Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1143976 |
04/13/2025 |
Late Report |
King City WWTF violated Existing Permit Section VI.D by failing to submit the Time Schedule Compliance Plan due April 12, 2025. |
Violation |
None |
Report |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143975 |
04/13/2025 |
Late Report |
King City WWTF violated Existing Permit Section VI.D by failing to submit the Operations and Maintenance Manual due April 12, 2025. |
Violation |
None |
Report |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143974 |
03/02/2025 |
Late Report |
King City WWTF violated Existing Permit Section VI.D by failing to submit the 2024 Annual Report due March 1, 2025. |
Violation |
None |
Report |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143971 |
08/28/2024 |
Order Conditions |
[2 Violations] King City failed to maintain enough working aerators in Ponds 1 and 3 of the WWTF to provide sufficient aeration, thereby violating Section VI.B.4 of the existing permit. During the inspection on August 28, 2024, some of the aerators were non-functional and needed to be repaired. King City also violated Existing Permit Section VI.B.4 by not having a functioning effluent meter at the WWTF. |
Violation |
None |
Inspection |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143969 |
08/28/2024 |
Order Conditions |
King City violated Existing Permit section IV.E.1 by failing to appropriately manage sludge in the ponds. |
Violation |
None |
Inspection |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143967 |
08/28/2024 |
Order Conditions |
King City violated Existing Permit section IV.B.4 by failing to minimize weeds and debris along the banks of Ponds 1 and 2. |
Violation |
N |
Inspection |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
Y |
1143508 |
01/15/2025 |
Groundwater |
Sulfate Instantaneous Maximum limit is 205 mg/L and reported value was 238 mg/L at MW #6. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143507 |
01/15/2025 |
Hydro Modification |
Sulfate Instantaneous Maximum limit is 205 mg/L and reported value was 220 mg/L at MW #5. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143506 |
01/15/2025 |
Groundwater |
Total Kjeldahl Nitrogen (TKN) Instantaneous Maximum limit is 2.2 mg/L and reported value was 5.3 mg/L at MW #2. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143505 |
01/15/2025 |
Groundwater |
Total Dissolved Solids (TDS) Instantaneous Maximum limit is 990 mg/L and reported value was 2790 mg/L at MW #1. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143504 |
01/15/2025 |
Groundwater |
Sulfate Instantaneous Maximum limit is 205 mg/L and reported value was 1090 mg/L at MW #1. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143503 |
01/15/2025 |
Groundwater |
Nitrate Instantaneous Maximum limit is 8 mg/L and reported value was 142 mg/L at MW #1. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143502 |
01/15/2025 |
Groundwater |
Chloride Instantaneous Maximum limit is 250 mg/L and reported value was 251 mg/L at MW #1. |
Violation |
N |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1143409 |
03/11/2025 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average limit is 30 mg/L and reported value was 32 mg/L. |
Violation |
N |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1143408 |
02/06/2025 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average limit is 30 mg/L and reported value was 37 mg/L. |
Violation |
N |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1143407 |
01/15/2025 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average limit is 37 mg/L and reported value was 30 mg/L. |
Violation |
N |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1143406 |
03/11/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 30 mg/L and reported value was 70 mg/L. |
Violation |
N |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1143405 |
02/06/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 30 mg/L and reported value was 37 mg/L. |
Violation |
N |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1143234 |
12/31/2024 |
Order Conditions |
Freeboard Other limit is 2 feet and reported value was 0.97 feet. |
Violation |
None |
Report |
Dole Fresh Vegetables, Inc. |
399691 |
R3-2004-0066 |
N |
1143213 |
02/27/2025 |
CAT1 |
Sodium, Total Instantaneous Maximum limit is 125.0 mg/L and reported value was 152.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1143210 |
01/13/2025 |
CAT1 |
Sodium, Total Instantaneous Maximum limit is 125.0 mg/L and reported value was 152.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1143209 |
01/13/2025 |
CAT1 |
Chloride Instantaneous Maximum limit is 125.0 mg/L and reported value was 160.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1143207 |
01/13/2025 |
CAT1 |
Total Dissolved Solids (TDS) Instantaneous Maximum limit is 600.0 mg/L and reported value was 740.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1142951 |
03/31/2025 |
CAT1 |
Chloride Monthly Average limit is 250.0 mg/L and reported value was 426.0 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1142950 |
03/31/2025 |
CAT1 |
Sodium, Total Monthly Average limit is 250.0 mg/L and reported value was 269.0 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1142258 |
11/08/2024 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Daily Maximum limit is 10.0 mg/L and reported value was 12.0 mg/L. |
Violation |
None |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1142256 |
08/04/2024 |
CAT1 |
Nitrate, Total (as N) Daily Maximum limit is 5.0 mg/L and reported value was 5.5 mg/L. |
Violation |
None |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1142255 |
08/04/2024 |
Groundwater |
Nitrate limit is 2.2 mg/L. Reported value was 152 mg/L. |
Violation |
None |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1142157 |
09/29/2024 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Daily Maximum limit is 10.0 mg/L and reported value was 12.0 mg/L. |
Violation |
None |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1141146 |
10/01/2024 |
CAT1 |
Chloride Other limit is 250.0 mg/L and reported value was 464.4 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1141145 |
10/01/2024 |
CAT1 |
Sodium, Total Other limit is 250.0 mg/L and reported value was 298.7 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1141023 |
08/28/2024 |
Order Conditions |
Failure to properly maintain electrical and mechanical equipment |
Violation |
None |
Inspection |
San Lucas WWTF |
144125 |
89-076 |
Y |
1141022 |
08/28/2024 |
Order Conditions |
Failure to prevent formation of habitat for carriers of pathogenic microorganisms in any part of the treatment and disposal system |
Violation |
None |
Inspection |
San Lucas WWTF |
144125 |
89-076 |
Y |
1141021 |
08/28/2024 |
Order Conditions |
Failure to properly operate and maintain all facilities and systems of treatment and control |
Violation |
N |
Inspection |
San Lucas WWTF |
144125 |
89-076 |
Y |
1140346 |
08/23/2024 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 45 mg/L and reported value was 48 mg/L. |
Violation |
N |
Report |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
N |
1140344 |
10/01/2024 |
Deficient Reporting |
No effluent flow readings for Q3. A meter has not been installed. |
Violation |
N |
Report |
King City Domestic WWTF |
456568 |
R3-2020-0020 |
N |
1140103 |
10/09/2024 |
Groundwater |
Exceedances at Well #1 of Nitrate (105 mg/L), Sulfate (927 mg/L), pH (6.2) and TDS (2560 mg/l). Exceedances at Well #2 of Kjeldahl Nitrogen (5.5 mg/L) and total Nitrogen (5.5 mg/l). Exceedance at Well #6 of Sulfate (223 mg/l). Exceedance at Well #7 of sulfate (233 mg/L) and Coliform (4 MPN/100 ml). Exceedance at Well #8 of sulfate (233 mg/L). Exceedance at Well #9 of sulfate (238 mg/L) and Coliform (4 MPN/100 ml). |
Violation |
None |
Report |
Soledad WWTP |
349587 |
R3-2008-0042 |
N |
1139917 |
12/31/2024 |
Groundwater |
Nitrate (as N) exceeded limit of 10 mg/L in MW-1, MW-2, and MW-4 with levels of 120, 62, and 27 mg/L respectively. |
Violation |
N |
Report |
Moonglow Dairy--Moss Landing |
131133 |
01-033 |
N |
1139916 |
12/31/2024 |
Groundwater |
Total Dissolved Solids exceeded limit of 4,000 mg/L in MW-1 with levels of 4,250 mg/L. |
Violation |
N |
Report |
Moonglow Dairy--Moss Landing |
131133 |
01-033 |
N |
1139872 |
10/31/2024 |
CAT1 |
Chloride Monthly Average limit is 250.0 mg/L and reported value was 440.0 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1139871 |
10/31/2024 |
CAT1 |
Sodium, Total Monthly Average limit is 250.0 mg/L and reported value was 283.0 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1139763 |
12/18/2024 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average of Daily Averages limit is 60.0 mg/L and reported value was 140.0 mg/L. |
Violation |
None |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1139762 |
12/18/2024 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average of Daily Averages limit is 60.0 mg/L and reported value was 196.0 mg/L. |
Violation |
None |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1139761 |
10/30/2024 |
CAT1 |
Total Suspended Solids (TSS) 30-Day Average of Daily Averages limit is 60.0 mg/L and reported value was 245.0 mg/L. |
Violation |
None |
Report |
PRUNETREE SHOPPING CENTER Onsite WW Treatment System |
304606 |
97-010-DWQ |
N |
1139274 |
10/10/2024 |
CAT1 |
Chloride Instantaneous Maximum limit is 125.0 mg/L and reported value was 160.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1139273 |
10/10/2024 |
CAT1 |
Sodium, Total Instantaneous Maximum limit is 125.0 mg/L and reported value was 152.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1139272 |
10/10/2024 |
CAT1 |
Total Dissolved Solids (TDS) Instantaneous Maximum limit is 600.0 mg/L and reported value was 920.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1136831 |
09/19/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.0 mg/L and reported value was 44.0 mg/L. |
Violation |
None |
Report |
Pfeiffer Big Sur State Park WWTP |
147285 |
98-062 |
N |
1135204 |
10/09/2024 |
CAT1 |
Sodium, Total Monthly Average limit is 250.0 mg/L and reported value was 297.0 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1135203 |
10/01/2024 |
CAT1 |
Chloride Monthly Average limit is 250.0 mg/L and reported value was 460 mg/L. |
Violation |
None |
Report |
California Utilities |
446382 |
R3-2020-0020 |
N |
1134666 |
07/18/2024 |
CAT1 |
Chloride Instantaneous Maximum limit is 125.0 mg/L and reported value was 379 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1134665 |
07/18/2024 |
CAT1 |
Sodium, Total Instantaneous Maximum limit is 125.0 mg/L and reported value was 219.0 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1134664 |
07/18/2024 |
CAT1 |
Total Dissolved Solids (TDS) Instantaneous Maximum limit is 600.0 mg/L and reported value was 840 mg/L. |
Violation |
None |
Report |
Pasadera Reclamation Facility (Producer) |
147281 |
98-058 |
N |
1132995 |
08/31/2024 |
Deficient Monitoring |
Installation of a new flow meter will require extensive planning and coordination. The work will require cutting into the industrial force main and using heavy lifting equipment. Production of the industrial facility will be disrupted during the period of work. Work has been deferred to later this year 2024. |
Violation |
N |
Report |
King City Industrial WWTF |
147377 |
91-084 |
N |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|