Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1142434 |
03/23/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1142433 |
03/22/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1142432 |
03/21/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1142431 |
03/20/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1142430 |
03/19/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1142429 |
03/18/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1132891 |
08/09/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. *** MMP Exempt Reason:Recycled Water limitation is not subject to MMPs. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1132890 |
08/06/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. *** MMP Exempt Reason:Recycled Water limitation is not subject to MMPs. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1132889 |
08/05/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. *** MMP Exempt Reason:Recycled Water limitation is not subject to MMPs. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1129978 |
06/06/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. *** MMP Exempt Reason:Recycled Water limitation is not subject to MMPs. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1129977 |
06/05/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at REC-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1128845 |
03/22/2022 |
Order Conditions |
Based on the influent calibration records, the annual calibration of the influent Parshall flumes was overdue, as it is required on 20 January 2022. According to MRP Provision I.D of the WDRs, ?Appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to ensure the accuracy and reliability of measurements of the volume of monitored discharges. All monitoring instruments and devices used by the Discharger to fulfill the prescribed monitoring program shall be properly maintained and calibrated as necessary, at least yearly, to ensure their continued accuracy. All flow measurement devices shall be calibrated at least once per year to ensure continued accuracy of the devices.? |
Violation |
None |
Inspection |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1128844 |
03/22/2022 |
Order Conditions |
During the inspection, it was discovered that one of the UV module?s bulbs exceeded the manufacture?s recommended hours, 12,000 run hours, by 471 hours. According to the Standard Provision I.D, ?The Discharger shall, at all times, properly operate and maintain all facilities and systems of treatment and control (and related appurtenances) which are installed or used by the Discharger to achieve compliance with the conditions of this Order.? According to the Discharger, it was due to an oversight and the Discharger will replace the bulbs and update the Standard Operating Procedures (SOPs) to ensure the bulbs not exceeding the recommended hours in the future. |
Violation |
None |
Inspection |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1118209 |
05/09/2023 |
Deficient Monitoring |
On 9 May 2023, TRWQCF staff did not conduct field analysis for the plant influent (INF-001) pH grab resulting in deficient monitoring. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1116095 |
03/03/2023 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1113413 |
01/08/2023 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1112891 |
10/14/2022 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3 MPN/100 mL at EFF-001. |
Violation |
N |
Report |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1112890 |
09/04/2022 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
Violation |
N |
Report |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
Y |
1112012 |
07/31/2022 |
CAT2 |
Dibromochloromethane Monthly Average limit is 19 ug/L and reported value was 19.9 ug/L at EFF-001A. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1107226 |
01/09/2022 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001. |
Violation |
N |
Report |
Turlock City, Turlock Regional Water Quality Control Facility |
442540 |
R5-2021-0005 |
N |
1105756 |
05/29/2022 |
Deficient Monitoring |
The eSMR is missing a required results for BOD at locations INF-001 and EFF-001B for May 29, 2022. The Laboratory missed the readback time for BOD and the results for the batch were deemed unreportable. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1103440 |
03/18/2022 |
Order Conditions |
The eSMR does not include required results for BOD at location INF-001B for March 18, 20, and 21 and also at location EFF-001B for March 20, and 21, 2022 due to QC failures. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1103439 |
02/01/2022 |
Order Conditions |
In February 2022 it was discovered that the UV lamps in bank 1B of phase II were 471 hours over the manufacturer¿s specifications of 12,000 run hours. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1102742 |
02/03/2022 |
Order Conditions |
The eSMR does not include required results for BOD at location INF-001B and EFF-001B for February 3, 2022 due to an instrumentation programming failure, as well as a procedural breakdown during initial set up in the City laboratory. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1101265 |
01/17/2022 |
OEV |
Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 540 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1099777 |
12/21/2021 |
Deficient Monitoring |
The eSMR does not include required results for BOD at locations INF-001 and EFF-001B for December 21 ¿ 23, 2021. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1097361 |
10/23/2021 |
CAT2 |
Chlorine, Total Residual 4-Day Average (Mean) limit is 0.011 mg/L and reported value was .042 mg/L at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1097360 |
10/23/2021 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 4.042 mg/L at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1093909 |
02/08/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093908 |
02/07/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093907 |
02/06/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
None |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093906 |
02/05/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
None |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093905 |
02/04/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
None |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093904 |
02/03/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
None |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093903 |
02/02/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
None |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1093902 |
02/01/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 4 NTU at EFF-001A. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1092661 |
06/01/2021 |
Order Conditions |
On June 1, 2021 at 17:43 a lap in one of the UV vessels hit 12,000 run hours. This went un-noticed until June 2, 2021 at 09:43. During that 16-hour window the flow through the vessel was 635,889 gallons. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090687 |
04/29/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090686 |
04/15/2021 |
CAT1 |
Aluminum, Total Monthly Average limit is 330 ug/L and reported value was 373 ug/L at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090685 |
04/04/2021 |
Deficient Monitoring |
The eSMR does not include required weekly results for conductivity at locations DMC-001 and DMC-002 for the week of April 4, 2021. Though the required samples were collected, an error within the laboratory caused them to be discarded before analysis. Discovery of the processing error did not occur until after the week had ended, making resample impossible. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090684 |
04/26/2021 |
Order Conditions |
Turbidity Annual Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090683 |
04/23/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090682 |
04/22/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 6 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090681 |
04/21/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 8 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090680 |
04/22/2021 |
Order Conditions |
Turbidity Instantaneous Maximum limit is 10 NTU and reported value was 10 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090679 |
04/21/2021 |
Order Conditions |
Turbidity Instantaneous Maximum limit is 10 NTU and reported value was 10 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090678 |
04/15/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090677 |
04/17/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090676 |
04/13/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090675 |
04/16/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090674 |
04/27/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090673 |
04/21/2021 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.170 mg/L at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090672 |
04/28/2021 |
Order Conditions |
Turbidity Annual Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090671 |
04/14/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1090670 |
04/20/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1090669 |
04/19/2021 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
N |
1089854 |
02/03/2021 |
Order Conditions |
On 3 February 2021, the effluent turbidity was reported as 4 NTU exceeding WDRs effluent limitation of 2 NTU. |
Violation |
N |
Report |
Turlock City, Turlock Regional Water Quality Control Facility |
400734 |
R5-2015-0027 |
N |
1088690 |
12/21/2020 |
Surface Water |
According to the WDRs Provision V.A.15, ¿The natural temperature to be increased by more than 5°F. Compliance to be determined based on the difference in temperature at Monitoring Locations DMC-001 and DMC-002.¿ On 21 December 2020, the effluent caused the receiving water temperature to increase 6.5°F, which a violation of WDRs (CIWQS Violation ID #). |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1088689 |
01/09/2021 |
CAT1 |
Total Suspended Solids (TSS) Daily Maximum limit is 2400 lb/day and reported value was 3175 lb/day at EFF-001B. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1088688 |
01/05/2021 |
CAT1 |
Total Suspended Solids (TSS) Daily Maximum limit is 20 mg/L and reported value was 39 mg/L at EFF-001B. |
Violation |
N |
Report |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1088226 |
02/12/2021 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.065 mg/L at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1086918 |
01/13/2021 |
Order Conditions |
Turbidity Instantaneous Maximum limit is 10 NTU and reported value was 10 NTU at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1083368 |
11/21/2020 |
OEV |
Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 1600 MPN/100 mL at EFF-001A. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1082465 |
10/21/2020 |
OEV |
Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 1600 MPN/100 mL at REC-001. *** MMP Exempt Reason:Recycled Water violation not Subject to MMP. |
Violation |
N |
eSMR |
Turlock City, Turlock Regional Water Quality Control Facility |
400734 |
R5-2015-0027 |
N |
1082168 |
10/06/2020 |
Deficient Monitoring |
The eSMR for October 2020 does not include Flow results at location INF-001 from October 6-7, 2020. The City of Modesto¿s Ignition SCADA system had an issue with the vendor database server on October 6th, 2020, which interrupted data collection. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1078916 |
07/06/2020 |
Deficient Monitoring |
The eSMR is missing a result for BOD, TSS and Hardness at location EFF-001B for July 6, 2020. The composite sampler at the site suffered a malfunction overnight leaving little volume that was not representative of the discharge. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |
1077487 |
06/05/2020 |
Deficient Monitoring |
June 5, 2020 the BOD and TSS sample at INF-001 was collected as a grab sample instead of a composite as required by the permit. The composite sample collected was inadvertently discarded in the laboratory as it was mistaken for a previously analyzed sample. |
Violation |
N |
eSMR |
North Valley Regional Recycled Water Program - Modesto WWTP & Turlock RWQCF |
405123 |
R5-2016-0010 |
Y |