Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1136728 |
10/21/2024 |
Deficient Monitoring |
Daily total coliform samples are required to be collected from the final effluent sample REC-001 and are used to represent samples collected at REC-002 and M-003A. On 10/21/2024, a temporary power outage occurred, and water was diverted from the aeration basin rather than discharged to the recycled system to respond to the outage, and to access the vault to make repairs by the maintenance staff. During this time, the daily compliance sample was collected during the diversion but was deemed unrepresentative of the final effluent as it was not being sent to the system for tertiary recycled water reuse. A representative sample for that day was not collected; however, based on prior results, there is no indication that water quality changed during this period. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1136727 |
10/21/2024 |
Deficient Monitoring |
Daily total coliform samples are required to be collected from the final effluent sample REC-001 and are used to represent samples collected at REC-002 and M-003A. On 10/21/2024, a temporary power outage occurred, and water was diverted from the aeration basin rather than discharged to the recycled system to respond to the outage, and to access the vault to make repairs by the maintenance staff. During this time, the daily compliance sample was collected during the diversion but was deemed unrepresentative of the final effluent as it was not being sent to the system for tertiary recycled water reuse. A representative sample for that day was not collected; however, based on prior results, there is no indication that water quality changed during this period. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1136726 |
10/21/2024 |
Deficient Monitoring |
Daily total coliform samples are required to be collected from the final effluent sample REC-001 and are used to represent samples collected at REC-002 and M-003A. On 10/21/2024, a temporary power outage occurred, and water was diverted from the aeration basin rather than discharged to the recycled system to respond to the outage, and to access the vault to make repairs by the maintenance staff. During this time, the daily compliance sample was collected during the diversion but was deemed unrepresentative of the final effluent as it was not being sent to the system for tertiary recycled water reuse. A representative sample for that day was not collected; however, based on prior results, there is no indication that water quality changed during this period. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135978 |
11/01/2024 |
Late Report |
Annual SMR ( PRETRPT ) report for 2023 (2736597) was due on 31-OCT-24 |
Violation |
None |
Report |
Los Alisos WD WWTP |
402182 |
R8-2015-0024 |
N |
1135139 |
09/11/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 34 mg/L at REC-003. |
Violation |
N |
eSMR |
Los Alisos WD WWTP |
402182 |
R8-2015-0024 |
N |
1135138 |
08/21/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 36 mg/L at REC-003. |
Violation |
N |
eSMR |
Los Alisos WD WWTP |
402182 |
R8-2015-0024 |
N |
1135137 |
09/11/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 18 mg/L at REC-002. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135136 |
08/07/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 16 mg/L at REC-002. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135135 |
09/11/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 18 mg/L at REC-001. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135134 |
08/07/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 16 mg/L at REC-001. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135133 |
07/10/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 16 mg/L at REC-001. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1135132 |
07/10/2024 |
CAT1 |
Nitrogen, Total (as N) Other limit is 10 mg/L and reported value was 16 mg/L at REC-002. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1133872 |
05/21/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Collection System Maintenance Failure (specify below) caused 165 gallons of sewage to spill from Other (specify below) at 2400 Main St, Irvine, CA 92614 to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
IRWD - OCSD Regional 1 CS |
338949 |
2022-0103-DWQ |
N |
1133666 |
03/27/2024 |
Sanitary Sewer Overflow/Spill/ |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 650 gallons of sewage to spill from Manhole at 2 Willowrun, Irvine, CA, 92604, USA to Drainage Conveyance System that discharges to surface water |
Violation |
None |
SSO |
Michelson WRP CS |
298936 |
2022-0103-DWQ |
N |
1130335 |
08/01/2024 |
CAT1 |
Nitrate, Total (as NO3) 12-Month Average limit is 45 mg/L and reported value was 50 mg/L at REC-001. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1129105 |
04/05/2024 |
CAT2 |
Hydrocarbons, Petroleum Maximum Daily (MDEL) limit is 100 ug/L and reported value was 246 ug/L at M-008. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
1128217 |
04/05/2024 |
CAT2 |
Hydrocarbons, Petroleum Daily Maximum limit is 100 ug/L and reported value was 246 ug/L at M-008. |
Violation |
N |
eSMR |
Michelson WWRF |
402182 |
R8-2015-0024 |
N |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|