| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(+) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1153824 |
01/12/2026 |
Deficient Monitoring |
Operator failed to monitor D.O. in pond. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1153823 |
01/31/2026 |
CAT1 |
Nitrogen, Total (as N) Monthly Average limit is 10 mg/L and reported value was 1 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1153822 |
03/25/2026 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 28 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1153821 |
03/21/2026 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 41 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1153820 |
02/25/2026 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 34 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1153819 |
01/27/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Daily Maximum limit is 20 mg |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150872 |
12/29/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 0 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150871 |
12/29/2025 |
Deficient Monitoring |
Operator forgot to sample for dissolved oxygen. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150870 |
12/27/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 41 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150869 |
12/26/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 17 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150868 |
12/25/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 24 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150867 |
12/24/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 24 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150866 |
12/17/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 58 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150865 |
12/12/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 75 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150864 |
12/08/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 64 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150863 |
12/25/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was .524 NTU at UV-00 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150862 |
12/17/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.125 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150861 |
12/16/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 7.708 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150860 |
12/15/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.296 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150859 |
12/14/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.21 NTU at UV-00 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150858 |
12/13/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.023 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150857 |
12/11/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was .992 NTU at UV-00 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150856 |
12/12/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.095 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150855 |
12/10/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 7.708 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150854 |
12/09/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.157 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150853 |
12/08/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was .997 NTU at UV-00 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150852 |
12/07/2025 |
OEV |
Turbidity Daily Maximum limit is .5 NTU and reported value was 1.1054 NTU at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150851 |
12/16/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .359 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150850 |
12/15/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .522 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150849 |
12/14/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .449 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150848 |
12/13/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .549 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150847 |
12/12/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .545 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150846 |
12/11/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .492 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150845 |
12/10/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .433 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150844 |
12/09/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .456 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150843 |
12/08/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .377 NTU a |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150842 |
12/07/2025 |
OEV |
Turbidity Daily Average (Mean) limit is .2 NTU and reported value was .32 NTU at |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150841 |
12/31/2025 |
CAT1 |
Nitrogen, Total (as N) Monthly Average (Mean) limit is 10 mg/L and reported valu |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150840 |
11/18/2025 |
CAT1 |
UV Transmittance Daily Minimum limit is 53.6 % and reported value was 25.16 % at |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150839 |
10/16/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 24 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150838 |
10/15/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 1 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150837 |
10/13/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 62 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150836 |
10/18/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 27 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150835 |
11/08/2025 |
OEV |
Total Coliform Monthly Maximum limit is 240 MPN/100 mL and reported value was 29 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150834 |
11/12/2025 |
Deficient Monitoring |
Operator forgot to sample for dissolved oxygen. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1150833 |
11/02/2025 |
Deficient Monitoring |
Operator forgot to sample dissolved oxygen. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148959 |
09/14/2025 |
Deficient Monitoring |
Operator forgot to record D.O. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148958 |
09/20/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 0 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148957 |
09/12/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 0 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148956 |
09/10/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 65 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148955 |
09/02/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 4 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148954 |
07/05/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 55 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148953 |
07/29/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 62 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148952 |
08/30/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 62 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148951 |
07/09/2025 |
CAT1 |
UV Transmittance Daily Minimum limit is 53.6 % and reported value was 52.56 % at |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148950 |
09/14/2025 |
Deficient Monitoring |
Operator forgot to record D.O. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148949 |
09/30/2025 |
CAT1 |
Nitrogen, Total (as N) Monthly Average limit is 10 mg/L and reported value was 2 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148948 |
09/07/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 48 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1148947 |
07/22/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 0 mJ/cm2 at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1145445 |
05/30/2025 |
OEV |
Turbidity Daily Minimum limit is .5 NTU and reported value was 2.759 NTU at UV-0 |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1145444 |
06/04/2025 |
Deficient Monitoring |
Contracted lab personnel failed to pick up coliform sample. |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
| 1145442 |
06/12/2025 |
CAT1 |
UV Dose Daily Minimum limit is 80 mJ/cm2 and reported value was 64 mJ/cm2 at UV- |
Violation |
N |
eSMR |
Visalia Water Reclamation Facility (WRF) |
409518 |
R5-2018-0046 |
N |
|
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|