| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1156121 |
07/02/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Other (specify below) caused 500 gallons of sewage to spill from Other (specify below),Force Main at Anita Street beach access to Surface Water |
Violation |
None |
SSO |
City of Laguna Beach CS |
300501 |
2022-0103-DWQ |
N |
| 1155949 |
06/21/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 2120 gallons of sewage to spill from Manhole at 162 Rue de Valle, San Marcos, CA 92078 to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
Meadowlark CS |
300566 |
2022-0103-DWQ |
N |
| 1155929 |
03/01/2026 |
Late Report |
MRP No. R9-2012-0055 sections B.1 and C requires annual recycled water user compliance reports to be submitted by March 1 the following year. The 2025 annual recycled water user compliance report was due March 1, 2026. The Discharger failed to submit the January through March 2026 report by May 1, 2026. |
Violation |
N |
Report |
Rincon Del Diablo MWD Recycled Water Service Area |
386901 |
R9-2012-0055 |
Y |
| 1155927 |
03/01/2026 |
Late Report |
Monitoring and Reporting Program No. R9-2012-0055 (MRP No. R9-2012-0055), sections B.1 and C requires quarterly recycled water user reports to be submitted by the first day of the second month following the quarter. The January through March 2026 report was due May 1, 2026. The Discharger failed to submit the January through March 2026 report by May 1, 2026. The report was submitted July 2, 2026. |
Violation |
None |
Report |
Rincon Del Diablo MWD Recycled Water Service Area |
386901 |
R9-2012-0055 |
Y |
| 1155923 |
06/18/2026 |
Basin Plan Prohibition |
Basin Plan Prohibition 14: below from NOV On June 18, 2026, San Diego Water Board staff documented evidence of construction and grading at the Project site within the boundaries of the aquatic features as detailed in the MSHCP Analysis and Clinton Keith JDR. The activities resulted in the discharge of sediment and soil into the aquatic features that San Diego Water Board staff determined were waters of the State. The Discharger causes and contributes to conditions of pollution and nuisance in surface waters, threatens downstream waters, and unreasonably affects habitat and ecosystem-related beneficial uses from the discharge of waste directly into the aquatic features at the Project site. The Discharger failed to submit a ROWD to the San Diego Water Board for the discharges and failed to obtain any permits, authorizations, or waivers for the fill activities from the San Diego Water Board. |
Violation |
None |
Inspection |
Wildomar Crossroads Mixed-Use Project |
465523 |
None |
Y |
| 1155922 |
06/18/2026 |
Basin Plan Prohibition |
Basin Plan Prohibition 7: below from NOV On June 18, 2026, San Diego Water Board staff documented evidence of construction and grading at the Project site within the boundaries of the aquatic features as detailed in the MSHCP Analysis and Clinton Keith JDR. The activities resulted in the discharge of sediment and soil into the aquatic features that San Diego Water Board staff determined were waters of the State. The Discharger causes and contributes to conditions of pollution and nuisance in surface waters, threatens downstream waters, and unreasonably affects habitat and ecosystem-related beneficial uses from the discharge of waste directly into the aquatic features at the Project site. The Discharger failed to submit a ROWD to the San Diego Water Board for the discharges and failed to obtain any permits, authorizations, or waivers for the fill activities from the San Diego Water Board. |
Violation |
None |
Inspection |
Wildomar Crossroads Mixed-Use Project |
465523 |
None |
Y |
| 1155921 |
06/18/2026 |
Basin Plan Prohibition |
Basin Plan Prohibition 1: below from NOV On June 18, 2026, San Diego Water Board staff documented evidence of construction and grading at the Project site within the boundaries of the aquatic features as detailed in the MSHCP Analysis and Clinton Keith JDR. The activities resulted in the discharge of sediment and soil into the aquatic features that San Diego Water Board staff determined were waters of the State. The Discharger causes and contributes to conditions of pollution and nuisance in surface waters, threatens downstream waters, and unreasonably affects habitat and ecosystem-related beneficial uses from the discharge of waste directly into the aquatic features at the Project site. The Discharger failed to submit a ROWD to the San Diego Water Board for the discharges and failed to obtain any permits, authorizations, or waivers for the fill activities from the San Diego Water Board. |
Violation |
None |
Inspection |
Wildomar Crossroads Mixed-Use Project |
465523 |
None |
Y |
| 1155919 |
05/31/2026 |
Deficient Monitoring |
The Total Suspended Solids (TSS) batch for the dates indicated below did not meet quality control acceptance criteria due to duplicate analyses exceeding the allowable Relative Percent Difference (RPD) limits. As a result, the affected data have been excluded from reporting. Affected sample locations and dates: May 25, 2026: N_DIV_STRUCT, N34-REC, N20-SE, N01-PD, N01-FB, N10-EFF, N01-PS_INF, N01-PEN; and May 26, 2026: N20-RAS COMB, N15-WAS HCP, N15-AE. The QC failure was attributed to inconsistent sample homogenization prior to duplicate aliquot measurement. While samples were mixed prior to pouring the first aliquot, they were not re-mixed immediately before pouring the second aliquot, allowing suspended solids to settle. This resulted in non-representative duplicate measurements and RPD values outside acceptance limits. The current SOP assumes adequate mixing prior to each aliquot; however, it does not explicitly require immediate re-mixing before every individual aliquot withdrawal. This gap contributed to the variability observed in the duplicate results. In addition, the samples were disposed of before the failure was identified and therefore could not be reanalyzed. The Biological Oxygen Demand (BOD) analyses for samples MBC_COMBCN dated May 30, 2026 and May 31, 2026 are not available due to a software failure during probe readings for final dissolved oxygen measurements. The sample bottles were disposed of before the issue was identified, and the original samples exceeded holding time for this analysis and could not be rerun. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
464790 |
R9-2026-0002 |
N |
| 1155918 |
05/31/2026 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 60 mg/L and reported value was 64.3 mg/L at EFF-001. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
464790 |
R9-2026-0002 |
N |
| 1155917 |
05/31/2026 |
Deficient Monitoring |
The BOD laboratory control sample recovery for batch #26133BOD29 was outside of the established method quality control acceptance criteria. Therefore, the result values for the 05/11 and 05/12 Effluent and Influent samples were flagged as non-reportable. Due to the 5-day incubation period required for BOD testing, these samples could not be reanalyzed once the criteria failure was identified. This resulted in the laboratory not meeting the minimum sampling frequency of 1/Day. The relative percent difference (RPD) of the sample duplicates for Total Suspended Solids (TSS) batch #26149TSS71 exceeded the established method quality control acceptance criteria. Because an error in the spreadsheet's RPD calculation formula was identified after the holding time for the 05/27 and 05/28 samples, the samples could not be reanalyzed to resolve the issue. Consequently, the result values for the Effluent and Influent samples were flagged as non-reportable. This resulted in the laboratory not meeting the minimum sampling frequency of 1/Day. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
464790 |
R9-2026-0002 |
N |
| 1155916 |
05/31/2026 |
Deficient Monitoring |
The BOD laboratory control sample recovery for batch #26133BOD29 was outside of the established method quality control acceptance criteria. Therefore, the result values for the 05/11 and 05/12 Effluent and Influent samples were flagged as non-reportable. Due to the 5-day incubation period required for BOD testing, these samples could not be reanalyzed once the criteria failure was identified. This resulted in the laboratory not meeting the minimum sampling frequency of 1/Day. The relative percent difference (RPD) of the sample duplicates for Total Suspended Solids (TSS) batch #26149TSS71 exceeded the established method quality control acceptance criteria. Because an error in the spreadsheet's RPD calculation formula was identified after the holding time for the 05/27 and 05/28 samples, the samples could not be reanalyzed to resolve the issue. Consequently, the result values for the Effluent and Influent samples were flagged as non-reportable. This resulted in the laboratory not meeting the minimum sampling frequency of 1/Day. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
464790 |
R9-2026-0002 |
N |
| 1155915 |
06/18/2026 |
Other Codes |
California Water Code (Water Code) Section 13260: below from NOV On June 18, 2026, San Diego Water Board staff documented evidence of construction and grading at the Project site within the boundaries of the aquatic features as detailed in the MSHCP Analysis and Clinton Keith JDR. The activities resulted in the discharge of sediment and soil into the aquatic features that San Diego Water Board staff determined were waters of the State. The Discharger causes and contributes to conditions of pollution and nuisance in surface waters, threatens downstream waters, and unreasonably affects habitat and ecosystem-related beneficial uses from the discharge of waste directly into the aquatic features at the Project site. The Discharger failed to submit a ROWD to the San Diego Water Board for the discharges and failed to obtain any permits, authorizations, or waivers for the fill activities from the San Diego Water Board. |
Violation |
None |
Inspection |
Wildomar Crossroads Mixed-Use Project |
465523 |
None |
Y |
| 1155911 |
09/23/2025 |
CAT2 |
Chlorine, Total Residual Instantaneous Maximum limit is 0.0 mg/L and reported value was 4.79 mg/L. |
Violation |
N |
Report |
Hennessey Water Treatment Plant |
406270 |
R2-2021-0009 |
N |
| 1155874 |
03/31/2026 |
Deficient Monitoring |
Though the City did monitor for sulfamethoxazole and electrical conductivity (EC) at MFE and M-008 in Q1 2026, the City did not get paired MFE and M-008 samples for sulfamethoxazole or EC in Q1 2026 (i.e., samples taken from both locations on the same day) to comply with Section V.D.2. of Order No. R9-2021-0100 Attachment E. The City intends to collect paired samples for sulfamethoxazole and EC at MFE and M-008 in Q2 2026. |
Violation |
N |
Report |
San Luis Rey Water Reclamation Facility - Recycled Water and Pure Water |
443138 |
R9-2021-0100 |
N |
| 1155870 |
12/31/2025 |
Deficient Monitoring |
Quarterly monitoring for sulfamethoxazole (performance CEC) and electrical conductivity (surrogate CEC) was not conducted at MFE. Quarterly monitoring for performance and surrogate CECs at MFE is required to comply with Section V.D.2. of Attachment E to Order No. R9-2021-0100. |
Violation |
N |
Report |
San Luis Rey Water Reclamation Facility - Recycled Water and Pure Water |
443138 |
R9-2021-0100 |
N |
| 1155869 |
10/06/2025 |
CAT1 |
Sodium, % Daily Maximum limit is 60 % and reported value was 62.5 %. |
Violation |
N |
Report |
San Luis Rey Water Reclamation Facility - Recycled Water and Pure Water |
443138 |
R9-2021-0100 |
N |
| 1155744 |
05/31/2026 |
CAT1 |
Total Suspended Solids (TSS), Percent Removal Monthly Average limit is 82 % and reported value was 74.83 % at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1155673 |
06/11/2026 |
Order Conditions |
Condition V.I Project construction began August 21, 2024, and while the mitigation site was graded concurrently with Project construction, complete implementation of the mitigation site has not been completed. Construction of proposed mitigation must be concurrent with project grading and completed no later than 12 months following the start of Project construction. |
Violation |
N |
Inspection |
Hillside Meadows Development Project |
423173 |
R9-2021-0014 |
Y |
| 1155541 |
06/14/2026 |
Unauthorized Discharge |
Discharge of 110,000 gallons of untreated wastewater at the plant due to failure at the influent pump station. 66,295 gallons of sewage were captured and pumped back to the plant. The remaining 43,705 gallons were not contained. |
Violation |
N |
Report |
USMC Camp Pendleton Northern Regional Tertiary Treatment Plant |
389917 |
R9-2014-0006 |
N |
| 1154877 |
04/30/2026 |
Deficient Monitoring |
For Return Stream Monitoring (Monitoring Location RS-001): During the reporting period, all required BOD analyses were performed by the NCWRP Laboratory (ELAP 2477); however, several results were determined to be invalid due to not meeting method specific quality control criteria. Because these QC failures prevented the generation of valid analytical results, the affected samples are considered non reportable and constitute a failure to monitor. The impacted samples at sources (N01-PS_INF, N01-PEN, N01-PD, N01-FB, N_DIV_STRUCTURE, N34 REC WATER, MBC_COMBCN) could not be resampled, as the required 48 hour holding time had elapsed by the time the analyses were completed five days later. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1154876 |
04/25/2026 |
Deficient Monitoring |
For the sample collected on April 25, 2026, the laboratory identified that one of the five tubes for the 1.0 mL dilution had been inoculated into double strength lauryl tryptose broth rather than the required single strength broth. This is a deviation from the analytical method. Double strength broth contains a higher nutrient concentration and is considered at least as supportive of microbial growth as single strength media; therefore, its use does not reduce detection capability. All tubes were negative, and the deviation did not impact the validity of the reported result. |
Violation |
N |
eSMR |
North City WRP |
402158 |
R9-2015-0091 |
N |
| 1154845 |
04/21/2026 |
Deficient Monitoring |
Calculated Total Nitrogen results for locations RSW‑001 (surface, Gauge 52, Gauge 66, Gauge 81, Gauge 96, and bottom), RSW‑002 (surface, middle, and bottom), and RSW‑003 (surface, middle, and bottom) are non‑reportable due to a sampling error in which paired parameters were not collected during the same sampling event. Nitrogen and Total Kjeldahl Nitrogen (TKN) were sampled on different dates, preventing the required calculation of Total Nitrogen. Because resampling was not completed within the required monitoring window, monthly monitoring for these locations was missed. |
Violation |
N |
eSMR |
City of San Diego North City Pure Water Facility |
424907 |
R9-2020-0001 |
N |
| 1154646 |
05/12/2026 |
Unauthorized Discharge |
Unauthorized discharge of 2500 cy and 1300 lf of rip-rap and plastic sheeting in Telegraph Canyon Creek. Discharges were placed in early January to mid-February 2026 without contacting the San Diego Water Board for dredge and fill permits. |
Violation |
N |
Inspection |
Unauthorized Hilltop Park Fill to Riparian Area (Telegraph Canyon Creek) |
465124 |
UNDETERMINED |
N |
| 1154381 |
03/01/2026 |
Deficient Reporting |
The Discharger failed to submit an annual monitoring report for 2025. |
Violation |
None |
Report |
Vail Lake RV Resort |
407253 |
2014-0153-DWQ |
N |
| 1154218 |
03/24/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Air Relief Valve (ARV)/ Blow-Off Valve (BOV) Failure caused 302425 gallons of sewage to spill from Other (specify below),Force Main,Other Sewer System Structure,Manhole at NOT# 40201370275 OLD SEA WORLD DR. & S. SHORES DR. to Drainage Conveyance System,Drainage Conveyance System that discharges to surface water,Surface Water,Street/Curb and Gutter (2 3),Paved Surface,Unpaved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1154126 |
03/02/2026 |
Late Report |
Failure to submit the 2025 Annual Monitoring Report. |
Violation |
None |
Report |
Buckman Springs Safety Roadside Rest Area |
426856 |
2014-0153-DWQ |
N |
| 1154120 |
05/04/2026 |
Deficient Reporting |
Failure to submit the October-December 2025 Quarterly Monitoring Report. |
Violation |
None |
Report |
Buckman Springs Safety Roadside Rest Area |
426856 |
2014-0153-DWQ |
N |
| 1154119 |
02/02/2026 |
Deficient Reporting |
Failure to submit the October-December 2025 Quarterly Monitoring Report. |
Violation |
None |
Report |
Buckman Springs Safety Roadside Rest Area |
426856 |
2014-0153-DWQ |
N |
| 1154118 |
11/04/2025 |
Deficient Reporting |
Failure to submit the July-September 2025 Quarterly Monitoring Report. |
Violation |
None |
Report |
Buckman Springs Safety Roadside Rest Area |
426856 |
2014-0153-DWQ |
N |
| 1154117 |
08/04/2025 |
Deficient Reporting |
Failure to submit the April-June 2025 Quarterly Monitoring Report. |
Violation |
None |
Report |
Buckman Springs Safety Roadside Rest Area |
426856 |
2014-0153-DWQ |
N |
| 1153987 |
04/30/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pump Station Failure - Controls caused 15755 gallons of sewage to spill from Manhole at Galloway Pump Station (ALMH0003) to Surface Water |
Violation |
None |
SSO |
County of San Diego CS |
300520 |
2022-0103-DWQ |
N |
| 1153740 |
01/22/2026 |
Unauthorized Discharge |
Unauthorized discharges of wastewater to land and surface waters from the east basin, which the Discharger uses for management of compost wastewater from the Miramar Greenery. |
Violation |
None |
Inspection |
West Miramar Sanitary Landfill |
314078 |
R9-1987-0054 |
Y |
| 1153739 |
01/22/2026 |
Unauthorized Discharge |
Unauthorized discharge of wastewater to land and surface waters. Compost operation wastewater is conveyed to West Miramar Landfill's east basin for stormwater, which discharges to San Clemente Creek. |
Violation |
N |
Inspection |
Miramar Greenery Composting Facility |
449391 |
2015-0121-DWQ |
Y |
| 1153738 |
02/02/2026 |
Unauthorized Discharge |
Unauthorized discharge of waste to land. Discharger encountered waste in a "clean closed" area when digging an anchor trench. Two truckloads of waste were removed. Failure to follow CQA directive to immediately remove the waste once encountered. |
Violation |
N |
Report |
Forster Canyon Landfill |
407820 |
R9-2016-0149 |
Y |
| 1153722 |
03/10/2026 |
Deficient Monitoring |
Due to a SCADA connectivity issue continuous TDS data for M-001A was unavailable from March 3rd to March 10th. The daily TDS average for these dates was reported as the March monthly TDS average. |
Violation |
N |
eSMR |
J.B. Latham Wastewater Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1153690 |
03/31/2026 |
Deficient Monitoring |
During the reporting period, all required BOD analyses were performed by the NCWRP Laboratory (ELAP 2477); however, several results were determined to be invalid due to not meeting method specific quality control criteria. Because these QC failures prevented the generation of valid analytical results, the affected samples are considered non reportable and constitute a failure to monitor. The impacted samples at Monitoring Location RS-001 could not be resampled, as the required 48 hour holding time had elapsed by the time the analyses were completed five days later. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1153669 |
03/17/2026 |
CAT2 |
Chlorine, Total Residual Instantaneous Maximum limit is 5.28 mg/L and reported value was 5.5 mg/L at EFF-001. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1153668 |
03/17/2026 |
CAT2 |
Chlorine, Total Residual Instantaneous Maximum limit is 159 lb/day and reported value was 192.1 lb/day at EFF-001. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1153667 |
03/31/2026 |
Deficient Monitoring |
Due to an error in scheduling by the subcontractor responsible for conducting sampling and analysis (APTIM), no samples were collected at SRTTP Reclaimed Effluent to ensure compliance with quarterly requirements for Q1 2026. Due to the missed sampling, no results are available for the following parameters required for regulatory compliance: chloride, sulfate, % sodium, electrical conductivity, adjusted SAR, nitrate, total nitrogen, iron, manganese, MBAS, boron, fluoride, TDS, and TOC. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
414159 |
R9-2018-0023 |
N |
| 1153646 |
01/29/2026 |
CAT2 |
Copper, Total Recoverable Daily Maximum limit is 13.8 ug/L and reported value was 130 ug/L at NGD-001 & 002. |
Violation |
N |
eSMR |
US Navy NBSD Graving Dock |
444835 |
R9-2013-0064 |
N |
| 1153627 |
02/17/2026 |
OEV |
Fecal Coliform 1-Hour Average (Mean) limit is 400 MPN/100 mL and reported value was 540 MPN/100 mL at S4. |
Violation |
N |
eSMR |
San Luis Rey Water Reclamation Facility (NPDES - Ocean Discharge) |
434521 |
R9-2019-0166 |
N |
| 1153626 |
02/17/2026 |
OEV |
Fecal Coliform 1-Hour Average (Mean) limit is 400 MPN/100 mL and reported value was 1100 MPN/100 mL at S3. |
Violation |
N |
eSMR |
San Luis Rey Water Reclamation Facility (NPDES - Ocean Discharge) |
434521 |
R9-2019-0166 |
N |
| 1153625 |
02/17/2026 |
OEV |
Fecal Coliform 1-Hour Average (Mean) limit is 400 MPN/100 mL and reported value was 530 MPN/100 mL at S1. |
Violation |
N |
eSMR |
San Luis Rey Water Reclamation Facility (NPDES - Ocean Discharge) |
434521 |
R9-2019-0166 |
N |
| 1153547 |
04/24/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 135 gallons of sewage to spill from Manhole at 1134 14th St to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
City of Imperial Beach CS |
300495 |
2022-0103-DWQ |
N |
| 1153486 |
12/19/2025 |
Fees |
The Discharger failed to pay the fee for the 2025-2026 fiscal year, Invoice No. WD0311062. |
Violation |
None |
Report |
Lake Henshaw Resort |
143068 |
94-003 |
N |
| 1153484 |
02/04/2026 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 18.2 ADMI Color Unit. |
Violation |
None |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1153483 |
01/30/2026 |
Deficient Reporting |
The Discharger failed to submit a 2025 annual report. |
Violation |
None |
Report |
Lake Henshaw Resort |
143068 |
94-003 |
N |
| 1153464 |
04/06/2026 |
Late Report |
Finding IV.D of Attachment C of the Order specifies that the Discharger must submit an Emergency Spill Prevention Plan (SPP) within 180 days of adoption of the Order. The Discharger failed to submit an SPP within 180 days of adoption of the Order. The Discharger submitted an SPP on April 14, 2026. |
Violation |
None |
Report |
Pine Hill Egg Ranch |
446998 |
R9-2025-0012 |
N |
| 1153463 |
03/02/2026 |
Late Report |
Section IV.C of Attachment C of the Order specifies that the Discharger must submit the Annual Self-Monitoring Reports (SMRs) by March 1 each year. The Discharger submitted the 2025 Annual SMR on April 14, 2026. |
Violation |
None |
Report |
Pine Hill Egg Ranch |
446998 |
R9-2025-0012 |
N |
| 1153462 |
02/05/2026 |
Late Report |
Finding IV.A of Attachment C of the Order specifies that the Discharger must submit a Monitoring Work Plan (Work Plan) within 120 days of adoption of the Order. The Work Plan was due on February 5, 2026, and the Discharger submitted the Work Plan March 6, 2026. |
Violation |
None |
Report |
Pine Hill Egg Ranch |
446998 |
R9-2025-0012 |
N |
| 1153245 |
01/27/2026 |
Unauthorized Discharge |
On January 29, 2026, the Discharger reported the unauthorized discharge of approximately 940 gallons secondary effluent and brine to the San Luis Rey River that occurred on January 27, 2026. Section A.9 of Order No. 91-39 establishes a prohibition of discharging treated or untreated wastewater to the San Luis Rey River or Santa Margarita River. |
Violation |
None |
Report |
Fallbrook Water Reclamation Plant |
142164 |
91-039 |
Y |
| 1153244 |
10/31/2025 |
Late Report |
The July - September 2025 quarterly report was due on October 31, 2025, and was submitted on November 1, 2025. |
Violation |
N |
Report |
Fallbrook Water Reclamation Plant |
142164 |
91-039 |
Y |
| 1153242 |
10/31/2025 |
Late Report |
The September 2025 monthly report was due on October 31, 2025, and was submitted on November 1, 2025. |
Violation |
N |
Report |
Fallbrook Water Reclamation Plant |
142164 |
91-039 |
Y |
| 1153181 |
02/28/2026 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 771 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153180 |
02/28/2026 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 214 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153179 |
01/31/2026 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 785 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153178 |
01/31/2026 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 215 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153177 |
12/29/2025 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 215 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153176 |
12/29/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 793 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1153113 |
02/09/2026 |
Surface Water |
Approximately 20-gallons of marine diesel spilled onto the main deck of the USNS Sojourner Truth from a pressurized 4" line. A small portion of the fuel sprayed over the port side of the vessel and reached the Bay and pier below. Spilled fuel also discharged to the Bay through a nearby deck drain. Environmental Engineering reported the incident to NRC (#1454476), OES (26-0651), and left a voicemail to the RWQCB (Ella Knight). |
Violation |
N |
eSMR |
National Steel & Shipbuilding Co (NASSCO) |
459091 |
R9-2023-0012 |
N |
| 1153112 |
03/24/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Air Relief Valve (ARV)/ Blow-Off Valve (BOV) Failure caused 296776 gallons of sewage to spill from Force Main,Manhole,Other Sewer System Structure,Other (specify below) at NOT# 40201370275 OLD SEA WORLD DR. & S. SHORES DR. to Surface Water,Unpaved Surface,Paved Surface,Drainage Conveyance System,Street/Curb and Gutter (2 3),Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1152940 |
02/17/2026 |
Surface Water |
Enterococcus result was 2000 MPN/100mL. This was one of 4 results >110 MPN/100mL resulting in more than 10% of monthly samples in exceedance. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152939 |
02/17/2026 |
Surface Water |
Enterococcus result was 121 MPN/100mL. This was one of 4 results >110 MPN/100mL resulting in more than 10% of monthly samples in exceedance. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152938 |
02/17/2026 |
Surface Water |
Enterococcus result was 594 MPN/100mL. This was one of 4 results >110 MPN/100mL resulting in more than 10% of monthly samples in exceedance. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152937 |
02/17/2026 |
Surface Water |
Fecal coliform result was 540 MPN/100mL. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152936 |
02/17/2026 |
Surface Water |
Fecal coliform result was 1100 MPN/100 mL. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152935 |
02/17/2026 |
Surface Water |
Fecal coliform result was 540 MPN/100mL. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152934 |
02/17/2026 |
Surface Water |
Enterococcus result was 295 MPN/100mL. This was one of 4 results >110 MPN/100mL resulting in more than 10% of monthly samples in exceedance. The exceedance was likely due to the sample being taken within 72 hours after precipitation was greater than 0.10 inch. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1152910 |
02/17/2026 |
Surface Water |
S4 exceeded the single sample maximum for fecal coliform. |
Violation |
N |
eSMR |
Oceanside Ocean Outfall |
434521 |
R9-2019-0166 |
N |
| 1152909 |
02/17/2026 |
Surface Water |
S3 exceeded the single sample maximum for fecal coliform. |
Violation |
N |
eSMR |
Oceanside Ocean Outfall |
434521 |
R9-2019-0166 |
N |
| 1152908 |
02/17/2026 |
Surface Water |
S1 exceeded the single sample maximum for fecal coliform. |
Violation |
N |
eSMR |
Oceanside Ocean Outfall |
434521 |
R9-2019-0166 |
N |
| 1152894 |
02/11/2026 |
Deficient Monitoring |
Results for nitrate, nitrite, and calculated total nitrogen at sample locations RSW-001 (bottom and Gauge 96), RSW-002 (surface, middle, bottom), and RSW-003 (surface, middle, bottom) are non-reportable due to a laboratory error in which samples were analyzed beyond the required 48-hour holding time. As a result, valid analytical data were not obtained, and resampling was not completed within the required timeframe, resulting in a missed monthly monitoring requirement. |
Violation |
N |
eSMR |
City of San Diego North City Pure Water Facility |
424907 |
R9-2020-0001 |
N |
| 1152875 |
02/28/2026 |
Deficient Monitoring |
Due to issues with the commercial seed product used for the SBWRP Lab¿s Biochemical Oxygen Demand (BOD) analysis, the internal control standard recovery used during the 02/03/26, 02/04/26 and 02/07/26 Effluent composite samples determinations were outside of the method acceptance limits values established in the Current MDLs & Acceptance Criteria (Document #13584) and flagged as non-reportable. Therefore, the SBWRP monthly monitoring is not in compliance with the ¿Minimum Sampling Frequency¿ definition stated in the ORDER NO. R9-2021-0011 for the BOD. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
South Bay WRP |
437319 |
R9-2021-0011 |
N |
| 1152874 |
02/08/2026 |
Deficient Monitoring |
The BOD internal control standard recovery was outside of the method acceptance limits values established in the Current MDLs & Acceptance Criteria (Document #13584). Therefore, the result values for the 02/08/26 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1152873 |
02/08/2026 |
Deficient Monitoring |
The BOD internal control standard recovery was outside of the method acceptance limits values established in the Current MDLs & Acceptance Criteria (Document #13584). Therefore, the result values for the 02/08/26 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1152638 |
03/02/2026 |
Late Report |
Annual SMR ( PRETRPT ) (Annual Pretreatment Report) report for 2025 (2973925) was due on 01-MAR-26 |
Violation |
None |
Report |
City of San Diego North City Pure Water Facility |
424907 |
R9-2020-0001 |
N |
| 1152156 |
02/23/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Fats, Oil and Grease (FOG),Debris from Construction,Other (specify below) caused 280 gallons of sewage to spill from Manhole at NOT# 40201358467 EXCALIBUR WAY & TOWN CENTER DR. to Drainage Conveyance System that discharges to surface water,Paved Surface,Unpaved Surface,Street/Curb and Gutter (2 3),Surface Water |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1151967 |
01/21/2026 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 18 ADMI Color Unit. |
Violation |
None |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1151966 |
12/10/2025 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 17.7 ADMI Color Unit. |
Violation |
None |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1151964 |
11/04/2025 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 17.7 ADMI Color Unit. |
Violation |
None |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1151963 |
10/16/2025 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 17.8 ADMI Color Unit. |
Violation |
N |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1151962 |
09/11/2025 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 17.7 ADMI Color Unit. |
Violation |
N |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1151950 |
02/20/2026 |
Late Report |
Annual SMR ( SLUDGE ) (Annual Biosolids Report) report for 2025 (2973987) was due on 19-FEB-26 |
Violation |
None |
Report |
City of San Diego North City Pure Water Facility |
424907 |
R9-2020-0001 |
N |
| 1151948 |
03/01/2026 |
Late Report |
The Discharger failed to submit 2025 Annual Monitoring Report. |
Violation |
None |
Report |
LB Twin Lakes Resort |
450945 |
2014-0153-DWQ |
N |
| 1151945 |
02/01/2026 |
Late Report |
The Discharger failed to submit a Q4 2025 monitoring report for Oct-Dec, 2025. |
Violation |
None |
Report |
LB Twin Lakes Resort |
450945 |
2014-0153-DWQ |
N |
| 1151944 |
11/01/2025 |
Late Report |
The Discharger failed to submit a Q3 2025 monitoring report for Jul-Sep, 2025. |
Violation |
None |
Report |
LB Twin Lakes Resort |
450945 |
2014-0153-DWQ |
N |
| 1151943 |
08/01/2025 |
Late Report |
The Discharger failed to submit a Q2 2025 monitoring report for Apr-Jun, 2025. |
Violation |
None |
Report |
LB Twin Lakes Resort |
450945 |
2014-0153-DWQ |
N |
| 1151822 |
01/22/2026 |
Unauthorized Discharge |
Unauthorized discharge of wastewater to groundwater. Failure to maintain landfill cover led to differential settlement and establishment of wetlands over the waste footprint. |
Violation |
None |
Inspection |
South Miramar Landfill |
143109 |
R9-1994-028 |
Y |
| 1151813 |
12/02/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below) caused 2500 gallons of sewage to spill from Other Sewer System Structure at ARCHIE MOORE AIR VALVE #3 to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
Santa Maria CS |
300771 |
2022-0103-DWQ |
Y |
| 1151689 |
01/31/2026 |
Deficient Monitoring |
Due to issues with PLWTP Lab¿s BOD source water the method QC performance was impacted; deficiencies include method blanks exceeding the depletion criteria established in the SOP (1467) BOD_WW_SED_SLDS Revision 11 Section 16.1.1 and internal control standard recovery being outside of the method acceptance limits values stablished in the Current MDLs & Acceptance Criteria (Document #13584). Additionally, the relative percent difference (RPD) of sample duplicates exceeded the method acceptance criteria established in the SOP (1467) BOD_WW_SED_SLDS Revision 11 Section 16.1.4. Hereby, the result values for the 01/09, 01/10, 01/16, 01/17 and 01/25 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1151688 |
01/31/2026 |
Deficient Monitoring |
Due to issues with PLWTP Lab¿s BOD source water the method QC performance was impacted; deficiencies include method blanks exceeding the depletion criteria established in the SOP (1467) BOD_WW_SED_SLDS Revision 11 Section 16.1.1 and internal control standard recovery being outside of the method acceptance limits values stablished in the Current MDLs & Acceptance Criteria (Document #13584). Additionally, the relative percent difference (RPD) of sample duplicates exceeded the method acceptance criteria established in the SOP (1467) BOD_WW_SED_SLDS Revision 11 Section 16.1.4. Hereby, the result values for the 01/09, 01/10, 01/16, 01/17 and 01/25 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1151623 |
01/05/2026 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 9 ml/L at M-001C. |
Violation |
N |
eSMR |
SOCWA - 3A Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1151621 |
01/18/2026 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 64 ml/L at M-001A. |
Violation |
N |
eSMR |
J.B. Latham Wastewater Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1151620 |
01/24/2026 |
CAT1 |
Settleable Solids Weekly Average limit is 1.5 ml/L and reported value was 10.8 ml/L at M-001A. |
Violation |
N |
eSMR |
J.B. Latham Wastewater Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1151616 |
01/31/2026 |
Deficient Monitoring |
At IRWD-PTP facility 001E, the PTP monthly oil and grease sample for the month of January 2026 was missed due to miscommunication and calendar scheduling of the sampling requirement. |
Violation |
N |
eSMR |
Irvine Desalter Project Potable WT System |
446048 |
R9-2022-0006 |
N |
| 1151515 |
02/17/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 320 gallons of sewage to spill from Manhole at NOT-40201356518 4740 ADELPHI PL. to Unpaved Surface,Paved Surface,Drainage Conveyance System that discharges to surface water,Surface Water,Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1151331 |
10/23/2025 |
Unauthorized Discharge |
Failure to Report Project Modifications. Section II.F requires significant changes to the Project be reported to the San Diego Water Board for review and written approval. The plans with the 401 has the box culvert headwall located at the eastern property line in the unnamed tributary. The revised design has the location of the box culvert headwall 56 feet west of the property line with the addition of 0.03 acres of riprap protection to the east. The additional permanent impacts from the riprap were not included in the Project permanent impacts and no additional mitigation was proposed for the additional new impacts. |
Violation |
N |
Inspection |
Liberty Bell Plaza Project |
440979 |
R9-2021-0183 |
N |
| 1151309 |
01/30/2026 |
Late Report |
Failure to submit 2025 Annual Monitoring Report. |
Violation |
None |
Report |
Kamp Anza RV Resort |
142919 |
98-084 |
Y |
| 1151242 |
02/04/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 744 gallons of sewage to spill from Manhole,Inside Building or Structure,Lateral Clean Out (Private) at NOT# 40201352399 810 PAYNE ST. to Unpaved Surface,Street/Curb and Gutter (2 3),Drainage Conveyance System that discharges to surface water,Surface Water,Paved Surface,Building or Structure |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1151200 |
07/30/2025 |
Deficient Monitoring |
Failure to submit January-June 2025 semi-annual monitoring report. |
Violation |
None |
Report |
Skinner Lake Recreation Area |
142536 |
95-018 |
Y |
| 1151198 |
01/30/2026 |
Deficient Monitoring |
Failure to submit July-December 2025 semi-annual monitoring report. |
Violation |
None |
Report |
Skinner Lake Recreation Area |
142536 |
95-018 |
Y |
| 1151166 |
08/01/2025 |
Late Report |
The Discharger failed to submit a Q2 2025 monitoring report for Apr-June, 2025. |
Violation |
None |
Report |
Tucalota Springs RV Park |
437830 |
2014-0153-DWQ |
Y |
| 1151164 |
11/01/2025 |
Late Report |
The Discharger failed to submit a Q3 2025 monitoring report for Jul-Sep, 2025. |
Violation |
None |
Report |
Tucalota Springs RV Park |
437830 |
2014-0153-DWQ |
Y |
| 1151163 |
02/01/2026 |
Late Report |
The Discharger failed to submit a Q4 2025 monitoring report for Oct-Dec, 2025. |
Violation |
None |
Report |
Tucalota Springs RV Park |
437830 |
2014-0153-DWQ |
Y |
| 1151149 |
01/28/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris-General,Fats, Oil and Grease (FOG) caused 15000 gallons of sewage to spill from Manhole at Manhole 02Y111 15 Area Housing to Unpaved Surface,Surface Water |
Violation |
None |
SSO |
USMC Base, Camp Pendleton CS |
300837 |
2022-0103-DWQ |
N |
| 1151052 |
02/01/2026 |
Late Report |
The October-December 2025 Quarterly Report was not submitted. |
Violation |
None |
Report |
Dos Picos County Park |
438621 |
2014-0153-DWQ |
N |
| 1151051 |
11/01/2025 |
Late Report |
The July-September 2025 Quarterly Report was not submitted by the due date as described in the Order and is still not submitted. |
Violation |
None |
Report |
Dos Picos County Park |
438621 |
2014-0153-DWQ |
N |
| 1151050 |
08/01/2025 |
Late Report |
The April-June 2025 Quarterly Report was not submitted. |
Violation |
None |
Report |
Dos Picos County Park |
438621 |
2014-0153-DWQ |
N |
| 1150880 |
01/28/2026 |
Deficient Reporting |
Inadequate Sewer System Management Plan (SSMP); failure to include all elements of Attachment D to the SSS WDRs that describe required SSMP elements. |
Violation |
N |
Report |
USMC Base, Camp Pendleton CS |
300837 |
2022-0103-DWQ |
Y |
| 1150772 |
12/13/2025 |
Deficient Monitoring |
At IRWD SGU facility (M-001F), an unplanned shut off occurred at SGU at 6:00am on 12/9/2025. Daily grab samples were unable to be collected due to the facility being offline. Although there was a partial composite sample, the sample was not collected due to an oversight in field assignments after the facility was offline. As a result Total Suspended Solids had a deficient monitoring violation for the week ending on 12/13/2025. |
Violation |
N |
eSMR |
Irvine Desalter Project Shallow GW Unit |
446048 |
R9-2022-0006 |
N |
| 1150771 |
12/25/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3.0 ml/L and reported value was 4.5 ml/L at M-001B. |
Violation |
N |
eSMR |
SMWD - Chiquita WRP |
438059 |
R9-2022-0005 |
N |
| 1150770 |
07/15/2025 |
Deficient Monitoring |
In July at CSC facility, 001D, the Laboratory Coordinator of the City of San Clemente Water Quality Laboratory discovered an error in reporting during a routine internal audit. The Effluent Composite Total Suspended Solids for July 15, 2025 was originally reported as 3.1 mg/L. The actual Total Suspended Solids for July 15th was 12.6 mg/L. The mistake was a simple transcription error and went initially overlooked by the Laboratory Coordinator. There were no exceedances and the change is minute. |
Violation |
N |
eSMR |
City of San Clemente Segunda Deshecha Runoff Plant |
438059 |
R9-2022-0005 |
N |
| 1150769 |
12/27/2025 |
CAT1 |
Total Suspended Solids (TSS) Weekly Average limit is 45 mg/L and reported value was 92.6 mg/L at M-001B. |
Violation |
N |
eSMR |
SMWD - Chiquita WRP |
438059 |
R9-2022-0005 |
N |
| 1150740 |
12/22/2025 |
Deficient Monitoring |
Due to a laboratory scheduling deficiency, the sample preparation and testing processes for the Total Cyanide method were carried out outside the holding time defined by the Standard Operating Procedure (Document # 1411) Section 9.4. Therefore, the result value reported in batch 26006CN42 for the 12/22/25 influent composite sample was flagged as non-reportable. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1150710 |
11/17/2025 |
OEV |
Fecal Coliform 1-Hour Average (Mean) limit is 400 MPN/100 mL and reported value was 690 MPN/100 mL at S3. |
Violation |
N |
eSMR |
San Luis Rey Water Reclamation Facility (NPDES - Ocean Discharge) |
434521 |
R9-2019-0166 |
N |
| 1150664 |
10/07/2025 |
CAT2 |
Dibromochloromethane Monthly Average (Mean) limit is .401 ug/L and reported value was 28.0 ug/L at EFF-001A. |
Violation |
N |
eSMR |
East County Water Recycling Facility |
445333 |
R9-2022-0003 |
N |
| 1150657 |
08/04/2025 |
Deficient Reporting |
Failure to submit updated Sewer System Management Plan (SSMP) via CIWQS by August 2, 2025, pursuant to State Board Order WQ 2022-0103-DWQ, Statewide Waste Discharge Requirements, General Order for Sanitary Sewer Systems Attachment E1, section 3.11. |
Violation |
N |
Report |
Doheny State Beach CS |
362857 |
2022-0103-DWQ |
N |
| 1150652 |
10/03/2025 |
Surface Water |
On October 3, 2025, at approximately 1615 hours, NASSCO Security received a report of 55 gallons of oil spilled on the flight deck of the USNS Sojourner Truth (TAO-6). NASSCO's Fire Department (NFD) responded to the incident and found approximately 50 gallons of hydraulic oil on the flight deck of the TAO-6, which had spilled due to an overfilled 55-gallon drum. The source of the spill was secured, and NFD began containing the spill using rags and absorbent pads. |
Violation |
N |
eSMR |
National Steel & Shipbuilding Co (NASSCO) |
459091 |
R9-2023-0012 |
N |
| 1150651 |
11/21/2025 |
Surface Water |
On November 21, 2025, at approximately 1130 hours, an estimated 500 gallons of stormwater from the Pier 12 Storm Water Diversion System (SWDS) discharged into San Diego Bay. The pier coordinator alerted NASSCO Maintenance and Environmental Engineering about a pipe that had disconnected from a pier scupper. Maintenance teams promptly responded, secured the pipe, and stopped the discharge. Environmental Engineering personnel arrived on site to find Maintenance actively working on the pipe and pumping the collected stormwater to the Waste Water Treatment Facility (WWTF). Due to safety concerns regarding the pipe's location on the waterside of the pier wall, Environmental Engineering was unable to collect a sample. However, visual observations revealed no evidence of suspended or floating materials, oil or grease, discoloration, turbidity, odors, trash, debris, or any other pollutants. |
Violation |
N |
eSMR |
National Steel & Shipbuilding Co (NASSCO) |
459091 |
R9-2023-0012 |
N |
| 1150650 |
12/05/2025 |
CTOX |
Chronic Toxicity-Sea Urchin or Sand Dollar-Fertilization Event Discharge limit is 50 % effect and reported value was 97 % effect at M-2. |
Violation |
N |
eSMR |
National Steel & Shipbuilding Co (NASSCO) |
459091 |
R9-2023-0012 |
Y |
| 1150627 |
08/04/2025 |
Deficient Reporting |
Failure to submit updated Sewer System Management Plan (SSMP) via CIWQS by August 2, 2025, pursuant to State Board Order WQ 2022-0103-DWQ, Statewide Waste Discharge Requirements, General Order for Sanitary Sewer Systems Attachment E1, section 3.11. |
Violation |
None |
Report |
City Of Solana Beach CS |
301082 |
2022-0103-DWQ |
Y |
| 1150566 |
01/01/2026 |
Order Conditions |
Photos and videos received on November 4, 2025, and January 14, 2026, show the pond storing tertiary treated recycled water overflowing onto the golf course and into stormwater channels on January 1, 2026. This is a violation of General Order 2014-0153-DWQ which requires the Discharger to maintain sufficient freeboard in ponds to prevent spills and requires that the Discharger must maintain any facility, control system, or monitoring device installed to achieve compliance with the General Order. The photos and videos also show the spilled recycled water mixing with stormwater and entering stormwater channels. These stormwater channels connect to the Escondido Canal which connects to Escondido Creek further downstream. This a violation of the General Order which prohibits the direct or indirect discharge of any wastewater to surface waters or surface water drainage courses. |
Violation |
None |
Complaint |
Skyline Ranch Country Club |
441664 |
2014-0153-DWQ |
N |
| 1150532 |
11/21/2025 |
Order Conditions |
Failure to maintain cover in compliance with CAI Landfill General Order R9-2012-0001. Sinkhole and large crack in asphalt cover. |
Violation |
None |
Inspection |
South Chollas Landfill |
213991 |
R9-2012-0002 |
Y |
| 1150500 |
01/06/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation caused 22950 gallons of sewage to spill from Force Main at 41300 Force Main on N. Stuart Mesa to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
USMC Base, Camp Pendleton CS |
300837 |
2022-0103-DWQ |
N |
| 1150492 |
11/25/2025 |
Order Conditions |
The Enrollee failed to complete an evaluation of spill impacts to beneficial uses of the affected surface water, which is required when a spill is greater than 50,000 gallons. |
Violation |
None |
Inspection |
City of Coronado CS |
300485 |
2022-0103-DWQ |
Y |
| 1150491 |
11/25/2025 |
Deficient Reporting |
The Enrollee incorrectly reported the spill volumes associated with storm-related sewer spills by removing the estimated volume of stormwater entering and exiting the sewer system. |
Violation |
None |
Inspection |
City of Coronado CS |
300485 |
2022-0103-DWQ |
Y |
| 1150490 |
11/25/2025 |
Late Report |
The Enrollee submitted several Certified Spill Reports and Technical Reports late. |
Violation |
None |
Inspection |
City of Coronado CS |
300485 |
2022-0103-DWQ |
Y |
| 1150489 |
11/25/2025 |
Sanitary Sewer Overflow/Spill/ |
Between June 5, 2023 and January 15, 2026, the Enrollee's sanitary sewer system was responsible for 6,110,630 gallons of sewage reaching receiving waters. The sewer spills occurring during dry weather and causing beach closures are Class A violations. |
Violation |
None |
Inspection |
City of Coronado CS |
300485 |
2022-0103-DWQ |
Y |
| 1150455 |
01/12/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris from Lateral caused 1125 gallons of sewage to spill from Manhole at 1925 Gillespie Way to Surface Water |
Violation |
None |
SSO |
City of El Cajon CS |
300489 |
2022-0103-DWQ |
Y |
| 1150449 |
10/30/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation caused 21131 gallons of sewage to spill from Force Main at 170831 Force Main to Surface Water,Unpaved Surface |
Violation |
None |
SSO |
USMC Base, Camp Pendleton CS |
300837 |
2022-0103-DWQ |
N |
| 1150409 |
10/02/2025 |
Unauthorized Discharge |
On November 6, 2025, San Diego Water Board staff observed and documented evidence of excavating and grading adjacent to Reidy Canyon Creek, waters of the U.S. and/or state. These excavating and grading activities resulted in the discharge of waste (sediment and soil) into Reidy Canyon Creek, waters of the U.S. and/or state. The discharge of sediment and soil (wastes) pollutes surface waters, adversely affects aquatic life, and obstructs the aesthetic enjoyment of surface waters. The discharge of sediment and soil threatened to unreasonably affect beneficial uses of Reidy Canyon Creek, waters of the U.S. and/or state, and downstream waters, including habitat and ecosystem-related beneficial uses, and caused or contributed to pollution or nuisance conditions |
Violation |
N |
Complaint |
Quail Creek Apartments Property - Unauthorized Excavation Reidy Canyon Creek |
463843 |
None |
Y |
| 1150394 |
01/01/2026 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only),Other (specify below) caused 1640 gallons of sewage to spill from Other Sewer System Structure at Fanita Parkway SSO (9300) to Drainage Conveyance System that discharges to surface water,Unpaved Surface,Surface Water |
Violation |
None |
SSO |
Padre Dam CS |
300581 |
2022-0103-DWQ |
N |
| 1150371 |
08/04/2025 |
Deficient Reporting |
Failure to submit updated Sewer System Management Plan (SSMP) via CIWQS by August 2, 2025, pursuant to State Board Order WQ 2022-0103-DWQ, Statewide Waste Discharge Requirements, General Order for Sanitary Sewer Systems Attachment E1, section 3.11. |
Violation |
None |
Report |
City of Lemon Grove CS |
300504 |
2022-0103-DWQ |
Y |
| 1150368 |
12/22/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 790 gallons of sewage to spill from Manhole at NOT# 40201334684 2727 MORENA BLVD. to Surface Water,Unpaved Surface,Street/Curb and Gutter (2 3),Drainage Conveyance System that discharges to surface water,Paved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1150362 |
08/04/2025 |
Deficient Reporting |
Failure to submit updated Sewer System Management Plan (SSMP) via CIWQS by August 2, 2025, pursuant to State Board Order WQ 2022-0103-DWQ, Statewide Waste Discharge Requirements, General Order for Sanitary Sewer Systems Attachment E1, section 3.11. |
Violation |
None |
Report |
City of Imperial Beach CS |
300495 |
2022-0103-DWQ |
Y |
| 1150290 |
12/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Construction Diversion Failure,Other (specify below) caused 25000 gallons of sewage to spill from Manhole at NOT# 40201332833 2755 SNEAD AVE. to Surface Water,Drainage Conveyance System that discharges to surface water,Unpaved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1150275 |
11/26/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 797 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150274 |
11/26/2025 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 215 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150273 |
10/29/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 802 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150272 |
10/29/2025 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 214 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150271 |
09/24/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 807 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150269 |
08/14/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 57 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150268 |
08/13/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 57 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150267 |
08/12/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 57 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150266 |
08/11/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 57 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150265 |
08/10/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 57 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150264 |
08/29/2025 |
CAT1 |
Nitrate, Total (as NO3) 12-Month Average limit is 10 mg/L and reported value was 38 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150263 |
08/01/2025 |
CAT1 |
Total Dissolved Solids (TDS) Daily Maximum limit is 825 mg/L and reported value was 920 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150262 |
08/01/2025 |
CAT1 |
Chloride Daily Maximum limit is 250 mg/L and reported value was 270 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150261 |
09/24/2025 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 214 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150260 |
08/01/2025 |
CAT1 |
Chloride 12-Month Average limit is 200 mg/L and reported value was 215 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150259 |
08/01/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 810 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150258 |
08/01/2025 |
CAT1 |
Total Dissolved Solids (TDS) 12-Month Average limit is 750 mg/L and reported value was 776 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150254 |
07/28/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 44 mg/L. |
Violation |
None |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150252 |
07/27/2025 |
CAT1 |
Nitrate, Total (as NO3) Daily Maximum limit is 12 mg/L and reported value was 44 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150251 |
07/23/2025 |
CAT1 |
Nitrate, Total (as NO3) 12-Month Average limit is 10 mg/L and reported value was 37 mg/L. |
Violation |
N |
Report |
Santa Rosa WRF-Recycled WTR |
147138 |
94-092 |
Y |
| 1150231 |
12/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Pipe Structural Problem/Failure - Installation caused 990 gallons of sewage to spill from Other (specify below),Force Main at 701 Center Dr San Marcos Ca 92069 to Drainage Conveyance System |
Violation |
None |
SSO |
Meadowlark CS |
300566 |
2022-0103-DWQ |
N |
| 1150211 |
12/16/2025 |
Order Conditions |
When requested to provide calibration record of the effluent flow meters, the Discharger stated that they do not have technicians or consultants that perform calibrations on the effluent flow meters. |
Violation |
None |
Inspection |
SeaWorld, San Diego |
420773 |
R9-2018-0004 |
Y |
| 1150210 |
12/16/2025 |
Unauthorized Discharge |
An open port of the vertical pump for the east treatment system was visibly discharging onto foundation and the discharge flowed into Mission Bay. The Discharger stated that the pump collects water from several exhibits and aquaria and may contain chlorine. This point in the system circumvents the steel screens, chlorination, and dechlorination steps of the East Treatment System. |
Violation |
None |
Inspection |
SeaWorld, San Diego |
420773 |
R9-2018-0004 |
Y |
| 1150207 |
12/22/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 790 gallons of sewage to spill from Manhole at NOT# 40201334684 2727 MORENA BLVD. to Unpaved Surface,Drainage Conveyance System that discharges to surface water,Paved Surface,Surface Water,Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1150187 |
12/18/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 750 gallons of sewage to spill from Manhole at Railroad ROW s/o Alicia Parkway to Unpaved Surface,Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
Moulton Niguel Water District CS |
300574 |
2022-0103-DWQ |
N |
| 1150186 |
11/17/2025 |
OEV |
Fecal Coliform Single Sample Maximum limit is 400 MPN/100 mL and reported value was 690 MPN/100 mL at S3. |
Violation |
N |
eSMR |
Oceanside Ocean Outfall |
434521 |
R9-2019-0166 |
N |
| 1150184 |
12/26/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion,Other (specify below) caused 1125 gallons of sewage to spill from Lateral Clean Out (Private) at 2100 S Escondido Blvd, Escondido, CA 92025 to Drainage Conveyance System,Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
HARRF Disch To San Elijo OO CS |
300549 |
2022-0103-DWQ |
N |
| 1150172 |
11/03/2025 |
Deficient Monitoring |
For both Effluent and Influent composite samples collected in 11/03/25 the phenol, 4-methylphenol, 2,4-dinitrophenol, 4-nitrophenol, and 4,6-dinitro-2-methylphenol analytes¿ Matrix spike duplicate (MSD) Relative Percent Difference recoveries were outside the QC criteria stablished by SOP (6144) 625.1 Rev: 11 Section 16.5. Plus, due to a broken sample vial there was no LCS precision calculated for the mentioned analytes. Therefore, the PLWTP monthly monitoring is not in compliance with the ¿Minimum Sampling Frequency¿ definition stated in the ORDER NO. R9-2017-0007 for the Non-Chlorinated Phenols Sum. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1150171 |
11/03/2025 |
Deficient Monitoring |
For both Effluent and Influent composite samples collected in 11/03/25 the phenol, 4-methylphenol, 2,4-dinitrophenol, 4-nitrophenol, and 4,6-dinitro-2-methylphenol analytes¿ Matrix spike duplicate (MSD) Relative Percent Difference recoveries were outside the QC criteria stablished by SOP (6144) 625.1 Rev: 11 Section 16.5. Plus, due to a broken sample vial there was no LCS precision calculated for the mentioned analytes. Therefore, the PLWTP monthly monitoring is not in compliance with the ¿Minimum Sampling Frequency¿ definition stated in the ORDER NO. R9-2017-0007 for the Non-Chlorinated Phenols Sum. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1150164 |
11/29/2025 |
Deficient Monitoring |
Missed cBOD analysis for 3A (M-001C) Effluent on 11/24/25 due to lab oversight |
Violation |
N |
eSMR |
SOCWA - 3A Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1150163 |
11/30/2025 |
OEV |
Flow Monthly Average limit is 25 MGD and reported value was 30.85 MGD at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1150162 |
12/22/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance caused 12204 gallons of sewage to spill from Force Main at 701 Center Dr San Marcos Ca 92069 to Drainage Conveyance System |
Violation |
None |
SSO |
Meadowlark CS |
300566 |
2022-0103-DWQ |
N |
| 1150160 |
12/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below),Construction Diversion Failure caused 25000 gallons of sewage to spill from Manhole at NOT# 40201332833 2755 SNEAD AVE. to Drainage Conveyance System that discharges to surface water,Unpaved Surface,Surface Water |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1150142 |
11/17/2025 |
OEV |
Fecal Coliform Single Sample Maximum limit is 400 MPN/100 mL and reported value was 690 MPN/100 mL at S3. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1150117 |
11/17/2025 |
OEV |
Enterococci Single Sample Maximum limit is 104 MPN/100 mL and reported value was 128 MPN/100 mL at S4. |
Violation |
N |
eSMR |
HARRF DISCH to San Elijo Ocean Outfall |
420777 |
R9-2018-0002 |
N |
| 1150116 |
11/12/2025 |
Deficient Monitoring |
24 hour composite sample was not taken. Sampler malfunction as it did not sample. Operational shift checks were not performed. 10am analyst did not reset sampler to "run" mode. |
Violation |
N |
eSMR |
HARRF DISCH to San Elijo Ocean Outfall |
420777 |
R9-2018-0002 |
N |
| 1150115 |
11/03/2025 |
OEV |
Enterococci Single Sample Maximum limit is 104 MPN/100 mL and reported value was 222 MPN/100 mL at S5. |
Violation |
N |
eSMR |
HARRF DISCH to San Elijo Ocean Outfall |
420777 |
R9-2018-0002 |
N |
| 1150086 |
11/19/2025 |
Unauthorized Discharge |
Storm event erosion exposed relocated waste, contacted the waste, and discharged as wastewater off-site into the MS4 inlet. |
Violation |
None |
Inspection |
Forster Canyon Landfill |
407820 |
R9-2016-0149 |
Y |
| 1149921 |
12/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Pipe Structural Problem/Failure - Installation caused 990 gallons of sewage to spill from Force Main,Other (specify below) at 701 Center Dr San Marcos Ca 92069 to Drainage Conveyance System |
Violation |
None |
SSO |
Meadowlark CS |
300566 |
2022-0103-DWQ |
N |
| 1149672 |
10/08/2025 |
CAT1 |
Total Suspended Solids (TSS) Daily Maximum limit is 18.3 mg/L and reported value was 18.6 mg/L at EFF-002. |
Violation |
N |
eSMR |
SeaWorld, San Diego |
420773 |
R9-2018-0004 |
N |
| 1149660 |
10/04/2025 |
Deficient Monitoring |
At SGU Brine (001F), SGU operations were intermittent during September and October due to the Navy's activities. This operational change was not communicated to Operations staff, and as a result, monitoring staff were not aware that samples needed to be collected on 10/2/2025,10/3/2025 and 10/4/2025. This included daily (5 days a week) pH and TSS, and weekly settable solids, turbidity and TDS. A discharge occurred for one day before the plant returned offline. SGU resumed operation on 10/13/2025, and all water quality parameters were within permit limits when it returned online. |
Violation |
N |
eSMR |
Irvine Desalter Project Shallow GW Unit |
446048 |
R9-2022-0006 |
N |
| 1149659 |
10/18/2025 |
Deficient Monitoring |
At SCWD ACWRF (001G), On October 14, 2025, the plant operator who sampled the concentrate for total dissolved solids (TDS) found upon arriving at the laboratory that the sample had spilled inside the cooler. The operator returned to the plant and re-sampled but must have sampled from the wrong tap because the sample was not of the concentrate. |
Violation |
N |
eSMR |
SCWD Aliso Creek Water Harvesting Project |
446048 |
R9-2022-0006 |
N |
| 1149657 |
10/04/2025 |
CAT1 |
Settleable Solids Weekly Average limit is 1.5 ml/L and reported value was 6.5 ml/L at M-001D. |
Violation |
N |
eSMR |
City of San Clemente WRP |
438059 |
R9-2022-0005 |
N |
| 1149656 |
10/03/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 10 ml/L at M-001D. |
Violation |
N |
eSMR |
City of San Clemente WRP |
438059 |
R9-2022-0005 |
N |
| 1149655 |
10/08/2025 |
Deficient Monitoring |
For SJCOO M-001,The continuous meter measuring Total Dissolved Solids (TDS), Conductivity and Salinity was online the entire month, however due to a contractor error when transitioning to a new SCADA server, data for 10/1/25-10/8/25 is not available for reporting. Once the error was noticed, data recovery was attempted from the sensors controller however the unit only saves data for about 2 weeks due to memory limitations. |
Violation |
N |
eSMR |
SOCWA San Juan Creek Ocean Outfall |
438059 |
R9-2022-0005 |
N |
| 1149654 |
10/02/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 21 ml/L at M-001D. |
Violation |
N |
eSMR |
City of San Clemente WRP |
438059 |
R9-2022-0005 |
N |
| 1149637 |
10/01/2025 |
Deficient Monitoring |
Due to a laboratory scheduling deficiency, the sample extraction process for the 625.1 Phenols method was carried out outside the holding time defined by the Standard Operating Procedure (Document # 6144) Section 9.4.2. Hereby, the result values reported in batch 25282PHN18 for the 10/01/25 influent and effluent composite samples were flagged as non-reportable. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1149636 |
10/01/2025 |
Deficient Monitoring |
Due to a laboratory scheduling deficiency, the sample extraction process for the 625.1 Phenols method was carried out outside the holding time defined by the Standard Operating Procedure (Document # 6144) Section 9.4.2. Hereby, the result values reported in batch 25282PHN18 for the 10/01/25 influent and effluent composite samples were flagged as non-reportable. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1149633 |
10/04/2025 |
CAT1 |
Total Suspended Solids (TSS) Weekly Average limit is 9383 lb/day and reported value was 10639 lb/day at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1149632 |
10/31/2025 |
CAT1 |
Total Suspended Solids (TSS), Percent Removal Monthly Average limit is 85 % and reported value was 82.61 % at Influent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1149631 |
10/31/2025 |
OEV |
Flow Monthly Average (Mean) limit is 25 MGD and reported value was 29.34 MGD at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1149622 |
11/25/2025 |
Order Conditions |
The TSO required an updated NOI for Order R9-2015-0013 would be submitted on November 23, 2025. The updated NOI was submitted on November 25, 2025. |
Violation |
N |
Report |
GW EX - Lake San Marcos |
458787 |
R9-2024-0110 |
N |
| 1149586 |
09/30/2025 |
Order Conditions |
Approximately 200 gallons of filtered, local seawater was discharged to the storm drain at the Birch Aquarium at Scripps due to a plumbing drain issue. |
Violation |
N |
eSMR |
Scripps Institution of Oceanography |
450871 |
R9-2023-0004 |
N |
| 1149585 |
09/30/2025 |
Order Conditions |
Approximately 450 gallons of fresh water that had been treated with hydrogen peroxide from the Shark Shores backwash system was accidentally discharged to the non-indigenous species (NIS) treatment system and to Outfall 001 instead of to the sanitary sewer system due to operator error. The Shark Shores backwash valves had been incorrectly turned to send water to the NIS treatment system instead of to the sanitary sewer. |
Violation |
N |
eSMR |
Scripps Institution of Oceanography |
450871 |
R9-2023-0004 |
N |
| 1149584 |
09/30/2025 |
Order Conditions |
The top off valve on the BAS gulf reserve system was inadvertently left open by a staff aquarist, resulting in an overflow. Approximately 2,500 gallons of seawater previously treated in May 2025 with Seachem Cupramine, a medication containing copper, discharged to the non-indigenous species (NIS) treatment system which discharges to Outfall 001. |
Violation |
N |
eSMR |
Scripps Institution of Oceanography |
450871 |
R9-2023-0004 |
N |
| 1149574 |
11/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 4650 gallons of sewage to spill from Manhole at 36425 Trail Ride Lane to Street/Curb and Gutter (2 3),Drainage Conveyance System |
Violation |
None |
SSO |
Southern Section CS (Duplicate Place ID 256451) |
352066 |
2022-0103-DWQ |
N |
| 1149572 |
11/16/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below),Flow Exceeded Capacity (Separate Collection System Only) caused 800 gallons of sewage to spill from Manhole at 36425 Trail Ride Lane to Street/Curb and Gutter (2 3) |
Violation |
None |
SSO |
Southern Section CS (Duplicate Place ID 256451) |
352066 |
2022-0103-DWQ |
N |
| 1149356 |
11/03/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Other (specify below) caused 15015 gallons of sewage to spill from Gravity Mainline at 1815 N Broadway to Surface Water,Unpaved Surface |
Violation |
None |
SSO |
HARRF Disch To San Elijo OO CS |
300549 |
2022-0103-DWQ |
N |
| 1149117 |
10/13/2025 |
Order Conditions |
The TVRCS Closed-circuit television video (CCTV) inspection frequency does not meet SSS WDR requirements. Per Attachment D of the SSS WDRs, Enrollees are required to develop, update, and implement a Sewer System Management Plan (SSMP). Section 4.2 of Attachment D requires Enrollees to establish a scheduling system in their SSMP that includes ?regular? visual and CCTV inspections of manholes and sewer pipes. EMWD submitted an addendum to their SSMP on October 1, 2025, stating that ?routine? CCTV inspections are conducted to ?identify structural deficiencies such as offset joints, cracks, or other defects within sewer mains?. The addendum also included an annual system assessment target (10% of pipeline greater than 25 years old), but it appears that this value is for the entire service area, and not specific to the TVRCS. During the audit, EMWD confirmed that only 0.6% of the TVRCS had been visually inspected using CCTV to date. The San Diego Water Board finds this inspection frequency to be both below industry standards and not meeting the ?regular? or ?routine? CCTV inspection frequency described in the SSS WDRs or EMWD?s SSMP, respectively. |
Violation |
None |
Inspection |
Temecula Valley RCS |
300833 |
2022-0103-DWQ |
Y |
| 1149071 |
10/20/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below) caused 4089 gallons of sewage to spill from Force Main at Parker Pump Station to Drainage Conveyance System that discharges to surface water,Unpaved Surface |
Violation |
None |
SSO |
City of Coronado CS |
300485 |
2022-0103-DWQ |
Y |
| 1148888 |
09/23/2025 |
Deficient Monitoring |
For JBL M-001A, The continuous meter measuring Total Dissolved Solids (TDS) was online the entire month, however due to a contractor error when transitioning to a new SCADA server, data for 9/18/25-9/23/25 is not available for reporting. Once the error was noticed, data recovery was attempted from the sensors controller however the unit only saves data for about 2 weeks due to memory limitations. |
Violation |
N |
eSMR |
J.B. Latham Wastewater Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1148887 |
09/30/2025 |
Deficient Monitoring |
For SJCOO M-001,The continuous meter measuring Total Dissolved Solids (TDS), Conductivity and Salinity was online the entire month, however due to a contractor error when transitioning to a new SCADA server, data for 9/18/25-9/30/25 is not available for reporting. Once the error was noticed, data recovery was attempted from the sensors controller however the unit only saves data for about 2 weeks due to memory limitations. |
Violation |
N |
eSMR |
SOCWA San Juan Creek Ocean Outfall |
438059 |
R9-2022-0005 |
N |
| 1148860 |
09/21/2025 |
CAT1 |
Total Suspended Solids (TSS) Weekly Average (Mean) limit is 45 mg/L and reported value was 50 mg/L at EFF-001. |
Violation |
N |
eSMR |
USMC Camp Pendleton Southern Regional Tertiary Treatment Plant |
422969 |
R9-2019-0167 |
N |
| 1148823 |
09/23/2025 |
Deficient Monitoring |
Due to a sample preparation deficiency during the initial weight and extraction process described in the SOP (1418) O_G_HEM Revision: 7 Section 14.4; the Oil and Grease result values processed in batch 25272OG40 for the weekly 9/23/25 outfall grab sample was flagged as non-reportable. |
Violation |
N |
eSMR |
South Bay WRP |
437319 |
R9-2021-0011 |
N |
| 1148822 |
09/30/2025 |
Deficient Monitoring |
Due to a sample preparation deficiency during the initial weight and extraction process described in the SOP (1418) O_G_HEM Revision: 7 Section 14.4; the Oil and Grease result values processed in batch 25272OG40 for the 9/23, 9/24, 9/25 and 9/26 effluent and influent grab samples were flagged as non-reportable. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1148821 |
09/09/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 6 ml/L at EFF-001. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1148820 |
09/03/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 3.5 ml/L at EFF-001. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1148753 |
09/27/2025 |
Deficient Monitoring |
At IRWD-SGU (M-001F) the time of these sampling events, IRWD was implementing a new LIMS system and electronic COC process; the daily samples were collected but the 9/27/2025 weekly for TDS (Total Dissolved Solids), turbidity, and SS (Settleable Solids) was not analyzed off the bottles turned in for that sampling event. The new LIMS system did not have the weekly samples linked properly and it was missed in error. The sample would have been recollected, however, SGU went offline and there was no discharge to collect representative samples. |
Violation |
N |
eSMR |
Irvine Desalter Project Shallow GW Unit |
446048 |
R9-2022-0006 |
N |
| 1148752 |
09/06/2025 |
Deficient Monitoring |
At IRWD-PTP (M-001E), pH samples were collected on 9/3 at PTP during routine monitoring. At the time of these sampling events, IRWD was implementing a new LIMS system and electronic COC process. Due to the new system, the pH samples were not properly logged in the LIMS system, and the COCs were not completed with names and dates as the COCs were supposed to be done electronically. There is no evidence suggesting the pH grabs were out of effluent permit limitations, but the documentation was incomplete, and the samples are not included in the data. |
Violation |
N |
eSMR |
Irvine Desalter Project Potable WT System |
446048 |
R9-2022-0006 |
N |
| 1148751 |
09/06/2025 |
Deficient Monitoring |
At IRWD-SGU (M-001F) , pH samples were collected on 9/3 at PTP during routine monitoring. At the time of these sampling events, IRWD was implementing a new LIMS system and electronic COC process. Due to the new system, the pH samples were not properly logged in the LIMS system, and the COCs were not completed with names and dates as the COCs were supposed to be done electronically. There is no evidence suggesting the pH grabs were out of effluent permit limitations, but the documentation was incomplete, and the samples are not included in the data. |
Violation |
N |
eSMR |
Irvine Desalter Project Shallow GW Unit |
446048 |
R9-2022-0006 |
N |
| 1148744 |
09/30/2025 |
OEV |
Flow 30-Day Average limit is 25 MGD and reported value was 29.22 MGD at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1148743 |
09/30/2025 |
CAT1 |
Total Suspended Solids (TSS), Percent Removal 30-Day Average limit is 85 % and reported value was 83.24 % at Effluent. |
Violation |
N |
eSMR |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1148696 |
09/24/2025 |
Deficient Monitoring |
The weekly temperature monitoring was not conducted at RSW-001b and RSW-002b during the week of September 22, 2025. The impact on the compliance calculation of the running annual average temperature delta between the discharge brine and the receiving waters was insignificant (as three weekly temperature monitoring events were conducted in September 2025), however, this will be reported as a monitoring violation. |
Violation |
N |
eSMR |
Sweetwater Authority Groundwater Demin |
412286 |
R9-2017-0020 |
N |
| 1148470 |
08/02/2025 |
Late Report |
Quarterly SMR ( MONRPT ) (Tijuana River Valley Monitoring Program Quarterly Monitoring Report) report for Q2 2025 (3038039) was due on 01-AUG-25 |
Violation |
None |
Report |
South Bay International WWTP |
442331 |
R9-2021-0001 |
N |
| 1148467 |
10/20/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below) caused 6636 gallons of sewage to spill from Force Main at Parker Pump Station to Drainage Conveyance System that discharges to surface water,Unpaved Surface |
Violation |
None |
SSO |
City of Coronado CS |
300485 |
2022-0103-DWQ |
N |
| 1148453 |
10/12/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris-Rags,Fats, Oil and Grease (FOG) caused 2210 gallons of sewage to spill from Manhole,Gravity Mainline at 206 S Rose St sewer manhole FacilityID 5463 to Surface Water,Drainage Conveyance System that discharges to surface water,Drainage Conveyance System |
Violation |
None |
SSO |
HARRF Disch To San Elijo OO CS |
300549 |
2022-0103-DWQ |
N |
| 1148439 |
08/11/2025 |
Surface Water |
On August 11, 2025 at 0913 hrs, NASSCO Security received a report of a sheen in San Diego Bay adjacent to Berth 6 of approximately 800' x 100'. Security notified NASSCO Fire Department (NFD) and NASSCO Environmental Engineering (EE) to respond to the incident. At the time of the incident, two NASSCO departments were operating vessel systems that had the potential to discharge fuel. EE made regulatory notifications to the Office of Emergency Services (#25-3980), National Response Center (#143-9509), and Regional Water Quality Control Board (voicemail). An oil boom was around the vessel that contained the sheen and NASSCO Waterfront Services (NWF) placed a secondary boom around the sheen to prevent migration. NFD, EE, and WFS conducted an investigation to identify a source of the discharge. NFD nor EE identify any source or evidence of a spill onboard the vessel, NWF used a skiff and diver but did not identify a source within the water or under the vessel. NASSCO continued to monitor the incident, the sheen was not recoverable and dissipated over time. |
Violation |
N |
eSMR |
National Steel & Shipbuilding Co (NASSCO) |
459091 |
R9-2023-0012 |
N |
| 1148403 |
10/04/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Pump Station Failure - Power caused 660 gallons of sewage to spill from Pump Station at NOT-#40201301596 15600 SAN ANDRES DR. to Street/Curb and Gutter (2 3),Drainage Conveyance System that discharges to surface water,Paved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1147949 |
08/12/2025 |
OEV |
Color, ADMI 12-Month Average limit is 15 ADMI Color Unit and reported value was 17 ADMI Color Unit. |
Violation |
N |
Report |
Hale Avenue Resource Recovery Facility (HARRF) Recycled Water |
374060 |
R9-2010-0032 |
Y |
| 1147910 |
08/17/2025 |
Deficient Monitoring |
During the reporting period of August 17-23, 2025, the North City Water Reclamation Plant (NCWRP) did not submit pH monitoring data for the reclaimed final effluent. This omission was due to a scheduled facility shutdown originally planned for August 18-22, 2025. At the time, it was anticipated that operations would resume on August 23, allowing for sample collection in accordance with permit requirements. However, the shutdown unexpectedly extended through August 23, preventing sampling and analysis on that date. |
Violation |
N |
eSMR |
North City WRP |
402158 |
R9-2015-0091 |
N |
| 1147879 |
08/27/2025 |
Deficient Monitoring |
Analyst Error for M001 CBOD 8-27-25 |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1147878 |
08/25/2025 |
Deficient Monitoring |
Analyst Error for Sample M002 CBOD 8-25-2025 |
Violation |
N |
eSMR |
Vallecitos WD Meadowlark WRP |
425154 |
R9-2018-0059 |
N |
| 1147877 |
08/25/2025 |
Deficient Monitoring |
Analyst error for site M002 CBOD resulting in less than 7 consecutive CBOD samples for 7-day monitoring per page E-6 of order R9-2018-0059 permit. |
Violation |
N |
eSMR |
Vallecitos WD Meadowlark WRP |
425154 |
R9-2018-0059 |
N |
| 1147846 |
08/26/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3 ml/L and reported value was 4 ml/L at EFF-001. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1147845 |
08/31/2025 |
Deficient Monitoring |
1. Due to a programmed power outage at the PLWTP, the composite effluent and influent samples from the 08/26/25 collection may differ from the composite sample definition stated in the ORDER NO. R9-2017-0007; NPDES NO. CA0107409 Part 2. ¿ Glossary of Common Terms ¿Daily Discharge¿. The 08/26/2025 effluent and influent composite samples were obtained from a combination of at least eight sample aliquots of at least 100 mL at periodic intervals during the time frame from 0001 to 0110 and 1300 to 2359; therefore, the samples not necessarily reflect the plant¿s operating hours over a 24-hour period for the following analyses: Floatable solids, BOD, TDS, TSS_VSS. 2. The BOD internal control standard recovery was outside of the method acceptance limits values stablished in the Current MDLs & Acceptance Criteria (Document #13584). Herby, the result values for the 8/22, 8/23 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. 3. Due to contamination during the batch 25219BN35 continuous liquid-liquid extraction; the Hexachlorocyclopentadiene internal control standard recovery and RPD percentages were outside of the method acceptance limits values stablished in the SOP (6144) 625.1 Revision: 11, Section 16. Herby, the result values for the 08/06 Effluent and Influent composite samples processed in were flagged as non-reportable. Additionally, the Bis(2-ethylhexyl) phthalate compound was detected in the Method Blank above the Method Detection Level; the result values for the 08/06 Influent composite sample processed in batch 25219BN35 were flagged as non-reportable. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1147784 |
08/05/2025 |
Unauthorized Discharge |
A spill was reported on 8/5/2025 at approximately 13:20 at the AWT Brine Line ARV ROC #16. The spill occurred when a vehicle struck and sheared off the ARV pipe connection, causing the brine to percolate into ground on the dirt shoulder of Vandergrift Blvd. West. The spill was contained by responders at 14:20 and a temporary valve was installed. The estimated spill volume of 300 gallons was calculated using the volume by area estimation method. The spill did not reach or affect any drinking water systems or surface waters and did not result in any closures. |
Violation |
N |
eSMR |
Advanced Water Treatment Plant at Haybarn Canyon |
422969 |
R9-2019-0167 |
N |
| 1147679 |
08/31/2025 |
CAT1 |
Oil and Grease Monthly Average limit is 25 mg/L and reported value was 28 mg/L at M-001C. |
Violation |
N |
eSMR |
SOCWA - 3A Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1147678 |
08/09/2025 |
Deficient Monitoring |
On August 4, 2025, Plant MNWD-3A (M-001C) operations staff mistakenly did not submit a secondary effluent composite sample. This was due to using the wrong bottle for sample collection. Operations staff discarded the composite sample for the day and forgot to conduct a makeup sample later in the week. This resulted in a missed monitoring event for the R9-2025-0001 permit. Operations staff collected the secondary effluent daily composite sample in the incorrect sample bottles. The contracted laboratory provides premade sample kits for each compliance sample day. The collected sample was deemed unusable as it was put into the incorrect bottle which contained preservative for a different analysis at another sample location; therefore, the sample was discarded because it was now contaminated. Operations staff forgot to schedule a makeup sample collection for this later in the week. |
Violation |
N |
eSMR |
SOCWA - 3A Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1147676 |
09/15/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Other (specify below),Pipe Structural Problem/Failure - Installation caused 1125 gallons of sewage to spill from Inside Building or Structure,Manhole at NOT# 40201293362 10445 FRIARS RD. to Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3),Unpaved Surface,Surface Water,Building or Structure,Paved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1147144 |
08/26/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Other (specify below) caused 840 gallons of sewage to spill from Lateral Clean Out (Private),Manhole at NOT# 40201284796 3414 GOVERNOR DR. to Paved Surface,Drainage Conveyance System,Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3),Unpaved Surface |
Violation |
None |
SSO |
San Diego City CS (Wastewater Collection System) |
300511 |
2022-0103-DWQ |
N |
| 1146776 |
07/11/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Root Intrusion caused 3000 gallons of sewage to spill from Gravity Mainline,Manhole at La Media RD / Santa Venetia st to Street/Curb and Gutter (2 3),Drainage Conveyance System |
Violation |
None |
SSO |
City of Chula Vista CS |
300484 |
2022-0103-DWQ |
N |
| 1146547 |
07/11/2025 |
Unauthorized Discharge |
On Friday, July 11, 2025 at approximately 9:50am, a contractor onsite at MNWD's Plant 3A (26801 Camino Capistrano, Mission Viejo CA) opened an incorrect pipe connected to a digester. Liquid from the digester flowed until the pipe was able to be re-capped around 10:30 am. Total spill volume was calculated at 18,548 gallons of liquid that left the digester. Dirt berms were used to contain flow as best as possible, but approximately 300 gallons did enter a storm drain and subsequently Oso Creek. It was calculated that 18,280 gallons were recovered. MNWD staff set up a portable dam in the Oso Creek channel downstream, equipped with a portable pump, and began pumping this flow into a nearby sewer manhole to return to a treatment plant. Staff observations did not note any downstream impacts during bypass pumping, which continued for approximately 30 hours, removing approximately 630,000 gallons of water over that time period. Surface water sampling was conducted same-day and additionally 2 days of follow up sampling. |
Violation |
N |
eSMR |
SOCWA - 3A Treatment Plant |
438059 |
R9-2022-0005 |
N |
| 1146546 |
07/19/2025 |
Deficient Monitoring |
The City of San Clemente, M-INFD, did set up an Influent cBOD that week of 7/19 but the tech was out the following week due to an accident and was unable to complete the analysis. The tech normally setup Influent cBOD twice a week to ensure that they have at least one data point but he happened to be out that Thursday which is the day the tech normally setup the additional Influent cBOD. |
Violation |
N |
eSMR |
City of San Clemente WRP |
438059 |
R9-2022-0005 |
N |
| 1146482 |
07/25/2025 |
Deficient Monitoring |
Please see cover letter. |
Violation |
N |
eSMR |
SeaWorld - Fireworks Event Location |
451974 |
R9-2022-0002 |
N |
| 1146479 |
07/25/2025 |
Deficient Monitoring |
Please see cover letter. |
Violation |
N |
eSMR |
SeaWorld - Fireworks Event Location |
451974 |
R9-2022-0002 |
N |
| 1146463 |
07/31/2025 |
Deficient Monitoring |
Due to a Control Standard preparation deficiency during the dilution series process described in the SOP (1467) BOD_WW_SED_SLDS Revision: 11, Section 14.2.12; The Biochemical Oxygen Demand internal control standard recovery was outside of the method acceptance limits values stablished in the Current MDLs & Acceptance Criteria (Document #13584). Hereby, the result values for the 07/18, 07/19 Effluent and Influent composite samples were flagged as non-reportable. Due to the nature of the BOD testing, the samples could not be reanalyzed after the 5-day incubation period when results become known. |
Violation |
N |
eSMR |
Point Loma WWTP & Ocean Outfall |
414988 |
R9-2017-0007 |
N |
| 1146398 |
08/07/2025 |
Enforcement Action |
Surfacing effluent was observed on a portion of the drip dispersal field, possibly as a result of a damaged drip dispersal line. |
Violation |
N |
Inspection |
Oak Tree Ranch Private Residential Community OWTS |
417286 |
2014-0153-DWQ |
N |
| 1145963 |
07/31/2025 |
Deficient Reporting |
2025 Quarter 2: Incorrect chronic toxicity testing species used. Marine species used instead of freshwater. |
Violation |
None |
Report |
GW EX - 13247 Poway Road |
456278 |
R9-2015-0013 |
Y |
| 1145609 |
07/31/2025 |
Deficient Reporting |
The Discharger failed to report the information and data required in the quarterly recycled water user summary reports. |
Violation |
None |
Report |
Rincon Del Diablo MWD Recycled Water Service Area |
386901 |
R9-2012-0055 |
Y |
| 1145603 |
08/01/2025 |
Late Report |
The April-June 2025 Quarterly Report was not submitted. |
Violation |
None |
Report |
(Pacifica) Champagne Lakes RV Resort |
455122 |
2014-0153-DWQ |
N |
| 1144843 |
07/14/2025 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Debris-Rags caused 260 gallons of sewage to spill from Manhole at 4039 Calle Platino to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
City of Oceanside Collection System, La Salina WWTP |
300562 |
2022-0103-DWQ |
N |
|
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|