Party ID Party Name Party Classification Mailing Address Work Phone Email/Website
551798 Dutra Farms, Inc. Privately-Owned Business 5501 West Ripon Road Manteca, CA 95337 None None
  
  
  
  
Expand/Contract Related Places
Related Places
Place ID Place Name County Region Place Type Relationship to Party Relationship Start Date Relationship End Date
239343 City of Manteca WW Quality Control Facility San Joaquin 5S Wastewater Treatment Facility None None None
Total Related Places: 1
  
  
  
  
Expand/Contract Related Parties
Related Parties
Party ID Party Name Party Type Role/Relationship Relationship Start Date Relationship End Date Classification
Total Related Parties: 0
  
  
  
  
Expand/Contract Regulatory Measures
Regulatory Measures (non-enforcement)
Reg. Measure ID Regulatory Measure Type Region WDID Status Program Order No. RM Effective Date RM Termination Date Relationship Relationship Start Date Relationship End Date Amended?
400860 NPDES Permit 5S 5B390104001 Historical NPDMUNILRG R5-2015-0026 06/01/2015 03/31/2021 Discharger 06/23/2015 None N
Total Regulatory Measures: 1
  
  
  
  
Expand/Contract Violations
Violations within the past five years
Violation ID Occurrence Date Violation Type Violation Description(-) Violation Status Priority Source Facility Name Violated Reg. Meas. ID Violated Reg. Meas. Order No. Linked to Enf.
1061699 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report BOD mg/L. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1061700 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report BOD LBS. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1061698 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report TSS % removal. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1061701 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report BOD % removal. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1061697 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report TSS LBS. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1061696 06/21/2019 Deficient Monitoring Flow to River was halted on the afternoon of 6/20/2019 for UV maintenance. Flow to River was restored the morning of 6/21/2019 and composite sampler for EFF-001 was resumed. Collection of EFF-001 composite sample did not occur on 6/21/2019 at end of day and was collected the morning of 6/22/2019. This resulted in not having an EFF-001 composite sample for 6/21/2019. Failure to report TSS mg/L. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1080874 09/03/2020 Deficient Monitoring Lnd-001 sample collected on 9-3-2020 @ 9:28am was not preserved and stored in the lab for total kjeldahl nitrogen. Due to this missed sample preservation and storage, total nitrogen cannot be calculated and report for Lnd-001 on 9-3-2020 Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
1066039 09/29/2019 OEV Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23 MPN/100 mL and reported value was 41 MPN/100 mL at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1086799 01/26/2021 OEV Temperature Daily Average (Mean) limit is 20 Degrees F and reported value was 21 Degrees F at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1068528 11/27/2019 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.3 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1092818 12/02/2020 OEV Temperature Daily Average (Mean) limit is 20 Degrees F and reported value was 21 Degrees F at EFF-001. Violation N Report City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1070243 12/05/2019 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.4 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1068529 11/28/2019 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.4 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1070244 12/04/2019 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.4 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1083256 11/08/2020 OEV Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23.0 MPN/100 mL and reported value was 46.0 MPN/100 mL at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1068527 11/23/2019 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.3 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1070245 12/03/2019 OEV pH Instantaneous Maximum limit is 6.5 SU and reported value was 6.3 SU at EFF-001. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1084107 11/08/2020 Order Conditions On November 8, 2020 the REC-001 total coliform was 46 MPN/100ml which was the second total coliform within 30 days to exceed 23 MPN/100ml as required in IV.C.4.i.ii. The first total coliform over 23 MPN/100ml was on October 20, 2020 which was 33 MPN/100ml. Violation N eSMR City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1071491 02/12/2020 Order Conditions During the inspection, Board staff noted that the internal temperature of the influent composite sampler read 14.5°C. WDRs Standard Provision III.B requires the Discharger to conduct sampling in accordance with 40 CFR Part 136 which specifies sample preservation temperature of 4˚C + 2˚ for proper preservation. Since the influent composite sampler is not maintained within the required temperature range, it does not meet sample preservation requirements, in violation of Standard Provision III.B. Violation N Inspection City of Manteca WW Quality Control Facility 400860 R5-2015-0026 Y
1071492 02/12/2020 Order Conditions Board staff noted that temperature measurements since 1 January 2020 have not been maintained within the required temperature range, as recorded in the logbook inside the composite sampler. WDRs Standard Provision I.D requires the Discharger to properly operate and maintain all facilities and systems of treatment and control. Proper operation and maintenance also includes adequate laboratory controls and appropriate quality assurance procedures. Board staff assert that the Facility staff have not been properly trained and do not have adequate knowledge of sample preservation; therefore, the Discharger is in violation of Standard Provision I.D. Violation N Inspection City of Manteca WW Quality Control Facility 400860 R5-2015-0026 N
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 20
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
  
  
  
  
Expand/Contract Enforcement Actions
Enforcement Actions
Enforcement ID Enforcement Type Enf. Order No. Title Program Effective Date Status
416773 Notice of Violation None NOV 10/17/2017 for City of Manteca, Dutra Farms, Inc., Secondary Wastewater Spill NPDMUNILRG 10/17/2017 Historical
436607 Notice of Violation None NOV 01/31/2020 for Dutra Farms, Inc. NPDMUNILRG 01/31/2020 Historical
409650 Notice of Violation None NOV 10/06/2016 for Dutra Farms, Inc. NPDMUNILRG 10/06/2016 Historical
437246 Notice of Violation None NOV 03/05/2020 for Dutra Farms, Inc. NPDMUNILRG 03/05/2020 Historical
420814 Notice of Violation None NOV 04/10/2018 for Dutra Farms, Inc. NPDMUNILRG 04/10/2018 Historical
406357 Notice of Violation None NOV 05/23/2016 for Secondary WW Spill NPDMUNILRG 05/23/2016 Historical
449651 Notice of Violation None NOV 08/06/2021 for Dutra Farms, Inc. NPDMUNILRG 08/06/2021 Historical
433696 Notice of Violation None NOV 08/05/2019 for Dutra Farms, Inc. NPDMUNILRG 08/05/2019 Historical
423335 Notice of Violation None NOV 08/07/2018 for Dutra Farms, Inc. NPDMUNILRG 08/07/2018 Historical
428517 Notice of Violation None NOV 01/28/2019 for Dutra Farms, Inc. NPDMUNILRG 01/28/2019 Historical
429345 Notice of Violation None NOV 03/11/2019 for Dutra Farms, Inc. NPDMUNILRG 03/11/2019 Historical
413077 Notice of Violation None NOV 05/02/2017 for Manteca City NPDMUNILRG 05/02/2017 Historical
435527 Admin Civil Liability R5-2019-0534 ACL R5-2019-0534 for Dutra Farms, Inc. NPDMUNILRG 12/24/2019 Historical
425521 Admin Civil Liability R5-2018-0524 ACL R5-2018-0524 for Dutra Farms, Inc. NPDMUNILRG 11/16/2018 Historical
438223 Admin Civil Liability R5-2020-0525 ACL R5-2020-0525 for Dutra Farms, Inc. NPDMUNILRG 08/04/2020 Historical
433154 Admin Civil Liability R5-2019-0512 ACL R5-2019-0512 for Dutra Farms, Inc. NPDMUNILRG 08/27/2019 Historical
Total Enforcement Actions: 16
  
  
  
  
Expand/Contract Enforcement Actions
Regulatory Measures linked to Related Parties
Reg. Measure ID Organization Regulatory Measure Type Program Effective Date Status
Total Regulatory Measures linked to Related Parties: 0
  
  
The current report was generated with data as of: 05/16/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.