| Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
| 1160262 |
09/30/2026 |
Order Conditions |
Irrigation system along the north property was recently reinstated. A small section of piping was unknowingly supplied by 3WHP and experienced a leak. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1147879 |
08/27/2025 |
Deficient Monitoring |
Analyst Error for M001 CBOD 8-27-25 |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1147878 |
08/25/2025 |
Deficient Monitoring |
Analyst Error for Sample M002 CBOD 8-25-2025 |
Violation |
N |
eSMR |
Vallecitos WD Meadowlark WRP |
425154 |
R9-2018-0059 |
N |
| 1147877 |
08/25/2025 |
Deficient Monitoring |
Analyst error for site M002 CBOD resulting in less than 7 consecutive CBOD samples for 7-day monitoring per page E-6 of order R9-2018-0059 permit. |
Violation |
N |
eSMR |
Vallecitos WD Meadowlark WRP |
425154 |
R9-2018-0059 |
N |
| 1143730 |
04/28/2025 |
CAT1 |
Settleable Solids Instantaneous Maximum limit is 3.0 ml/L and reported value was 3.4 ml/L at M-001. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1141599 |
02/13/2025 |
Order Conditions |
8,750 gallons of chlorinated secondary treated effluent (3WHP) was spilled into the Encinas Creek flood control channel from a brow ditch. This was due to operator error performing cleaning activities. Cal OES and County of SD Dept of Environmental Health and Quality were notified 2-13-25. Sampling was not required per DEHQ. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1138283 |
11/03/2024 |
Order Conditions |
A pipe carrying chlorinated, secondary-treated effluent (3WHP) failed in a fully contained area near the secondary clarifiers of the Encina Water Pollution Control Facility. The spill lasted from 0100 to 0715 AM and totaled 9,375 gallons. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1126510 |
01/19/2024 |
Unauthorized Discharge |
Failsafe line break released 200 gallons of tertiary treated, reclaimed water with no chlorine residual into San Marcos Creek. Although the water was treated to Title 22 standards; the plant was not reclaiming, and the water was routed to the failsafe pipe-location M002. |
Violation |
N |
eSMR |
Vallecitos WD Meadowlark WRP |
425154 |
R9-2018-0059 |
N |
| 1124723 |
01/18/2024 |
Order Conditions |
At 11:30pm on Thursday January 18th, a minor equipment failure resulted in a release of chlorinated secondary effluent (3W) water, which was fully captured by our in-plant drainage system. The spill volume is estimated at 1500 gallons. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1120659 |
08/10/2023 |
Order Conditions |
5,980 gallons of chlorinated secondary effluent discharged from broken irrigation line to brow ditch with check dams; no observed discharge to creek. 115 gallons per day, 5 days a week from 5/31/23-8/10/23. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1119447 |
04/08/2023 |
Deficient Monitoring |
From April 1 to 14, 2023, Encina reported flow from M-002. During the week of April 2 to 8, the report appears to only include four monitoring results for CBOD at M-002. During the week of April 9 to 15, the report includes the required five monitoring results for CBOD at M-002. |
Violation |
N |
Report |
Carlsbad WRF |
425154 |
R9-2018-0059 |
N |
| 1119423 |
07/11/2022 |
Unauthorized Discharge |
2 W Hydropneumatic Tank drain is not alligned with the drain in the ground/concrete pad causing drain 2W water to overflow to adjacened ground which was draining via a french drain directly to the brow ditch, which ultimatly trickled to the storm channel (estimated 20 gallons). |
Violation |
N |
Report |
Carlsbad WRF |
425154 |
R9-2018-0059 |
N |
| 1119422 |
05/23/2022 |
Unauthorized Discharge |
The contractor broke an airvac on the discharge pipe, spilling 1,750 gallons of secondary-treated wastewater at the Leucadia Pump Station discharge pipe. Encina reported recovering 1,300 gallons of the spill. The spill reached flood control channel/receiving water. |
Violation |
N |
Report |
Carlsbad WRF |
425154 |
R9-2018-0059 |
N |
| 1104718 |
04/30/2022 |
CAT1 |
Carbonaceous Biochemical Oxygen Demand (CBOD) (5-day @ 20 Deg. C) Weekly Average (Mean) limit is 14000 lb/day and reported value was 14276 lb/day at M-001. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
N |
| 1104717 |
04/30/2022 |
CAT1 |
Carbonaceous Biochemical Oxygen Demand (CBOD) (5-day @ 20 Deg. C) Weekly Average (Mean) limit is 40 mg/L and reported value was 76.8 mg/L at M-001. |
Violation |
N |
eSMR |
Encina Water Pollution Control Facility |
425154 |
R9-2018-0059 |
Y |
|