General Specifications for Reclamation and Use, No. 10, ?Recycled water pipes shall be colored purple or wrapped in purple color tape.? ? The paint on the standpipe for recycled water at the swivel ell is worn and it is not readily apparent that it is a non-potable water line. |
Violation |
None |
Inspection |
Rancho Larios WWTP |
371615 |
R3-2004-0153 |
N |
1098113 |
11/30/2021 |
Order Conditions |
Violation of Board Order R3-2004-0153 Section E. General Specifications for Reclamation and Use, No. 9, ?Permitter warning signs for the spray irrigation area shall be posted every 1250 ft. At a minimum, signs shall be posted at each corner and at access roads. Signs shall provide information consistent with the Department of Health guidelines 60310(f)?, There were no signs posted at the disposal spray field. |
Violation |
None |
Inspection |
Rancho Larios WWTP |
371615 |
R3-2004-0153 |
N |
1098112 |
11/30/2021 |
Order Conditions |
Violation of Board Order R3-2004-0153 Section E. General Specifications for Reclamation and Use, No. 7, ?All recycled water reservoirs and other areas with public access shall be posted (in English and Spanish) with signs that are visible to the public, in a size no less than 4 inches high by 8 inches wide, that include the following wording: ?Recycled Water ? Do Not Drink? ? there was no signage at the storage pond posted along the fence. |
Violation |
None |
Inspection |
Rancho Larios WWTP |
371615 |
R3-2004-0153 |
N |
1098111 |
11/30/2021 |
Order Conditions |
Violation of Board Order R3-2004-0153 Section B. Reclamation Specifications, No. 8, ?Proper backflow and cross connection protection for domestic water services and irrigation wells shall be provided? ? DDW staff mentioned the need to have a locking device on the swivel ell device and the current protection is not adequate. |
Violation |
None |
Inspection |
Rancho Larios WWTP |
371615 |
R3-2004-0153 |
N |
1098110 |
11/30/2021 |
Order Conditions |
1. Violation of Board Order R3-2004-0153 Section B. Reclamation Specifications, No. 7, ?Valves in the recycled water irrigation system shall be designed and constructed so unauthorized persons cannot open them? ? There is no locking mechanism on either valves nor the gated area of the swivel ell to prevent unauthorized persons from opening the valves. |
Violation |
None |
Inspection |
Rancho Larios WWTP |
371615 |
R3-2004-0153 |
N |
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|