| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1156382 |
06/04/2026 |
CAT1 |
Nitrate, Total (as N) Maximum Daily (MDEL) limit is 17 mg/L and reported value was 19 mg/L. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
449668 |
R3-2022-0046 |
N |
| 1154802 |
04/04/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average (Mean) limit is 45 mg/L and reported value was 68 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
| 1153620 |
03/31/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average (Mean) limit is 30 mg/L and reported value was 35 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
| 1153619 |
03/07/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average (Mean) limit is 45 mg/L and reported value was 54 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
| 1153373 |
03/17/2026 |
Order Conditions |
Failure to properly operate and maintain treatment facility in violation of Permit Section VI, Provisions, Subsection A, Standard Provisions, Items 1 and 2 requires the CSD to comply with all Standard Provisions and Central Coast Water Board Standard Provisions included in Attachment D of the Permit. Attachment D - Standard Provisions Section I, Standard Provisions - Permit Compliance, Subsection D, Proper Operation and Maintenance. Two of the three necessary process control aerators for Pond 1 failed with no existing backup or auxiliary systems in place, or in redundancy, to ensure continued compliance with the permit. |
Violation |
None |
Complaint |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
Y |
| 1153372 |
03/17/2026 |
Order Conditions |
Causing nuisance odors beyond treatment facility boundaries in violation of Permit Section VI, Provisions, Subsection A, Standard Provisions, Items 1 and 2 requiring the CSD to comply with all Standard Provisions and Central Coast Water Board Standard Provisions included in Attachment D of the Permit. Attachment D - Standard Provisions Section VIII, Central Coast Water Board Standard Provisions (January 2013), Subsection B, Central Coast Standard Provision - Provisions, Item 1 states the ¿Collection, treatment, and discharge of waste shall not create a nuisance or pollution, as defined in California Water Code (CWC) 13050.¿ |
Violation |
N |
Complaint |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
Y |
| 1152896 |
02/28/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average (Mean) limit is 45 mg/L and reported value was 51 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
| 1152895 |
02/28/2026 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 30 mg/L and reported value was 39 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
| 1149625 |
10/11/2025 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 51 mg/L at M-001. |
Violation |
N |
eSMR |
Heritage Ranch WWTP |
418018 |
R3-2017-0026 |
N |
|
Report currently showing last five years of violations. Click here to return to viewing one year of violations. Refer to the Interactive Violation Report for more data.
|