Party ID Party Name Party Classification Mailing Address Work Phone Email/Website
520971 Michael Fischer 11020 Sun Center Drive 200 Rancho Cordova, CA 95670 916-464-4663 MFischer@waterboards.ca.gov
  
  
  
  
Expand/Contract Related Places
Related Places
Place ID Place Name County Region Place Type Relationship to Party Relationship Start Date Relationship End Date
Total Related Places: 0
  
  
  
  
Expand/Contract Related Parties
Related Parties
Party ID Party Name Party Type Role/Relationship Relationship Start Date Relationship End Date Classification
137762 Central Valley Regional Water Quality Control Board, Sacramento Office Organization Employee 02/02/2010 None Waterboard
Total Related Parties: 1
  
  
  
  
Expand/Contract Regulatory Measures
Regulatory Measures (non-enforcement)
Reg. Measure ID Regulatory Measure Type Region WDID Status Program Order No. RM Effective Date RM Termination Date Relationship Relationship Start Date Relationship End Date Amended?
Total Regulatory Measures: 0
  
  
  
  
Expand/Contract Violations
Violations within the past five years
Violation ID Occurrence Date Violation Type Violation Description(-) Violation Status Priority Source Facility Name Violated Reg. Meas. ID Violated Reg. Meas. Order No. Linked to Enf.
1141646 02/03/2025 Deficient Monitoring Effluent pH readings were bad/invalid for approximately 26 minutes following routine maintenance of pH analyzers. The redundant pH analyzer was being cleaned at the time of the incident. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 N
1131471 07/10/2024 Deficient Monitoring Echowater Facility lost continuous monitoring of the EFF-001 for approximately 8 minutes when a contractor working on upgrading the Emerson Ovation Plant Computer Control System made an error and connected a wire to the wrong system. Operations immediately diverted discharge from the river; however, it takes approximately 8 minutes for the valve to close. The dechlorination process continued to operate automatically by a local Programmable Logic Controller, and an area operator at that location manually checked and ensured all values remained within compliance with the permit; however, the 8 minutes of lost data could not be recovered. See cover letter for additional details. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1115051 02/01/2023 CAT2 Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.018 mg/L and reported value was 0.28 mg/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1114028 01/07/2023 CAT1 Settleable Solids Weekly Average limit is 0.2 ml/L and reported value was 0.5 ml/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1114027 01/31/2023 CAT2 Copper, Total Monthly Average limit is 7.4 ug/L and reported value was 8.3 ug/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1112739 12/02/2022 Deficient Monitoring Loss of continuous effluent monitoring for CL2, SO3, DO, pH for 1 minute and 20 seconds due to operator error. Operator was working on redundant sample pump and accidently opened a bypass valve that caused a loss of flow from the in service pump. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1111086 05/31/2022 Deficient Monitoring Effluent total residual chlorine, sulfur dioxide, sodium bisulfite, temperature, pH, DO, influent pH and emergency storage freeboard was not recorded due to a data server capacity issue for 2.75 hours on 3 May 2022 and for 5 hours on 4 May 2022. The issue has been resolved. Violation N Report EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1110656 10/06/2022 CAT2 Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.018 mg/L and reported value was 0.086 mg/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1110655 10/21/2021 Deficient Monitoring Lost sample pumps that feed EFF-001 continuous analyzers for pH, Dissolved Oxygen, Total Residual Chlorine, and Sulfur Dioxide for approximately 9 minutes. Error occurred during an unplanned SMUD power outage. Error occurred when redundant sample pumps/analyzers were offline for routine preventative maintenance. See cover letter for additional details. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1102622 02/28/2022 CAT2 Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.255 mg/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1095886 09/30/2021 CAT2 Dichlorobromomethane Monthly Average (Mean) limit is 31 ug/L and reported value was 32 ug/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 443209 R5-2021-0019-02 Y
1092573 12/13/2020 Order Conditions On 13 December 2020, approximately 400,000 gallons of Chlorinated Secondary Effluent (CSE) spilled at the Facility due to a failure of a restrained coupler in an underground high pressure reclaimed water pipe. The majority of the spill discharged to pavement and drained back to the treatment plant¿s headworks; however, a portion of the spill discharged to dry land and was not recovered. No surface water was impacted by the spill. The failed section of pipe was replaced with a restrained sleeve coupling in accordance with current design standards and recurrence of the spill is unlikely. The 13 December 2020 spill is a violation of WDRs Discharge Prohibition III.A, which prohibits discharge of wastewater in a manner different from what the WDRs describe. Violation N Report EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
1091465 05/02/2021 Deficient Monitoring On May 2, 2021 laboratory staff collected a CFE sample while SRWTP was in diversion. This sample was taken while SRWTP was not discharging to the Sacramento River, therefore the sample was not representative of the discharge for that day. Violation N eSMR EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
1089522 03/26/2021 CAT2 Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.023 mg/L at EFF-001. Violation N eSMR EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
1088962 12/11/2020 Order Conditions The Discharger failed to enrolled under the General Strom Water Permit. Violation N Complaint Sumiden Wire Company 442988 None Y
1085508 10/29/2020 Order Conditions On 29 October 2020, approximately 4.5 million gallons of CSE spilled at the Facility for a duration of approximately 40 minutes due to a closed motorized gate blocking flow while diverting flow to Emergency Storage Basin A . The spill discharged to dry land and storm water and plant drainage structures that return flow to the headworks for retreatment. The spill was contained within the Facility and no surface water was impacted. The 29 October 2020 spill is a violation of WDRs Discharge Prohibition III.A, which prohibits discharge of wastewater in a manner different from what the WDRs describe. Violation N Report EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
1085507 11/01/2020 Deficient Monitoring On October 20, 2020 SRWTP had a power failure at the outfall facility where continuous effluent monitoring is performed prior to effluent discharge to the Sacramento River. This resulted in effluent discharge that was not monitored for pH, dissolved oxygen, total residual chlorine, and sulfur dioxide (or sodium bisulfite) for a period of approximately nine minutes. A second power failure occurred on 27 October 2020 which resulted in a loss of effluent continuous monitoring for pH, dissolved oxygen, total residual chlorine, and sulfur dioxide (or sodium bisulfite), temperature and flow rate for a period of nine minutes and 32 seconds. No loss of treatment occurred during either of these power failures. Violation N Report EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
1083509 11/16/2020 Order Conditions On 16 November 2020, approximately 4,280 gallons of Chlorinated Secondary Effluent (CSE) spilled at the Facility because a contractor struck a hydrant with a vehicle in an active contruction zone. The spill occured for a duration of 5 minutes dispersed to dry land and sanitary drains nearby and no CSE discharged to surface water during the event. Sanitary drains return flow to SRWTP for retreatment. No surface water was impacted by this spill and no one was injured as a result of this spill. Violation N eSMR EchoWater Resource Recovery Facility 405960 R5-2016-0020-01 Y
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 18
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
  
  
  
  
Expand/Contract Enforcement Actions
Enforcement Actions
Enforcement ID Enforcement Type Enf. Order No. Title Program Effective Date Status
Total Enforcement Actions: 0
  
  
  
  
Expand/Contract Enforcement Actions
Regulatory Measures linked to Related Parties
Reg. Measure ID Organization Regulatory Measure Type Program Effective Date Status
448363 Central Valley Regional Water Quality Control Board, Sacramento Office Resolution PLNBPP 06/10/2022 Historical
402503 Central Valley Regional Water Quality Control Board, Sacramento Office Resolution PLNBPP 07/09/2004 Historical
Total Regulatory Measures linked to Related Parties: 2
  
  
The current report was generated with data as of: 06/09/2025
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.