| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1125307 |
10/31/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 47 ug/L and reported value was 83 ug/L. |
Violation |
None |
Report |
915 DeGuigne Drive Groundwater Treatment System |
397989 |
R2-2017-0048 |
Y |
| 1125131 |
10/03/2023 |
CAT2 |
Zinc, Total Recoverable Maximum Daily (MDEL) limit is 95 ug/L and reported value was 120 ug/L. |
Violation |
None |
Report |
915 DeGuigne Drive Groundwater Treatment System |
397989 |
R2-2017-0048 |
Y |
| 1111210 |
09/27/2022 |
Late Report |
Total xylene effluent limit violation occurred on 9-7-22. The Discharger became aware of the violation on 9-20-22 and did not report the violation to the Regional Water Board until 9-27-22. The 5-day report would have been due on 9-25-22, instead it was submitted on 11-11-22, upon request by the Regional Water Board. |
Violation |
None |
Report |
915 DeGuigne Drive Groundwater Treatment System |
397989 |
R2-2017-0048 |
N |
| 1111208 |
09/20/2022 |
Failure to Notify |
Total xylene effluent limit violation occurred on 9-7-22. The Discharger became aware of the violation on 9-20-22 and did not report the violation to the Regional Water Board until 9-27-22. The requirement is to report within 24 hours. |
Violation |
N |
Report |
915 DeGuigne Drive Groundwater Treatment System |
397989 |
R2-2017-0048 |
N |
| 1111202 |
09/07/2022 |
CAT2 |
Xylenes, Total Maximum Daily (MDEL) limit is 0.5 ug/L and reported value was 1.1 ug/L. |
Violation |
N |
Report |
915 DeGuigne Drive Groundwater Treatment System |
397989 |
R2-2017-0048 |
Y |
|
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|