| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1151790 |
11/14/2025 |
Order Conditions |
Power failure of lift station storage tanks level sensor meant pumps did not engage, resulting in untreated overflow from the CMU lift station storage tanks, for which some analytes exceeded permit limits. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151789 |
11/14/2025 |
CAT1 |
Perchlorate Single Sample Maximum limit is 6 ug/L and reported value was 890 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151788 |
11/14/2025 |
CAT2 |
Zinc, Total Recoverable Single Sample Maximum limit is 100 ug/L and reported value was 256 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151787 |
11/14/2025 |
CAT2 |
Cadmium, Total Recoverable Single Sample Maximum limit is 1 ug/L and reported value was 1.18 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151786 |
11/14/2025 |
CAT2 |
Phenol, Single Compound Single Sample Maximum limit is 1 ug/L and reported value was 26 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151785 |
11/14/2025 |
CAT2 |
Bis (2-Ethylhexyl) Phthalate Single Sample Maximum limit is 1.8 ug/L and reported value was 7.3 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151784 |
11/14/2025 |
CAT2 |
1,2-Diphenylhydrazine Single Sample Maximum limit is 0.04 ug/L and reported value was 0.88 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151783 |
11/14/2025 |
CAT2 |
Lead, Total Recoverable Single Sample Maximum limit is 2.5 ug/L and reported value was 34.9 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151782 |
11/14/2025 |
CAT2 |
Copper, Total Recoverable Single Sample Maximum limit is 9 ug/L and reported value was 162 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1151781 |
11/14/2025 |
CAT2 |
Mercury, Total Recoverable Single Sample Maximum limit is 0.012 ug/L and reported value was 0.51 ug/L at EFF-002. |
Violation |
N |
eSMR |
Tajiguas Compost Management Unit |
459450 |
R3-2022-0035 |
N |
| 1130433 |
02/01/2024 |
OEV |
Flow Daily Maximum limit is 49999.0 GPD and reported value was 63700 GPD. |
Violation |
None |
Report |
Cachuma Lake Recreation Area WWTP |
448164 |
2014-0153-DWQ |
N |
| 1128880 |
02/29/2024 |
Order Conditions |
Wastewater was not managed in accordance with the approved Water and Wastewater Management Plan |
Violation |
None |
Report |
Tajiguas Compost Management Unit |
443847 |
2015-0121-DWQ |
Y |
| 1128879 |
02/29/2024 |
Order Conditions |
Discharge of wastes including overflow, wastewater, or bypass from transport, treatment, storage, or disposal systems to adjacent drainages or adjacent properties. |
Violation |
N |
Report |
Tajiguas Compost Management Unit |
443847 |
2015-0121-DWQ |
Y |
| 1126368 |
12/20/2023 |
Order Conditions |
Two separate discharge events from a sedimentation basin to Pila Creek with a combined total of 162,517 gallons |
Violation |
N |
Report |
Tajiguas Compost Management Unit |
443847 |
2015-0121-DWQ |
Y |
|
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|