Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1140649 |
01/06/2025 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 00.04 mg/L at EFF-001. |
Violation |
N |
eSMR |
American Valley WWTP |
456253 |
R5-2024-0008 |
N |
1139806 |
01/21/2025 |
Other Codes |
Undisinfected secondary treated wastewater is not permitted to discharge to Spanish Creek under WDRs Order R5-2024-0008. Undisinfected wastewater contains elevated concentrations of biological pathogens (e.g., E. coli) that pose a risk to human health. As reported, the Discharger discharged approximately 200,225 gallons of undisinfected secondary treated wastewater to Spanish Creek. Failure to provide a report of waste discharge 180 days in advance of the discharge of wastewater is a violation of CWC Section 13376. |
Violation |
None |
Report |
American Valley WWTP |
456253 |
R5-2024-0008 |
Y |
1139805 |
01/21/2025 |
Order Conditions |
The sodium hypochlorite valve was not re-opened after completing repair work, this prevented proper disinfection of the effluent. In addition, the chlorine analyzer was not set with the Facility?s SCADA system to perform a callout, this contributed to the length of time undisinfected effluent was discharged to surface water. These incident factors demonstrate a violation of Standard Provisions, Proper Operation and Maintenance (WDR Order R5-2024-0008, Attachment D Section 1.D). |
Violation |
None |
Report |
American Valley WWTP |
456253 |
R5-2024-0008 |
Y |
1139804 |
01/21/2025 |
Order Conditions |
By-pass of undisinfected wastewater to Spanish Creek is a violation of Discharge Prohibition III.B (WDR Order R5-2024-0008). |
Violation |
None |
Report |
American Valley WWTP |
456253 |
R5-2024-0008 |
Y |
1139803 |
01/21/2025 |
Order Conditions |
Failure to chlorinate wastewater as described in the permit Fact Sheet section II.A prior to discharge to Spanish Creek is a violation of Discharge Prohibition III.A. (WDRs Order R5-2024-0008). |
Violation |
None |
Report |
American Valley WWTP |
456253 |
R5-2024-0008 |
Y |
1139630 |
12/17/2024 |
OEV |
Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 240 MPN/100 mL at EFF-001. |
Violation |
N |
eSMR |
American Valley WWTP |
456253 |
R5-2024-0008 |
N |
1138539 |
11/24/2024 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 ug/L and reported value was 0.02 ug/L at EFF-001. |
Violation |
N |
eSMR |
American Valley WWTP |
456253 |
R5-2024-0008 |
N |
1129518 |
07/02/2024 |
Late Report |
Once Only OneTime ( TECHRPT ) (WDR VI.C.3.a Salinity Eval. Minimization Plan) report for 2024/07/01 (2824890) was due on 01-JUL-24 |
Violation |
None |
Report |
American Valley WWTP |
456253 |
R5-2024-0008 |
N |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|