| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1150890 |
10/01/2025 |
Order Conditions |
4Q2025; The freeboard limit of 1.5 feet was exceeded at PND-3 on 10/1/25, 10/15/25, 10/22/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25; At PND-4 on 11/5/25, 11/12/25, 12/3/25, 12/24/25, 12/31/25; At PND-5 on 10/1/25, 10/15/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25; At PND 6 on 10/1/25, 10/8/25, 10/15/25, 10/22/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25; At PND 7 on 10/1/25, 10/8/25, 10/15/25, 10/22/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25; At PND-8 on 10/1/25, 10/8/25, 10/15/25, 10/22/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25; At PND-9 on 10/1/25, 10/8/25, 10/15/25, 10/22/25, 10/29/25, 11/5/2025, 11/12/25, 11/19/25, 11/26/25, 12/3/25, 12/10/25, 12/17/25, 12/24/25, 12/31/25. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1150889 |
10/31/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 775 umhos/cm and reported value was 846 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1150888 |
12/31/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 774 umhos/cm and reported value was 879 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1150887 |
11/30/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 776 umhos/cm and reported value was 876 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1150886 |
11/30/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 40 mg/L and reported value was 51 mg/L at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1150587 |
11/17/2025 |
Order Conditions |
Unauthorized discharge of condensate water into Morrison Ditch prior to compliance with CWC Section 13260. Violation of CWC Sections 13260 and 13264. |
Violation |
None |
Inspection |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1150586 |
11/17/2025 |
Order Conditions |
At the time of inspection, operational freeboard was less than 1.5 feet in seven percolation ponds. This is a violation of Order Section G.10. |
Violation |
None |
Inspection |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
Y |
| 1150585 |
11/16/2025 |
Order Conditions |
Unauthorized discharge of treated wastewater from the percolation ponds into Morrison Ditch and the Casa Blanca Canal without filing a report of waste discharge. This is a violation of California Water Code sections 13260, 13264, 13350, Order sections A.1 and A.4. |
Violation |
None |
Inspection |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149744 |
08/13/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149743 |
09/17/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 77.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149742 |
09/03/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 70.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149741 |
09/30/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 42.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149740 |
08/20/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 36.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149739 |
08/13/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 27.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149738 |
08/31/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 21.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149737 |
07/02/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 44.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149736 |
07/31/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 26.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149735 |
08/20/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 30.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149734 |
08/13/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 51.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149733 |
08/31/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 29.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149731 |
07/02/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 48.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149728 |
07/31/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 17.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149725 |
09/30/2025 |
Surface Water |
3rd Quarter 2025: pH was changed more than 0.3 units in September 2025 (8.95 to 8.32 pH units). |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149724 |
07/31/2025 |
Surface Water |
3rd Quarter 2025: pH was changed more than 0.3 units in July 2025 (9.51 to 8.96 pH units). |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149231 |
06/18/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 42.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149230 |
06/04/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 89.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149229 |
06/30/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 42.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149228 |
05/21/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 23.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149227 |
05/07/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 30.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149226 |
05/31/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 15.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149225 |
04/30/2025 |
CAT1 |
Total Suspended Solids (TSS) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 52.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149224 |
04/30/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 10.0 mg/L and reported value was 19.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149223 |
06/18/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149222 |
06/11/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149221 |
05/28/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149220 |
05/21/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149219 |
05/14/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149218 |
05/07/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149217 |
05/31/2025 |
CAT2 |
Chlorine, Total Residual Monthly Average limit is 0.01 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149216 |
04/30/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149215 |
04/23/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149214 |
04/09/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149213 |
04/02/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149211 |
04/30/2025 |
CAT2 |
Chlorine, Total Residual Monthly Average limit is 0.01 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149210 |
06/18/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 54.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149209 |
06/30/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 18.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149207 |
05/07/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 26.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149206 |
05/31/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 15.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149205 |
04/23/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Maximum Daily (MDEL) limit is 20.0 mg/L and reported value was 45.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149204 |
04/30/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 18.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149203 |
03/26/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149202 |
03/19/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149201 |
03/12/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149200 |
03/05/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149199 |
03/31/2025 |
CAT2 |
Chlorine, Total Residual Monthly Average limit is 0.01 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149198 |
03/31/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 11.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149197 |
02/26/2025 |
CAT2 |
Chlorine, Total Residual Maximum Daily (MDEL) limit is 0.02 mg/L and reported value was 0.1 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149193 |
02/28/2025 |
CAT2 |
Chlorine, Total Residual Monthly Average limit is 0.01 mg/L and reported value was 0.2 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149191 |
02/28/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10.0 mg/L and reported value was 13.0 mg/L. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149178 |
06/30/2025 |
Surface Water |
2nd Quarter 2025: pH was changed more than 0.3 units in April 2025 (9.23 to 8.55 pH units). |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149177 |
04/30/2025 |
Surface Water |
2nd Quarter 2025: pH was changed more than 0.3 units in April 2025 (9.23 to 8.55 pH units). |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149176 |
02/28/2025 |
Surface Water |
1st Quarter 2025: pH was changed more than 0.3 units in February 2025 (8.3 to 7.5 pH units). |
Violation |
None |
Report |
Tipton Milk Processing Facility |
454740 |
R5-2022-0006-02 |
N |
| 1149043 |
05/22/2025 |
Order Conditions |
At the time of inspection, operational freeboard was less than 2 feet in some percolation ponds and the permanent markers in the percolation ponds are inadequate to determine operational freeboard available. This is a violation of Order Section G.10. |
Violation |
None |
Inspection |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149027 |
07/16/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 07/16/2025, 07/23/2025, 08/20/2025, 09/03/2025, 09/10/2025, 09/24/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149026 |
07/02/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 07/02/2025, 07/09/2025, 07/23/2025, 07/30/2025, 08/13/2025, 08/20/2025, 09/10/2025, 09/24/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149025 |
09/03/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 09/03/2025 and 09/24/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149024 |
08/20/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 08/20/2025, 08/27/2025, 09/17/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149023 |
09/24/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 774 umhos/cm and reported value was 821 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149022 |
07/30/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 774 umhos/cm and reported value was 824 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149021 |
07/02/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Daily Maximum limit is 80 mg/L and reported value was 120 mg/L at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149020 |
08/27/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 775 umhos/cm and reported value was 858 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149019 |
07/02/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 40 mg/L and reported value was 58 mg/L at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149018 |
07/30/2025 |
OEV |
pH Instantaneous Minimum limit is 6.0 SU and reported value was 5.7 SU at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149017 |
07/09/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 07/09/2025, 07/16/2025, 07/23/2025, 08/06/2025, 08/13/2025, 08/20/2025, 09/03/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149016 |
07/02/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 07/02/2025, 07/09/2025, 07/16/2025, 07/23/2025, 07/30/2025, 08/06/2025, 08/13/2025, 08/20/2025, 08/27/2025, 09/03/2025, 09/10/2025, 09/17/2025, 09/24/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1149015 |
07/30/2025 |
Order Conditions |
The freeboard limit of 1.5 feet was intermittently exceeded down to 1 foot of freeboard on the following dates: 07/30/2025, 08/06/2025, 08/27/2025, 09/03/2025, 09/10/2025, 09/17/2025, 09/24/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145402 |
05/07/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-9. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145401 |
05/07/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-8. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145399 |
05/07/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-7. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145398 |
04/16/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.92 mg/L at PND-7. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145397 |
05/07/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-6. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145396 |
05/14/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-4. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145395 |
05/14/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.0 mg/L at PND-3. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145292 |
04/30/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 40.0 mg/L and reported value was 45.5 mg/L at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145286 |
06/30/2025 |
OEV |
Electrical Conductivity @ 25 Deg. C 12-Month Average limit is 773 umhos/cm and reported value was 792 umhos/cm at EFF-001. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1145157 |
03/26/2025 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.8 mg/L at PND-4. |
Violation |
None |
Report |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1142826 |
03/31/2025 |
Deficient Monitoring |
Quarterly average results for Chloride and Boron are not available. Once this was identified, the contracted lab was contacted, and they did not have a record of sampling for quarterly minerals in Q1 2025. The sampling technician from the lab was new and missed the quarterly minerals sampling. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
| 1142821 |
03/26/2025 |
Order Conditions |
1Q2025; The freeboard limit of 2 feet was intermittently exceeded at PND-3 on the following dates: 1/8/25, 1/29/25, 2/5/25, 2/12/25, 2/19/25, 2/26/25, 3/5/25, 3/12/25, 3/19/25, 3/26/25. At PND-4 on the following dates 1/2/25, 1/8/25, 1/15/25, 1/22/25, 1/29/25, 2/5/25, 3/12/25. At PND-5 on 01/02/2025, 01/08/2025, 01/15/2025,1/22/2025,1/29/2025, 02/05/2025, 02/12/2025, 02/19/2025, 02/26/2025, 03/05/2025, 03/12/2025, 03/19/2025, 03/26/2025. At PND-6 on 01/02/2025, 01/08/2025, 01/15/2025, 01/22/2025, 01/29/2025, 02/05/2025, 02/12/2025, 02/19/2025, 02/26/2025, 03/05/2025, 03/12/2025, 03/19/2025, 03/26/2025. At PND-8 on 01/02/2025, 01/08/2025, 01/15/2025, 01/22/2025, 01/29/2025, 02/05/2025, 02/12/2025, 02/19/2025, 02/26/2025, 03/05/2025, 03/12/2025, 03/19/2025, 03/26/2025. At PND-9 on 01/02/2025, 01/08/2025, 01/15/2025, 01/22/2025, 01/29/2025, 02/05/2025, 02/12/2025, 02/19/2025, 02/26/2025, 03/05/2025, 03/12/2025, 03/19/2025, 03/26/2025. |
Violation |
N |
eSMR |
Tipton Milk Processing Facility |
390167 |
R5-2013-0109 |
N |
|
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|