1080910 |
10/07/2020 |
LREP |
Violation of Attachment section IX.D.3 - Submittal of 5-day permit violation report. The 5-day permit violation report describing the January 30, 2020 effluent limit violations for copper and zinc was due at the latest on February 24, 2020. It wasn''t submitted until October 7, 2020, after an email request from the Water Board. |
The Discharger acknowledged this permit compliance failure in its October 7, 2020, permit violation report. |
Violation |
B |
Report |
1080906 |
02/20/2020 |
CAT2 |
Copper, Total Recoverable Maximum Daily (MDEL) limit is 14 ug/L and reported value was 32.7 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |
1080907 |
02/20/2020 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 7 ug/L and reported value was 32.7 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |
1080904 |
01/30/2020 |
CAT2 |
Copper, Total Recoverable Maximum Daily (MDEL) limit is 14 ug/L and reported value was 206 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |
1080905 |
01/30/2020 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 7 ug/L and reported value was 206 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |
1080909 |
01/30/2020 |
CAT2 |
Zinc, Total Recoverable Maximum Daily (MDEL) limit is 95 ug/L and reported value was 1320 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |
1080908 |
01/30/2020 |
CAT2 |
Zinc, Total Recoverable Monthly Average limit is 47 ug/L and reported value was 1320 ug/L. |
As a corrective action the discharger switched to the sanitary sewer and replaced treatment system copper fittings with PVC. Discharge to receiving water has not resumed since. |
Violation |
B |
Report |