Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1139584 |
12/12/2024 |
CAT1 |
Boron, Total Monthly Average limit is 1.5 mg/L and reported value was 2.6 mg/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1139583 |
11/14/2024 |
Deficient Monitoring |
Dioxins and Furans samples were missed because the lab did not send the bottles with the original bottle shipment. DWR requested dioxin bottles, but the lab was not able to provide bottles before November ended. The January 2024 - October 2024 dioxin results for all monitoring stations are non-detect. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1139582 |
11/14/2024 |
Deficient Monitoring |
Dioxins and Furans samples were missed because the lab did not send the bottles with the original bottle shipment. DWR requested dioxin bottles, but the lab was not able to provide bottles before November ended. The January 2024 - October 2024 dioxin results for all monitoring stations are non-detect. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1139581 |
12/12/2024 |
CAT2 |
Chlorine, Total Residual Daily Maximum limit is 0.1 mg/L and reported value was 0.11 mg/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1134979 |
08/22/2024 |
OEV |
pH Instantaneous Maximum limit is 8.7 SU and reported value was 9.0 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1134978 |
07/25/2024 |
OEV |
Temperature Daily Maximum limit is 80 Degrees F and reported value was 84.2 Degrees F at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1134977 |
09/12/2024 |
OEV |
Temperature Instantaneous Maximum limit is 80 Degrees F and reported value was 80.96 Degrees F at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1130201 |
04/25/2024 |
CAT2 |
Copper, Total Monthly Average limit is 29 ug/L and reported value was 35 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1127271 |
07/31/2022 |
CAT2 |
Copper, Total Recoverable Monthly Average (Mean) limit is 24 ug/L and reported value was 80 ug/L at EFF-002. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1126974 |
03/31/2024 |
Deficient Monitoring |
The following parameters were not analyzed, despite discharge being reported, for the month of March 2024: BOD, Chloride, Total Residual Chlorine, Nitrate + Nitrite, Copper, Boron, Lead, Mercury, Zinc, Dibromochloromethane, Dichlorobromomethane, Tetrachloroethylene, Bis(2-ethylhexyl) Phthalate, Chloroform, Total Trihalomethanes, and TCDD. |
Violation |
N |
Report |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1126973 |
03/31/2024 |
Deficient Monitoring |
The following parameters were not analyzed, despite discharge being reported, for the month of March 2024: BOD, Chloride, Copper, Boron, Mercury, Bis(2-ethylhexyl) Phthalate, and TCDD. |
Violation |
N |
Report |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
N |
1121323 |
09/21/2023 |
OEV |
pH Daily Maximum limit is 8.8 SU and reported value was 8.9 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1121322 |
08/24/2023 |
OEV |
Temperature Daily Maximum limit is 80 Degrees F and reported value was 81.86 Degrees F at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1121321 |
07/20/2023 |
OEV |
Temperature Daily Maximum limit is 80 Degrees F and reported value was 81.5 Degrees F at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1118972 |
05/31/2023 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 29 ug/L and reported value was 48 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1118971 |
06/30/2023 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 29 ug/L and reported value was 35 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1112929 |
11/17/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.8 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
446992 |
R4-2022-0237 |
Y |
1109475 |
08/25/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 9.4 SU at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1109474 |
07/28/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 9.2 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1109473 |
07/28/2022 |
CAT2 |
Copper, Total Recoverable Daily Maximum limit is 79 ug/L and reported value was 80 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1109472 |
08/25/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 9.4 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1106481 |
05/19/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1106480 |
06/23/2022 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1103169 |
11/02/2021 |
Late Report |
Report was submitted 1 day late. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1103167 |
08/30/2021 |
CTOX |
Chronic Toxicity-C.dubia-Reproduction Maximum Daily (MDEL) limit is 0.0 Pass/Fail (Pass = 0, Fail = 1) and reported value was 0.0 Pass/Fail (Pass = 0, Fail = 1) at EFF-001 (A & B). |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1103131 |
06/30/2021 |
Deficient Monitoring |
The facility experienced a power outage due to State Water Project Operations Control management which provides daily water and power operation schedules. Therefore, certain parameters were not sampled for June 2021. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1103130 |
06/30/2021 |
Deficient Monitoring |
The facility experienced a power outage due to State Water Project Operations Control management which provides daily water and power operation schedules. Therefore, certain parameters were not sampled for June 2021. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1103129 |
06/30/2021 |
Deficient Monitoring |
The facility experienced a power outage due to State Water Project Operations Control management which provides daily water and power operation schedules. Therefore, monthly parameters were not sampled for June 2021. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1103128 |
06/30/2021 |
Deficient Monitoring |
The facility experienced a power outage due to State Water Project Operations Control management which provides daily water and power operation schedules. Therefore, monthly parameters were not sampled for June 2021. |
Violation |
N |
Report |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1099914 |
11/30/2021 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 24 ug/L and reported value was 38 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1096144 |
07/22/2021 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1096143 |
09/27/2021 |
CTOX |
Chronic Toxicity-C.dubia-Reproduction Monthly Median limit is 0.0 Pass/Fail (Pass = 0, Fail = 1) and reported value was 1.0 Pass/Fail (Pass = 0, Fail = 1) at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1096142 |
08/12/2021 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1096141 |
07/22/2021 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1096140 |
08/30/2021 |
CTOX |
Chronic Toxicity-C.dubia-Reproduction Monthly Median limit is 0.0 Pass/Fail (Pass = 0, Fail = 1) and reported value was 1.0 Pass/Fail (Pass = 0, Fail = 1) at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1092283 |
05/26/2021 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1088717 |
02/18/2021 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1084511 |
11/23/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1084510 |
12/17/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1084509 |
12/17/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1084508 |
10/07/2020 |
Deficient Monitoring |
Unit one was down for maintenance during the entire month of October. Samples were not collected in October due to maintenance work conducted at power plant. Discharge numbers have been reduced since the start of maintenance work. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1084507 |
10/07/2020 |
Deficient Monitoring |
Unit one was down for maintenance during the entire month of October. Samples were not collected in October due to maintenance work conducted at power plant. Discharge numbers have been reduced since the start of maintenance work. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1084506 |
10/07/2020 |
Deficient Monitoring |
Unit one was down for maintenance during the entire month of October. Samples were not collected in October due to maintenance work conducted at power plant. Discharge numbers have been reduced since the start of maintenance work. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1084505 |
10/07/2020 |
Deficient Monitoring |
Unit one was down for maintenance during the entire month of October. Samples were not collected in October due to maintenance work conducted at power plant. Discharge numbers have been reduced since the start of maintenance work. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1080557 |
07/30/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 9.5 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1080556 |
08/20/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.7 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1080555 |
09/17/2020 |
CAT2 |
Copper, Total Monthly Average (Mean) limit is 24 ug/L and reported value was 38 ug/L at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1080554 |
07/30/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 9.5 SU at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1077663 |
05/27/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.6 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
N |
1077662 |
06/03/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.8 SU at EFF-002. |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
1077661 |
06/03/2020 |
OEV |
pH Instantaneous Maximum limit is 8.5 SU and reported value was 8.8 SU at EFF-001 (A & B). |
Violation |
N |
eSMR |
William E Warne Power Plant |
399606 |
R4-2016-0224 |
Y |
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|