| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1149574 |
11/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 4650 gallons of sewage to spill from Manhole at 36425 Trail Ride Lane to Street/Curb and Gutter (2 3),Drainage Conveyance System |
Violation |
None |
SSO |
Southern Section CS (Duplicate Place ID 256451) |
352066 |
2022-0103-DWQ |
N |
| 1149572 |
11/16/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below),Flow Exceeded Capacity (Separate Collection System Only) caused 800 gallons of sewage to spill from Manhole at 36425 Trail Ride Lane to Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
Southern Section CS (Duplicate Place ID 256451) |
352066 |
2022-0103-DWQ |
N |
| 1149571 |
11/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Rainfall Exceeded Design, I and I (Separate Collection System Only) caused 27000 gallons of sewage to spill from Manhole at 32585 Mission Trail to Drainage Conveyance System |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1144467 |
06/20/2025 |
Order Conditions |
The June 16, 2025, and June 20, 2025, notifications provided by Elsinore Valley Municipal Water District (Discharger) do not meet the requirements of its enrollment under Order WQ 2-14-0194-DWS, General Order No. CAG14001 (Order). Consistent with section V of Attachment E to the Order (https://www.waterboards.ca.gov/board_decisions/adopted_orders/water_quality/2014/wqo2014_0194_dwq.pdf) beginning on page E-6, notifications for large (greater than one acre-foot), planned discharges must be provided at least three days prior to the initiation of the planned discharge. Notification was sent day of discharge. |
Violation |
N |
Complaint |
Elsinore Valley Municipal Water District WS |
412274 |
2014-0194-DWQ |
Y |
| 1143988 |
05/03/2025 |
Deficient Reporting |
Failure to submit updated Sewer System Management Plan (SSMP) via CIWQS by May 2, 2025, pursuant to State Board Order WQ 2022-0103-DWQ, Statewide Waste Discharge Requirements, General Order for Sanitary Sewer Systems Attachment E1, section 3.11. |
Violation |
None |
Report |
Southern Section CS (Duplicate Place ID 256451) |
352066 |
2022-0103-DWQ |
Y |
| 1143307 |
05/01/2025 |
Late Report |
Quarterly SMR ( PRETRPT ) report for Q1 2025 (2935516) was due on 30-APR-25 |
Violation |
None |
Report |
EVMWD Regional WWRF |
371955 |
R8-2013-0017 |
N |
| 1142245 |
04/11/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 160 gallons of sewage to spill from Force Main at 23016 Pheasant Dr to Drainage Conveyance System |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1141248 |
03/05/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris-General,Other (specify below),Debris from Lateral,Root Intrusion caused 425 gallons of sewage to spill from Manhole at 22216 San Joaquin Dr W Canyon lake to Surface Water |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1134752 |
10/16/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 360 gallons of sewage to spill from Gravity Mainline at Village Pkwy to Drainage Conveyance System,Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1133493 |
03/20/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris from Construction, Debris-General caused 750 gallons of sewage to spill from Lateral Clean Out (Private), Manhole at Winward Dr. to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1133492 |
12/18/2023 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation, Pump Station Failure - Mechanical caused 9762 gallons of sewage to spill from Force Main, Pump Station at Village Way Lift Station to Surface Water |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1133490 |
06/11/2023 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below) caused 100 gallons of sewage to spill from Force Main at Gray Fox dr to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
EVMWD Regional Plant CS |
300417 |
2022-0103-DWQ |
N |
| 1103409 |
03/31/2022 |
CAT1 |
Ammonia, Total (as N) 30-Day Average limit is 4.5 mg/L and reported value was 5.08 mg/L at M-002. |
Violation |
N |
eSMR |
EVMWD Regional WWRF |
371955 |
R8-2013-0017 |
N |
|
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|