Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1123148 |
12/08/2023 |
Order Conditions |
The measured values for Iron from the sample collected 12/8/2023 at discharge point EFF-001 exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1123146 |
12/08/2023 |
Order Conditions |
The measured values for Aluminum from the sample collected 12/8/2023 at discharge point EFF-001 exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1123149 |
12/21/2023 |
Order Conditions |
The measured values for Iron from the sample collected 12/8/2023 at discharge point EFF-001 exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1123147 |
12/21/2023 |
Order Conditions |
The measured values for Aluminum from the sample collected 12/8/2023 at discharge point EFF-001 exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1124333 |
01/03/2024 |
Order Conditions |
The measured value for total Iron from the samples collected at discharge point EFF-001 on 1/3/2024 was 4310 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1124331 |
01/03/2024 |
Order Conditions |
The allowed increase in receiving water turbidity was exceeded. The allowed increase in receiving water turbidity based on the RSW-001 sample result of 5.23 ntu was a 20% increase. The RSW-002 sample result was 8.1 ntu which was an increase of 54%. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1124332 |
01/03/2024 |
Order Conditions |
The measured value for total aluminum from the samples collected at discharge point EFF-001 on 1/3/2024 was 5620 ug/L, which exceeded the Storm Water Action Level 750 ug/L |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1124330 |
01/19/2024 |
Order Conditions |
The measured value for total iron from the samples collected at discharge point EFF-001 on 1/19/2024 was 2410 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1124329 |
01/19/2024 |
Order Conditions |
The measured value for total Aluminum from the samples collected at discharge point EFF-001 on 1/19/2024 was 2890 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125104 |
02/01/2024 |
Order Conditions |
The measured value for total iron from the samples collected at discharge point EFF-001 on 2/1/2024 was3080 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125105 |
02/01/2024 |
Order Conditions |
The measured value for total aluminum from the samples collected at discharge point EFF-001 on 2/1/2024 was 3650 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125100 |
02/01/2024 |
Order Conditions |
The allowed increase in receiving water turbidity was exceeded. The allowed increase in receiving water turbidity based on the RSW-001 samples result of 3.48 NTUs is + 1 NTU. The RSW-002 sample result was 5.76 NTUs, which was an increase of 2.26 NTUs. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125101 |
02/14/2024 |
Order Conditions |
The measured valued for total iron from the samples collected at discharge point EFF-001 on 2/14/2024 was 1480 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125102 |
02/14/2024 |
Order Conditions |
The measured value for total aluminum from the samples collected at discharge point EFF-001 on 2/14/2024 was 1670 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1125103 |
02/14/2024 |
Order Conditions |
The allowed increase in receiving water turbidity was exceeded. The allowed increase in receiving water turbidity based on the RSW-001 samples result of 2.82 NTU is +1 NTU. The RSW-002 sample result of 4.31 NTUs is an increase of 1.49 NTUs. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1126204 |
03/14/2024 |
Order Conditions |
The measured value for total aluminum from the samples collected at discharge point EFF-001 on 3/14/2024 was 2600 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1126202 |
03/14/2024 |
Order Conditions |
The measured value for total iron from the samples collected at discharge point EFF-001 on 3/14/2024 was 2300 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1126203 |
03/27/2024 |
Order Conditions |
The measured value for total aluminum from the samples collected at discharge point EFF-001 on 3/27/2024 was 1270 ug/l, which exceeded the Storm water action level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1126201 |
03/27/2024 |
Order Conditions |
The measured value for total iron from the samples collected at discharge point EFF-001 on 3/27/2024 was 1350 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1127064 |
04/03/2024 |
Order Conditions |
The measured value for total Iron from the samples collected at discharge point EFF-001 on 4/3/2024 was 1230 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1127066 |
04/03/2024 |
Order Conditions |
The measured value for total Aluminum from the samples collected at discharge point EFF-001 on 4/3/2024 was 1480 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1127063 |
04/18/2024 |
Order Conditions |
The measured value for total Aluminum from the samples collected at discharge point EFF-001 on 4/18/2024 was 920 ug/L, which exceeded the Storm Water Action Level of 750 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
1127065 |
04/18/2024 |
Order Conditions |
The measured value for total Iron from the samples collected at discharge point EFF-001 on 4/18/2024 was 1010 ug/L, which exceeded the Storm Water Action Level of 1000 ug/L. |
Violation |
N |
eSMR |
Burney Cogeneration/Sawmill |
433220 |
R5-2019-0048 |
N |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|