Welcome to California
 California Home
Welcome to California - images of Golden Gate Bridge, ocean sunset, waterfall, flowers, and city skyline California Home Welcome to the California Environmental Protection Agency
 California Integrated Water Quality System Project (CIWQS)
   Party At-A-Glance Report

  
   [VIEW PRINTER FRIENDLY VERSION] [EXPORT THIS REPORT TO EXCEL]

  
  
  
  
  
General Information
Party ID Party Name Party Classification Mailing Address Work Phone Email/Website
624010 Railway Jonata, LLC Privately-Owned Business 2350 Railway Avenue Santa Barbara, CA 93441 310-207-5055 None
  
  
  
  
Expand/Contract Related Places
Related Places
Place ID Place Name County Region Place Type Relationship to Party Relationship Start Date Relationship End Date
874693 Inn at Mattei's Tavern Storm Drain Outlet Santa Barbara 3 Dredge/Fill Site Owner 06/14/2021 None
771776 The Inn at Mattei's Tavern Santa Barbara 3 Domestic Site NEC Owner 05/03/2021 None
Total Related Places: 2
  
  
  
  
Expand/Contract Related Parties
Related Parties
Party ID Party Name Party Type Role/Relationship Relationship Start Date Relationship End Date Classification
625291 Brain Strange Person Legally Responsible Official 06/14/2021 None None
Total Related Parties: 1
  
  
  
  
Expand/Contract Regulatory Measures
Regulatory Measures (non-enforcement)
Reg. Measure ID Regulatory Measure Type Region WDID Status Program Order No. RM Effective Date RM Termination Date Relationship Relationship Start Date Relationship End Date Amended?
443159 Enrollee - WRR 3 3 420422967 Active WDRMUNIOWTS 2014-0153-DWQ 03/21/2022 None Discharger 05/03/2021 None N
443735 Enrollee - WDR 3 34221WQ08 Active CERFILLEXC 2004-0004-DWQ 07/09/2021 None Discharger 06/14/2021 None N
Total Regulatory Measures: 2
  
  
  
  
Expand/Contract Violations
Violations within the past five years
Violation ID Occurrence Date Violation Type Violation Description(-) Violation Status Priority Source Facility Name Violated Reg. Meas. ID Violated Reg. Meas. Order No. Linked to Enf.
1136182 01/04/2024 Order Conditions Exceedance of flow and wastewater limits from January to June of 2024 Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134721 05/31/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 10.0 mg/L and reported value was 11.3 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134720 04/19/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 10.0 mg/L and reported value was 25.5 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134719 06/12/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 24 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134718 05/07/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 11 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134717 05/03/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 20 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134716 04/05/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 34 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1134715 01/04/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 58 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130703 05/16/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 16.0 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130702 04/19/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 7-Day Average (Mean) limit is 15 mg/L and reported value was 27 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130701 04/05/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 7-Day Average (Mean) limit is 15 mg/L and reported value was 24 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130700 04/19/2024 CAT1 Total Suspended Solids (TSS) 7-Day Average (Mean) limit is 7.5 mg/L and reported value was 10.0 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130699 05/03/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 7-Day Average (Mean) limit is 15 mg/L and reported value was 21 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130698 05/31/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 28 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130697 04/19/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 18 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130696 04/30/2024 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) 30-Day Average limit is 10 mg/L and reported value was 25.5 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130695 06/15/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 11192.2 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130694 06/09/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 12651.1 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130693 06/08/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 14765.1 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130692 06/07/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 12911.1 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130690 06/01/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 11599.0 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130689 05/26/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 12166.5 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130688 05/18/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 11561.4 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130687 05/11/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 12002.8 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130686 05/04/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 12419.7 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130685 04/28/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 11586.9 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130684 04/27/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 11605.7 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130683 04/20/2024 OEV Flow Instantaneous Maximum limit is 11100.0 GPD and reported value was 13328.6 GPD. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1130682 01/11/2024 CAT1 Nitrogen, Total (as N) Instantaneous Maximum limit is 10.0 mg/L and reported value was 11 mg/L. Violation N Report The Inn at Mattei's Tavern 443159 2014-0153-DWQ Y
1116477 04/26/2023 Order Conditions Performing washdown of WWTP equipment on bare soil is a violation of General Permit Provision section E.2.v. Wastewater discharges can only occur in designated disposal areas of the Railway Jonata, LLC permit. Essentially, the discharge shall remain within the disposal area designated in the permit at all times. Discharge of wastewater to the bare ground during facility maintenance and cleaning is prohibited. All wastewater must be captured and placed back into the WWTP. Violation None Inspection The Inn at Mattei's Tavern 443159 2014-0153-DWQ N
1116476 04/26/2023 Deficient Reporting Monitoring and Reporting Program No. R3-2022-0023 requires turbidity measurements occur on a continuous basis just prior to the UV disinfection lamp chamber. The turbidity meter has not been installed. Therefore, turbidity readings have not occurred since startup. Turbidity readings are crucial to ensure proper disinfection will occur within the UV chamber. The absence of turbidity measurements and not allowing the contract operators the knowledge of a properly functioning WWTP is a violation of General Permit Provisions section E.2.j (presented earlier) and section E.2 r, which states Railway Jonata, LLC shall maintain in good working order, and operate as efficiently as possible any facility, control system, or monitoring device installed to achieve compliance with the General Permit and the Notice of Applicability. Violation None Inspection The Inn at Mattei's Tavern 443159 2014-0153-DWQ N
1116475 04/26/2023 Order Conditions Water softeners are prohibited in Santa Barbara County. Staff?s review of the Report of Waste Discharges submitted by Railway Jonata, LLC does not indicate the use of water softener systems. This is a violation of General Permit Provision E.2.e, which states the General Permit does not relieve the Discharger from responsibility to obtain other necessary local, state, or federal permits to prevent imposition of additional standards, requirements, or conditions. Violation None Inspection The Inn at Mattei's Tavern 443159 2014-0153-DWQ N
1116474 04/26/2023 Order Conditions Central Coast Water Board Staff discussed with facility operators that, of main concern, is the sizing of the WWTP and the upcoming summer event schedule. Wastewater flows into the WWTP more than the permitted 11,100 gallons per day instantaneous maximum is a violation of the General Permit. Flow rates verbally reported by facility operators indicates the daily maximum flow rate has been exceeded. This is a violation of General Permit Provision section E.2.j, which states the Discharger shall comply with all the conditions of the General Permit. Any noncompliance with the General Permit constitutes a violation of the Porter Cologne Water Quality Control Act and/or appropriate Regional Water Board?s Basin Plan and may be grounds for an enforcement action. Violation None Inspection The Inn at Mattei's Tavern 443159 2014-0153-DWQ N
1114761 03/20/2023 Order Conditions Anonymous complaint about septic odors emanating from the Matteis' Tavern property on March 21, 2023. This is a violation of their order. Specifically, section B.1.e. Nuisance odors shall not be perceivable beyond the property line of the wastewater treatment facility Violation None Complaint The Inn at Mattei's Tavern 443159 2014-0153-DWQ N
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 34
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
  
  
  
  
Expand/Contract Enforcement Actions
Enforcement Actions
Enforcement ID Enforcement Type Enf. Order No. Title Program Effective Date Status
459210 Notice of Violation None NOV 10/31/2024 for Railway Jonata, LLC, The Inn at Mattei's Tavern OWTS WDRMUNIOWTS 10/31/2024 Historical
Total Enforcement Actions: 1
  
  
  
  
Expand/Contract Enforcement Actions
Regulatory Measures linked to Related Parties
Reg. Measure ID Organization Regulatory Measure Type Program Effective Date Status
Total Regulatory Measures linked to Related Parties: 0
  
  
The current report was generated with data as of: 06/03/2025
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
Back to Main Page  |  Back to Top of Page