Report Monthly SMR ( MONNPDES ) report for September 2016
  
  
  
  
  
General Information
Contract All Sections Expand All Sections
Agency Facility Reporting Period Due Date Date Received Certified By
Poseidon Resources (Channelside) LP Co. Claude "Bud" Lewis Carlsbad Desalination Plant 09/01/2016 to 09/30/2016 11/01/2016 10/31/2016 Peter MacLaggan
  
  
  
  
Expand/Contract Monitoring Locations
Monitoring Locations
Name Type Lat/Long Associated Discharge Point Receiving Water Description(+)
A-00 Receiving Water Monitoring 33.154444/-117.352222 None Pacific Ocean Coastal Waters SURF ZONE MONITORING STATION: 7,000 feet upcoast (northerly) of the discharge ch
A-10 Receiving Water Monitoring None None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 7,000 feet upcoast (northerly) of the discharge cha
A-20 Receiving Water Monitoring None None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 7,000 feet upcoast (northerly) of the discharge cha
A-30 Receiving Water Monitoring None None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 7,000 feet upcoast (northerly) of the discharge cha
A-40 Receiving Water Monitoring None None None 7000 feet upcoast (northerly) of the discharge channel, 3400 ft. offshore; surfa
C-10 Receiving Water Monitoring 33.14/-117.343056 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION:1,000 feet upcoast (northerly) of the discharge chan
C-20 Receiving Water Monitoring 33.139444/-117.344167 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION:1,000 feet upcoast (northerly) of the discharge chan
C-30 Receiving Water Monitoring 33.137778/-117.347222 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 1,000 feet upcoast (northerly) of the discharge cha
D-10 Receiving Water Monitoring 33.137222/-117.341944 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: Normal to the discharge channel, 656 feet (200 mete
D-20 Receiving Water Monitoring 33.136389/-117.343333 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: Normal to the discharge channel, 1,129 feet off the
D-30 Receiving Water Monitoring 33.135556/-117.344444 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: Normal to the discharge channel, 1,600 feet off the
D-50 Receiving Water Monitoring 33.133611/-117.347778 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: Normal to the discharge channel, 2,800 feet off the
E-10 Receiving Water Monitoring None None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 1,000 feet downcoast (southerly) of the discharge c
E-20 Receiving Water Monitoring 33.134722/-117.340556 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 1,000 feet downcoast (southerly) of the discharge c
E-30 Receiving Water Monitoring 33.132778/-117.344167 None Pacific Ocean Coastal Waters OFFSHORE MONITORING STATION: 1,000 feet downcoast (southerly) of the discharge c
M-001 Effluent Monitoring 38.138056/-117.339444 None N/A At a location downstream of all contributing flows to the Facility effluent, pri
M-002 Effluent Monitoring 38.138056/-117.339444 Outfall 001 N/A At the final effluent pond that contains combined Facility and Encina Power Stat
M-INF Influent Monitoring 38.138056/-117.339444 None N/A At a location upstream of all in-plant return flows where a representative influ
Total Monitoring Locations: 18
  
  
  
  
Expand/Contract No Discharge Dates
No Discharge Dates
Discharge Point Name Description(+) Dates of No Discharge Comments
  
  
  
  
Expand/Contract Analytical Data
Data Summary-Analytical
Monitoring Point Parameter Analytical Method Qualifier Result Units Sample Date MDL ML RL Comments
M-001 Chronic Toxicity Data Unavailable = 20 TUc 09/06/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable = 40 TUc 09/13/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable = 40 TUc 09/15/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable < 6.67 TUc 09/20/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable < 6.67 TUc 09/21/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable > 40 TUc 09/25/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable < 6.67 TUc 09/27/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Chronic Toxicity Data Unavailable = 20 TUc 09/28/2016 None None None EPA/600/R-95/136, 1995 West Coast Marine Chronic
M-001 Flow Data Unavailable = 57.33 MGD 09/01/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.29 MGD 09/02/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.01 MGD 09/03/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.03 MGD 09/04/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.03 MGD 09/05/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.42 MGD 09/06/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 56.71 MGD 09/07/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 56.22 MGD 09/08/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.92 MGD 09/09/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.67 MGD 09/10/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.78 MGD 09/11/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.09 MGD 09/12/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.85 MGD 09/13/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 57.58 MGD 09/14/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 56.13 MGD 09/15/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.27 MGD 09/16/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 54.26 MGD 09/17/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 51.1 MGD 09/18/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 32.87 MGD 09/19/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 49.25 MGD 09/20/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 31.38 MGD 09/21/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 22.32 MGD 09/22/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 19.13 MGD 09/23/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 19.23 MGD 09/24/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 22.43 MGD 09/25/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 37.01 MGD 09/26/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 54.29 MGD 09/27/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 56.47 MGD 09/28/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.8 MGD 09/29/2016 None None None Continuous Reading
M-001 Flow Data Unavailable = 55.61 MGD 09/30/2016 None None None Continuous Reading
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A < 1.3 mg/L 09/02/2016 None None None None
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A < 1.3 mg/L 09/09/2016 None None None None
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A < 1.3 mg/L 09/16/2016 None None None None
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A = 1.4 mg/L 09/20/2016 None None None None
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A < 1.3 mg/L 09/21/2016 None None None None
M-001 Oil and Grease HEM and SGT-HEM by Extraction and Gravimetry, Rev. A = 2 mg/L 09/26/2016 None None None None
M-001 Salinity Data Unavailable = 61 ppth 09/02/2016 None None None Units: ppt; Method: PSS-78
M-001 Salinity Data Unavailable = 62 ppth 09/09/2016 None None None Units: ppt; Method: PSS-78
M-001 Salinity Data Unavailable = 60 ppth 09/16/2016 None None None Units: ppt; Method: PSS-78
M-001 Salinity Data Unavailable = 57 ppth 09/26/2016 None None None Units: ppt; Method: PSS-78
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/02/2016 None None None None
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/09/2016 None None None None
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/16/2016 None None None None
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/20/2016 None None None None
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/21/2016 None None None None
M-001 Settleable Solids Standard Method (19th) 2540 F: Settleable Solids < 0.1 ml/L 09/26/2016 None None None None
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 75.4 Degrees F 09/02/2016 None None None Field Reading
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 75.6 Degrees F 09/09/2016 None None None Field Reading
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 67.9 Degrees F 09/16/2016 None None None Field Reading
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 67.8 Degrees F 09/20/2016 None None None Field Reading
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 71.6 Degrees F 09/21/2016 None None None Field Reading
M-001 Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 74.5 Degrees F 09/26/2016 None None None Field Reading
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 34 mg/L 09/02/2016 None None None None
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 37 mg/L 09/09/2016 None None None None
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 3 mg/L 09/16/2016 None None None None
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 56 mg/L 09/20/2016 None None None None
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 21 mg/L 09/21/2016 None None None None
M-001 Total Suspended Solids (TSS) Standard Method (19th) 2540 D: Tot. Sus. Solids Dried 103-105C = 40 mg/L 09/26/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 1.29 NTU 09/02/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 1.84 NTU 09/09/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 1.84 NTU 09/16/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 1.53 NTU 09/20/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 0.94 NTU 09/21/2016 None None None None
M-001 Turbidity Turbidity (Nephelometric) = 1.28 NTU 09/26/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 7.85 SU 09/02/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 7.71 SU 09/09/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 7.89 SU 09/16/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 8.05 SU 09/20/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 8.04 SU 09/21/2016 None None None None
M-001 pH Standard Method (19th) 4500-H+ B: pH by Electrometric Method = 7.93 SU 09/26/2016 None None None None
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.79 mmhos/cm 09/01/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.09 mmhos/cm 09/02/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.81 mmhos/cm 09/03/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.76 mmhos/cm 09/04/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.7 mmhos/cm 09/05/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.71 mmhos/cm 09/06/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 58.29 mmhos/cm 09/07/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.7 mmhos/cm 09/08/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.52 mmhos/cm 09/09/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.75 mmhos/cm 09/10/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.29 mmhos/cm 09/11/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.16 mmhos/cm 09/12/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.12 mmhos/cm 09/13/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.12 mmhos/cm 09/14/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 57.54 mmhos/cm 09/15/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 58.01 mmhos/cm 09/16/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 58.56 mmhos/cm 09/17/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 58.08 mmhos/cm 09/18/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 50.88 mmhos/cm 09/19/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 50.05 mmhos/cm 09/20/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 52 mmhos/cm 09/21/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 54.85 mmhos/cm 09/22/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 55.98 mmhos/cm 09/23/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.07 mmhos/cm 09/24/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 55.26 mmhos/cm 09/25/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 54.33 mmhos/cm 09/26/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 55.41 mmhos/cm 09/27/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 55.57 mmhos/cm 09/28/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 55.72 mmhos/cm 09/29/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Electrical Conductivity @ 25 Deg. C Data Unavailable = 56.69 mmhos/cm 09/30/2016 None None None Reporting continuous reading average; units: dS/m
M-002 Salinity Data Unavailable = 38 ppth 09/02/2016 None None None Units: ppt; Method: PSS-78
M-002 Salinity Data Unavailable = 39 ppth 09/09/2016 None None None Units: ppt; Method: PSS-78
M-002 Salinity Data Unavailable = 39 ppth 09/16/2016 None None None Units: ppt; Method: PSS-78
M-002 Salinity Data Unavailable = 33 ppth 09/26/2016 None None None Units: ppt; Method: PSS-78
M-INF Flow Data Unavailable = 113.74 MGD 09/01/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113.51 MGD 09/02/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113.03 MGD 09/03/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113.13 MGD 09/04/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113.11 MGD 09/05/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113.85 MGD 09/06/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 113 MGD 09/07/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 112.58 MGD 09/08/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 112.06 MGD 09/09/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.63 MGD 09/10/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 110.9 MGD 09/11/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 110.21 MGD 09/12/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.05 MGD 09/13/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 112.64 MGD 09/14/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.09 MGD 09/15/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 109.97 MGD 09/16/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 108.26 MGD 09/17/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 97.9 MGD 09/18/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 32.87 MGD 09/19/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 49.25 MGD 09/20/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 38.07 MGD 09/21/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 36.7 MGD 09/22/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 37.09 MGD 09/23/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 37.41 MGD 09/24/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 40.41 MGD 09/25/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 71.91 MGD 09/26/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 107.77 MGD 09/27/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.99 MGD 09/28/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.28 MGD 09/29/2016 None None None Continuous Reading
M-INF Flow Data Unavailable = 111.05 MGD 09/30/2016 None None None Continuous Reading
M-INF Salinity Data Unavailable = 34 ppth 09/02/2016 None None None Units: ppt; Method: PSS-78
M-INF Salinity Data Unavailable = 34 ppth 09/09/2016 None None None Units: ppt; Method: PSS-78
M-INF Salinity Data Unavailable = 34 ppth 09/16/2016 None None None Units: ppt; Method: PSS-78
M-INF Salinity Data Unavailable = 33 ppth 09/26/2016 None None None Units: ppt; Method: PSS-78
M-INF Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 71 Degrees F 09/02/2016 None None None Field Reading
M-INF Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 77.1 Degrees F 09/09/2016 None None None Field Reading
M-INF Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 64.4 Degrees F 09/16/2016 None None None Field Reading
M-INF Temperature Standard Method (19th) 2550 B: Temperature, Lab and Field Methods = 71.5 Degrees F 09/26/2016 None None None Field Reading
Total Analytical Data Points: 150
  
  
  
  
Expand/Contract Calculated Data
Data Summary-Calculated
Monitoring Point Parameter Analytical Method Qualifier Result Units Sample Date Comments
M-001 Flow Average Monthly (AMEL) = 48.82 MGD 09/30/2016 None
M-001 Oil and Grease Average Weekly (AWEL) < 1.3 mg/L 09/08/2016 None
M-001 Oil and Grease Average Weekly (AWEL) < 1.3 mg/L 09/15/2016 None
M-001 Oil and Grease Average Weekly (AWEL) = 0.9 mg/L 09/22/2016 None
M-001 Oil and Grease Instantaneous Maximum (IMAX) = 2 mg/L 09/26/2016 None
M-001 Oil and Grease Average Weekly (AWEL) < 2 mg/L 09/29/2016 None
M-001 Oil and Grease Average Monthly (AMEL) = 1 mg/L 09/30/2016 None
M-001 Settleable Solids Average Weekly (AWEL) < 0.1 ml/L 09/08/2016 None
M-001 Settleable Solids Average Weekly (AWEL) < 0.1 ml/L 09/15/2016 None
M-001 Settleable Solids Average Weekly (AWEL) < 0.1 ml/L 09/22/2016 None
M-001 Settleable Solids Instantaneous Maximum (IMAX) < 0.1 ml/L 09/26/2016 None
M-001 Settleable Solids Average Weekly (AWEL) < 0.1 ml/L 09/29/2016 None
M-001 Settleable Solids Average Monthly (AMEL) < 0.1 ml/L 09/30/2016 None
M-001 Total Suspended Solids (TSS) Average Monthly (AMEL) = 31.83 mg/L 09/30/2016 None
M-001 Turbidity Average Weekly (AWEL) = 1.29 NTU 09/08/2016 None
M-001 Turbidity Average Weekly (AWEL) = 1.84 NTU 09/15/2016 None
M-001 Turbidity Instantaneous Maximum (IMAX) = 1.84 NTU 09/16/2016 None
M-001 Turbidity Average Weekly (AWEL) = 1.44 NTU 09/22/2016 None
M-001 Turbidity Average Weekly (AWEL) = 1.28 NTU 09/29/2016 None
M-001 Turbidity Average Monthly (AMEL) = 1.45 NTU 09/30/2016 None
M-001 pH Instantaneous Minimum (IMIN) = 7.71 SU 09/09/2016 None
M-001 pH Instantaneous Maximum (IMAX) = 8.05 SU 09/20/2016 None
M-002 Salinity 1-Hour Average (Mean) = 38 ppth 09/02/2016 Units: ppt; Method: PSS-78
M-002 Salinity Daily Average (Mean) = 38 ppth 09/02/2016 Units: ppt; Method: PSS-78
M-002 Salinity Daily Average (Mean) = 39 ppth 09/09/2016 Units: ppt; Method: PSS-78
M-002 Salinity 1-Hour Average (Mean) = 39 ppth 09/09/2016 Units: ppt; Method: PSS-78
M-002 Salinity 1-Hour Average (Mean) = 39 ppth 09/16/2016 Units: ppt; Method: PSS-78
M-002 Salinity Daily Average (Mean) = 39 ppth 09/16/2016 Units: ppt; Method: PSS-78
M-002 Salinity 1-Hour Average (Mean) = 33 ppth 09/26/2016 Units: ppt; Method: PSS-78
M-002 Salinity Daily Average (Mean) = 33 ppth 09/26/2016 Units: ppt; Method: PSS-78
Total Calculated Data Points: 30
  
  
  
  
Expand/Contract Calculated Data
Violations
Violation ID Violation Date Violation Type Description(+) Corrective Action Created By Last Modified By
1014608 09/13/2016 Chronic Toxicity Chronic Toxicity Monthly Average limit is 16.5 TUc and reported value was 40 TUc A Toxicity Investigation Evaluation (TIE) is being conducted in conformance with the Order and the approved Toxicity Reduction Evaluation (TRE) Plant. The TIE includes investigative toxicity testing to identify the source of the toxicity that is causing the effects observed in the urchin fertilization test. During the month of September, the plant operator conducted mapping of various discharge stream configurations and collected a set of grab samples representing these configurations. Split samples were sent to the toxicity laboratory and the analytical laboratory for testing. The analytical laboratory ran a scan of trace elements, volatile and semi-volatile organic compounds. The toxicity laboratory is using various treatment methods for the samples and analyzing treated samples for toxicity in an effort to identify constituent(s) contributing to elevated toxicity. While there is no conclusion from the TIE testing as of yet, the investigation is ongoing and ruled out several constituent classes (including metals and salinity). Additional sampling and testing will continue in an effort to identify and minimize the sources(s) of toxicity. Discharger Discharger
1014609 09/15/2016 Chronic Toxicity Chronic Toxicity Monthly Average limit is 16.5 TUc and reported value was 40 TUc A Toxicity Investigation Evaluation (TIE) is being conducted in conformance with the Order and the approved Toxicity Reduction Evaluation (TRE) Plant. The TIE includes investigative toxicity testing to identify the source of the toxicity that is causing the effects observed in the urchin fertilization test. During the month of September, the plant operator conducted mapping of various discharge stream configurations and collected a set of grab samples representing these configurations. Split samples were sent to the toxicity laboratory and the analytical laboratory for testing. The analytical laboratory ran a scan of trace elements, volatile and semi-volatile organic compounds. The toxicity laboratory is using various treatment methods for the samples and analyzing treated samples for toxicity in an effort to identify constituent(s) contributing to elevated toxicity. While there is no conclusion from the TIE testing as of yet, the investigation is ongoing and ruled out several constituent classes (including metals and salinity). Additional sampling and testing will continue in an effort to identify and minimize the sources(s) of toxicity. Discharger Discharger
1014610 09/25/2016 Chronic Toxicity Chronic Toxicity Monthly Average limit is 16.5 TUc and reported value was 40 TUc A Toxicity Investigation Evaluation (TIE) is being conducted in conformance with the Order and the approved Toxicity Reduction Evaluation (TRE) Plant. The TIE includes investigative toxicity testing to identify the source of the toxicity that is causing the effects observed in the urchin fertilization test. During the month of September, the plant operator conducted mapping of various discharge stream configurations and collected a set of grab samples representing these configurations. Split samples were sent to the toxicity laboratory and the analytical laboratory for testing. The analytical laboratory ran a scan of trace elements, volatile and semi-volatile organic compounds. The toxicity laboratory is using various treatment methods for the samples and analyzing treated samples for toxicity in an effort to identify constituent(s) contributing to elevated toxicity. While there is no conclusion from the TIE testing as of yet, the investigation is ongoing and ruled out several constituent classes (including metals and salinity). Additional sampling and testing will continue in an effort to identify and minimize the sources(s) of toxicity. Discharger Discharger
1014611 09/28/2016 Chronic Toxicity Chronic Toxicity Monthly Average limit is 16.5 TUc and reported value was 20 TUc A Toxicity Investigation Evaluation (TIE) is being conducted in conformance with the Order and the approved Toxicity Reduction Evaluation (TRE) Plant. The TIE includes investigative toxicity testing to identify the source of the toxicity that is causing the effects observed in the urchin fertilization test. During the month of September, the plant operator conducted mapping of various discharge stream configurations and collected a set of grab samples representing these configurations. Split samples were sent to the toxicity laboratory and the analytical laboratory for testing. The analytical laboratory ran a scan of trace elements, volatile and semi-volatile organic compounds. The toxicity laboratory is using various treatment methods for the samples and analyzing treated samples for toxicity in an effort to identify constituent(s) contributing to elevated toxicity. While there is no conclusion from the TIE testing as of yet, the investigation is ongoing and ruled out several constituent classes (including metals and salinity). Additional sampling and testing will continue in an effort to identify and minimize the sources(s) of toxicity. Discharger Discharger
1014612 09/06/2016 Chronic Toxicity Chronic Toxicity Monthly Average limit is 16.5 TUc and reported value was 20 TUc A Toxicity Investigation Evaluation (TIE) is being conducted in conformance with the Order and the approved Toxicity Reduction Evaluation (TRE) Plant. The TIE includes investigative toxicity testing to identify the source of the toxicity that is causing the effects observed in the urchin fertilization test. During the month of September, the plant operator conducted mapping of various discharge stream configurations and collected a set of grab samples representing these configurations. Split samples were sent to the toxicity laboratory and the analytical laboratory for testing. The analytical laboratory ran a scan of trace elements, volatile and semi-volatile organic compounds. The toxicity laboratory is using various treatment methods for the samples and analyzing treated samples for toxicity in an effort to identify constituent(s) contributing to elevated toxicity. While there is no conclusion from the TIE testing as of yet, the investigation is ongoing and ruled out several constituent classes (including metals and salinity). Additional sampling and testing will continue in an effort to identify and minimize the sources(s) of toxicity. Discharger Discharger
Total Violations: 5
  
  
  
  
Expand/Contract Attachment Data
Attachments
File Name Description Size
09022016 NPDES Weekly CDP Lab.pdf None 246 KB
09022016 NPDES Weekly.PDF None 176 KB
09022016_COC.pdf None 40 KB
09092016 NPDES Weekly CDP Lab.pdf None 242 KB
09092016 NPDES Weekly.PDF None 176 KB
09092016_COC.pdf None 41 KB
09162016 NPDES Weekly CDP Lab.pdf None 242 KB
09162016 NPDES Weekly.PDF None 176 KB
09162016_COC.pdf None 40 KB
09202016 NPDES Daily CDP Lab.pdf None 231 KB
09202016 NPDES Daily.PDF None 168 KB
09202016_COC_Daily.pdf None 37 KB
09212016 092016 NPDES Daily CDP Lab.pdf None 231 KB
09212016 NPDES Daily.PDF None 161 KB
09212016_COC_Daily.pdf None 40 KB
09262016 NPDES Weekly.PDF None 179 KB
09262016_COC.pdf None 43 KB
CDP Chronic Daily_092116 Sample.pdf None 1 MB
CDP Chronic Daily_092716 Sample.pdf None 954 KB
CDP Chronic Weekly_090616 Sample.pdf None 1 MB
CDP Chronic Weekly_091316 Sample.pdf None 941 KB
CDP Chronic Weekly_091516 Sample.pdf None 896 KB
CDP Chronic Weekly_092516 Sample.pdf None 915 KB
CDP Chronic Weekly_092816 Sample.pdf None 973 KB
Total Attachments: 24
  
  
  
  
Expand/Contract Cover Letter
Cover Letter
File Name
Carlsbad NPDES DMR Cover Letter - Sept 2016.pdf
Total No. of Cover Letter Files: 1      Cover Leter Text: No
  
  
The current report was generated with data as of: 04/17/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
Back to Main Page  |  Back to Top of Page