Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1142064 |
02/28/2025 |
CAT2 |
Zinc, Total Recoverable Monthly Average limit is 67 ug/L and reported value was 87 ug/L at EFF-001. |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1142063 |
02/28/2025 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 16 ug/L and reported value was 29.4 ug/L at EFF-001. |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1140355 |
01/02/2025 |
Deficient Monitoring |
No RW monitoring conducted the week of 11/24 due to boat ramp being flooded |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1140354 |
02/02/2025 |
Deficient Monitoring |
Discharger did not conduct receiving water sampling due to the boat launch ramp being flooded, therefore they could not access the monitoring location. |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1135410 |
09/30/2024 |
Order Conditions |
Violation of Treatment Pont Operating Requirements: Maintain the dissolved oxygen (DO) content in the upper one foot of any wastewater treatment or storage pond at or above 1.0 mg/L. On 9/1 and 9/2 DO in pond 001 was reported at 0.95 mg/L |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1135406 |
08/31/2024 |
Order Conditions |
Violation of Treatment Pont Operating Requirements: Maintain the dissolved oxygen (DO) content in the upper one foot of any wastewater treatment or storage pond at or above 1.0 mg/L. On 8/29, 8/30, and 8/31 DO in pond 001 was reported at 0.95 mg/L |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1128617 |
05/31/2024 |
Late Report |
Once Only OneTime ( MONNPDES ) (ROWD) report for 2024/01/01 (2483881) was due on 30-MAY-24 |
Violation |
None |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1113954 |
01/12/2023 |
Order Conditions |
During the month of January, we experienced an excessive amount of rainfall. In order to not reach our pond freeboard limits, we ceased operation at our manufacturing facility, and discharged >50 GPM. We monitored / documented / reported the river conditions daily. During this time, we did not exceed any of our permitted effluent limits. and we notified your office prior to the change in operation. |
Violation |
N |
eSMR |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
Y |
1109521 |
09/30/2022 |
Deficient Monitoring |
Deficient monitoring of DO in PND-001, PND-002, and PND-003. Per cover letter, Discharger reports that daily DO for 9/13 through 9/20 was not automatically logged. In the past, they were able to retrieve the data, but have been unsuccessful in these attempts. per Discharger "In the future, if this were to reoccur, we will log the D.O. readings manually." |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
N |
1101003 |
11/19/2021 |
Order Conditions |
Pond 1 DO reported under 1 mg/L (0.85), which violates Construction, Operation, and Maintenance Specifications Section VI.C.4.c.iv.a |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
Y |
1101002 |
11/12/2021 |
Order Conditions |
Pond 1 DO reported under 1 mg/L (0.81), which violates Construction, Operation, and Maintenance Specifications Section VI.C.4.c.iv.a |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
Y |
1101001 |
11/05/2021 |
Order Conditions |
Pond 1 DO reported under 1 mg/L (0.59), which violates Construction, Operation, and Maintenance Specifications Section VI.C.4.c.iv.a |
Violation |
N |
Report |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
Y |
1093696 |
07/07/2021 |
Deficient Monitoring |
On 07/07/21 Samples were taken in the Sacramento river (RSW1 & RSW 2) An error was made on the chain of custody document (box not checked) resulting in the sample for RSW2 has no TDS results, The TDS was measured, analyzed and reported for RSW1. |
Violation |
N |
eSMR |
Bell Carter Industrial WWTP |
436568 |
R5-2021-0021 |
Y |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|