1078136 |
12/27/2019 |
UAUTHDISC |
3,100-gallon spill of untreated groundwater that reached San Tomas Aquino Creek. The treatment system overflowed at the media equalization tank that had faulty design and operation of level sensors. As a result, the sand filter preceding the equalization tank continued to move process groundwater to it. |
The Discharger installed a high-high level sensor in equalization tank is connected to autodialer and sand filter pump. Discharger revised emergency procedures to quickly address spills. Discharger reviewed reporting procedures to expedite notifications to the Water Board. Discharger will retrain field personnel to do monitoring response to a spill and perform receiving water sampling. |
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|
|
Total Violations: 1
|
Priority Violations: 0
|
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.
|
Violation Types |
UAUTHDISC = Unauthorized Discharge
|
|
|
|
Enforcement Actions
|
|
Total Enf Actions: 0
|
|
|
Inspections
|
|
Total Inspections: 0 |
Last Inspection: None |
|