Region Place ID Place Name Place Type Place Address Place County
5S 252771 Beach Wastewater Treatment Facility Wastewater Treatment Facility 1000 Beach Rio Vista, CA, 94571 Solano

Expand/Contract Related Parties
Related Parties
Party Party Type Party Name Role Classification Relationship Start Date Relationship End Date
544702 Person Derek Dill Is Onsite Manager For 03/17/2023
585607 Person Manuel Molina Is Onsite Manager For 11/08/2022 03/27/2023
526437 Person John Bailey Is Onsite Manager For 07/07/2022
520752 Person Fermin Garcia Is Onsite Manager For 10/07/2021
596523 Person Robert Hickey Is Onsite Manager For 04/05/2019
545655 Person Scott Anthony Biocic Is Onsite Manager For 01/09/2018 05/31/2022
520752 Person Fermin Garcia Is Onsite Manager For 09/03/2015 02/03/2021
585607 Person Manuel Molina Is Onsite Manager For 06/25/2015 09/01/2015
585607 Person Manuel Molina Pending-is a data submitter for 06/24/2015 06/25/2015
321250 Person Stephen J. Danehy Is Onsite Manager For 07/30/2013 06/24/2015
520218 Person Chris McAuliffe Is Onsite Manager For 10/14/2009 08/13/2014
37437 Organization Rio Vista City Owner City Agency 11/01/1994
Total Related Parties: 12

Expand/Contract Regulatory Measures
Regulatory Measures
Reg Measure ID Reg Measure Type Region Program Order No. WDID Effective Date Expiration Date Status Amended?
428745 NPDES Permit 5S NPDMUNIOTH R5-2019-0016 5A480104001 04/01/2019 03/31/2024 Active N
395363 NPDES Permit 5S NPDMUNIOTH R5-2014-0012 5A480104001 03/28/2014 03/01/2019 Historical Y
366405 NPDES Permit 5S NPDMUNIOTH R5-2008-0108-01 5A480104001 09/19/2008 09/30/2013 Historical N
351548 NPDES Permit 5S NPDMUNIOTH R5-2008-0108 5A480104001 09/19/2008 09/30/2013 Historical Y
148420 NPDES Permit 5S NPDMUNIOTH R5-2001-0178 5A480104001 06/14/2001 06/01/2006 Historical N
146416 NPDES Permit 5S NPDMUNIOTH 95-108 5A480104001 04/28/1995 04/01/2000 Historical N
140430 NPDES Permit 5S NPDMUNIOTH 90-137 5A480104001 05/25/1990 05/01/1995 Historical N
139134 NPDES Permit 5S NPDMUNIOTH 84-134 5A480104001 11/28/1984 11/01/1989 Historical N
Total Reg Measures: 8

Expand/Contract Violations
Violations
Violation ID Occurred Date Violation Type (-) Violation Description Corrective Action Status Classification Source
1125991 03/29/2024 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 40.7 MPN/100 mL at EFF-001. Chlorine dose was appropriate, project management confirmed proper sample procedure in field. Management suspects air leaks/losses through the system are contributing to poor air transfer and increase in turbidity that may be translating into the low coliform accounts for total (all results negative for fecal). Project staff intend on doing basin entry to inspect for premature fouling of membrane diffusers, secure endcaps, and replace any discovered and report findings to the SWRCB. Violation U eSMR
1124647 01/25/2024 OEV Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-001. Get clarifier 3 back online to increase contact time in disinfection chamber. Violation U eSMR
1124648 01/23/2024 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 33 MPN/100 mL at EFF-001. A subsequent issue was discovered that coincided with the coliform positive events (4-20 mA signal was found to be intermittent, wire corroded-replaced). Clarifier 3 offline-may have resulted in reduced disinfection time through contact chamber during high flow periods. Veolia/Telstar are pulling wire in the month of March to get unit back online. Violation U eSMR
1123698 12/31/2023 OEV Electrical Conductivity @ 25 Deg. C Annual Average (Mean) limit is 1300 mmhos/cm and reported value was 1305 mmhos/cm at EFF-001. Eliminate contributors of conductivity into the collection system. Violation B eSMR
1119159 06/30/2023 DMON Discharger did not report mercury at EFF-001 at the required frequency (WDRs require 1/quarter, and discharger reported 0/quarter). Violation B Report
1119158 05/27/2023 DMON Discharger did not report temperature at EFF-001 at the required frequency (WDRs require 5/week, and discharger reported 4/week). Violation B Report
1113579 02/02/2023 LREP Discharger did not submit the 2022 Mercury PPP Progress Report on time. The report was due on 2/1/2023, and was not submitted as of 2/22/2023. Violation B Report
1113578 12/31/2022 DMON Discharger did not report effluent yearly average conductivity, yearly mercury mass load, yearly methylmercury mass load; and yearly TDS at SPL-00. In addition, the discharger did not include a cover letter with the 2022 Annual SMR. Violation B Report
1112751 12/31/2022 OEV Electrical Conductivity @ 25 Deg. C Annual Average (Mean) limit is 1300 mmhos/cm and reported value was 1385 mmhos/cm at EFF-001. *** Dismissed:Violation created in error by the discharger. The source water needs to be lower in order to meet the discharge limit. Violation B eSMR
1112517 12/21/2022 OEV Total Coliform 7-Day Median limit is 23.0 MPN/100 mL and reported value was 76 MPN/100 mL at EFF-001. Investigation continues as to the cause of the violation Violation B eSMR
1110762 10/11/2022 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 79 MPN/100 mL at EFF-001. Investigation is on-going. Violation B eSMR
1110654 09/30/2022 Deficient Reporting Discharger did not report monitoring results for hardness in September. Violation B Report
1110657 09/30/2022 Deficient Reporting Discharger did not report monitoring results in Q3 2022 for the temperature difference between effluent and receiving water. Violation B Report
1110653 07/21/2022 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 176 MPN/100 mL at EFF-001. Violation B Report
1107804 07/20/2022 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-001. Continue to monitor process for adequate free chorine. Chlorine contact basins are cleaned weekly. Violation B eSMR
1107803 07/12/2022 CAT2 Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 5.7 mg/L at EFF-001. See other report from same event Violation B eSMR
1107802 07/12/2022 CAT2 Chlorine, Total Residual 4-Day Average (Mean) limit is 0.011 mg/L and reported value was 0.055 mg/L at EFF-001. Telstar responded but was not able to identify any specific fixes. System was restarted and working well since. Violation B eSMR
1106516 06/14/2022 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 85 MPN/100 mL at EFF-001. Instructed staff to maintain a higher level of chlorine residual. Violation B eSMR
1102745 02/23/2022 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-001. Process improved quickly once aeration was reduced to 0.8-1.0 mg/L. Violation B eSMR
1102743 02/16/2022 OEV Total Coliform 7-Day Median limit is 23.0 MPN/100 mL and reported value was 46 MPN/100 mL at EFF-001. Process improved quickly once aeration was reduced to 0.8-1.0 mg/L. Violation B eSMR
1099190 01/11/2022 Order Conditions Discharger was not able to provide requested daily bench sheets recording effluent pH results for December 2020 and January 2021. Violation B Inspection
1102232 12/31/2021 Deficient Reporting Discharger did not report receiving water visual observations or the temperature difference between effluent and receiving water during Q4 2021, as required by the WDRs. Violation B Report
1098600 11/30/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 66 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1098599 11/24/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 66 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1098598 11/18/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 81 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1098596 11/12/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 865 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1098602 11/08/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 105 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1098601 11/02/2021 OEV Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 79 MPN/100 mL at EFF-001. Additional process monitoring was conducted as the plant recovered. Violation B eSMR
1097427 10/31/2021 CAT1 BOD5 @ 20 Deg. C, Percent Removal Monthly Average limit is 85 % and reported value was 84 % at EFF-001. Increased process monitoring of effluent BOD, TSS, Ammonia-N, pH, Temperature and Total Coliforms. Violation B eSMR
1097426 10/31/2021 CAT1 Total Suspended Solids (TSS), Percent Removal Monthly Average limit is 85 % and reported value was 76 % at EFF-001. Increased process monitoring of effluent BOD, TSS, Ammonia-N, pH, Temperature and Total Coliforms. Violation B eSMR
1097425 10/23/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 71 mg/L at EFF-001. Increased process monitoring of effluent BOD, TSS, Ammonia-N, pH, Temperature and Total Coliforms. Violation B eSMR
1097424 10/23/2021 CAT1 Total Suspended Solids (TSS) Weekly Average limit is 45.0 mg/L and reported value was 55.0 mg/L at EFF-001. Increased process monitoring of effluent BOD, TSS, Ammonia-N, pH, Temperature and Total Coliforms. Violation B eSMR
1102231 09/30/2021 Deficient Reporting Discharger did not report the temperature difference between effluent and receiving water during Q3 2021 as required by the WDRs. Violation B Report
1102229 09/30/2021 CAT1 Ammonia, Total (as N) Monthly Average limit is 11 mg/L and reported value was 13 mg/L at EFF-001. Violation B Report
1102230 09/30/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 30 mg/L and reported value was 50 mg/L at EFF-001. Violation B Report
1102228 09/25/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 86 mg/L at EFF-001. Violation B Report
1093035 05/28/2021 Deficient Reporting Discharger was not able to report continuous monitoring data related to influent flow, effluent flow, and chlorine residual during 27-28 May 2021, due to a internet network outage. Violation B Report
1093034 04/27/2021 Deficient Reporting Discharger was not able to report continuous monitoring data related to influent flow, effluent flow, and chlorine residual during 22-27 April 2021, due to a internet network outage. Violation B Report
1086940 01/31/2021 CAT1 BOD5 @ 20 Deg. C, Percent Removal Monthly Average limit is 85 % and reported value was 70 % at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086936 01/31/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 30 mg/L and reported value was 51 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086937 01/31/2021 CAT1 Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 49 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086941 01/31/2021 CAT1 Total Suspended Solids (TSS), Percent Removal Monthly Average limit is 85 % and reported value was 24 % at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086939 01/16/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 81 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086943 01/16/2021 CAT1 Total Suspended Solids (TSS) Weekly Average limit is 45 mg/L and reported value was 94 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086938 01/09/2021 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 106 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1086942 01/09/2021 CAT1 Total Suspended Solids (TSS) Weekly Average limit is 45 mg/L and reported value was 95 mg/L at EFF-001. Evaluating continuous influent ORP monitoring solutions. Violation B eSMR
1085220 12/31/2020 OEV Electrical Conductivity @ 25 Deg. C Annual Average (Mean) limit is 1300 umhos/cm and reported value was 1322 umhos/cm at EFF-001. City of Rio Vista has a Salinity Reduction Program in place. Violation B eSMR
1086964 12/31/2020 CAT1 Total Suspended Solids (TSS), Percent Removal Monthly Average limit is 85 % and reported value was 78 % at EFF-001. Violation B Report
1086962 12/12/2020 CAT1 Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 45 mg/L and reported value was 58 mg/L at EFF-001. Violation B Report
1086963 12/12/2020 CAT1 Total Suspended Solids (TSS) Weekly Average limit is 45 mg/L and reported value was 56 mg/L at EFF-001. Violation B Report
1064526 08/10/2019 DMON Discharger failed to monitor temperature and pH at EFF-001 at the required frequency during the week ending 10 August 2019. Instructed plant personnel that everyone is responsible for ensuring pH and temperature readings are performed five times per week. Violation B eSMR
1065163 06/30/2019 DMON Discharger failed to monitor for zinc at EFF-001 at the required frequency during Q2 2019. Violation B Report
1060037 05/23/2019 DMON Discharger failed to monitor BOD at INF-001 and EFF-001 at the required frequency during the week ending 5/23/19. FGL wrote a letter explaining what happened and has been submitted with this report. Violation B eSMR
1060038 05/19/2019 Order Conditions Flow Daily Discharge limit is 0.65 million gallons and reported value was 0.71 million gallons at EFF-001. Reported to the regional board case worker and City personnel. Violation B eSMR
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 54 Priority Violations: 0
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.

Violation Types
CAT1 = Category 1 Pollutant (Effluent Violation for Group 1 Pollutant) CAT2 = Category 2 Pollutant (Effluent Violation for Group 2 Pollutant)
DMON = Deficient Monitoring Deficient Reporting = Deficient Reporting
LREP = Late Report Order Conditions = Order Conditions
OEV = Other Effluent Violation

Expand/Contract Enforcement Actions
Enforcement Actions
Enf Id Enf Type Enf Order No. Effective Date Status
455407 Admin Civil Liability R5-2023-0509 03/21/2024 Active
455853 Notice of Violation null 02/15/2024 Historical
453924 Notice of Violation null 08/14/2023 Historical
452590 Notice of Violation null 04/24/2023 Historical
451318 Notice of Violation null 02/22/2023 Historical
450338 Notice of Violation null 11/30/2022 Historical
449665 Admin Civil Liability R5-2022-0503 09/28/2022 Historical
449177 Notice of Violation null 09/13/2022 Historical
447848 Notice of Violation null 05/27/2022 Historical
447005 Notice of Violation null 03/17/2022 Historical
446360 Notice of Violation null 01/20/2022 Historical
444521 Notice of Violation null 08/10/2021 Historical
443451 Notice of Violation null 05/28/2021 Historical
442399 Notice of Violation null 03/01/2021 Historical
434874 Notice of Violation null 10/11/2019 Historical
422317 Notice of Violation 06/20/2018 Historical
419887 Admin Civil Liability R5-2018-0511 03/13/2018 Historical
419065 Notice of Violation 01/18/2018 Historical
413237 Notice of Violation 05/15/2017 Historical
408121 Admin Civil Liability R5-2016-0520 08/29/2016 Historical
407851 Notice of Violation 07/20/2016 Historical
406348 Notice of Violation 02/23/2016 Historical
406346 Notice of Violation 01/06/2016 Historical
402725 13267 Letter 08/11/2015 Historical
402217 Notice of Violation 07/01/2015 Historical
395277 Admin Civil Liability R5-2014-0512 04/07/2014 Historical
394140 Notice of Violation 12/06/2013 Historical
393152 Admin Civil Liability R5-2013-0572 09/04/2013 Historical
392390 Notice of Violation 05/14/2013 Historical
390611 Notice of Violation 05/14/2013 Historical
385682 Notice of Violation 06/21/2012 Historical
385505 Notice of Violation 06/04/2012 Historical
382981 Notice of Violation 01/13/2012 Historical
381228 13267 Letter 08/29/2011 Historical
378687 Notice of Violation 04/12/2011 Historical
378178 Notice of Violation 03/15/2011 Historical
377970 Admin Civil Liability WQ-2011-0001-EXEC 01/28/2011 Historical
377239 Notice of Violation 01/14/2011 Historical
377147 Admin Civil Liability R5-2011-0502 01/07/2011 Historical
376598 Notice of Violation 11/10/2010 Historical
376331 Notice of Violation 10/21/2010 Historical
375062 Notice of Violation 07/13/2010 Historical
374829 Admin Civil Liability R5-2010-0529 07/01/2010 Historical
373196 Notice of Violation 02/17/2010 Historical
374739 Notice of Violation 12/17/2009 Historical
351549 Time Schedule Order R5-2008-0109 09/19/2008 Active
344797 Admin Civil Liability R5-2008-0524 05/05/2008 Historical
256001 Oral Communication 06/06/2005 Historical
255996 Oral Communication 01/24/2005 Historical
255964 Oral Communication 11/09/2004 Historical
251813 Oral Communication 03/18/2004 Historical
250587 Oral Communication 12/31/2003 Historical
249819 Oral Communication 10/08/2003 Historical
242937 Oral Communication 07/02/2003 Historical
256947 Oral Communication 02/05/2003 Historical
256945 Oral Communication 01/10/2003 Historical
256926 Oral Communication 11/20/2002 Historical
256906 Oral Communication 09/24/2002 Historical
246526 Admin Civil Liability R5-2002-0512 07/10/2002 Historical
256904 Oral Communication 07/09/2002 Historical
256872 Oral Communication 05/01/2002 Historical
256875 Oral Communication 03/05/2002 Historical
238859 Oral Communication 12/12/2001 Historical
238858 Oral Communication 10/23/2001 Historical
245770 Admin Civil Liability R5-2001-0185 10/03/2001 Historical
246525 Admin Civil Liability R5-2001-0524 06/06/2001 Withdrawn
231575 Oral Communication 11/02/2000 Historical
231570 Oral Communication 09/27/2000 Historical
231395 Oral Communication 08/22/2000 Historical
231196 Staff Enforcement Letter 06/12/2000 Historical
232406 Oral Communication 04/18/2000 Historical
232121 Notice of Violation 03/17/2000 Historical
231637 Oral Communication 02/01/2000 Historical
Total Enf Actions: 73

Expand/Contract Inspections
Inspections
Inspection ID Inspection Type Lead Inspector Actual End Date Planned Violations Attachment
46269962 B Type compliance inspection Jon Rohrbough 01/11/2022 Y 1 Download
33964510 Prerequirement inspection Danielle Goode (Multiple) 08/30/2018 N 0 Download
27893285 B Type compliance inspection Ayda Soltani 03/15/2017 N 0 [Attachments]
21409881 Follow-up inspection (noncompliance) Lucio Orellana 07/30/2015 N 0 [Attachments]
20378128 B Type compliance inspection Lucio Orellana 04/23/2015 N 1 Download
12955768 B Type compliance inspection Dania Jimmerson (Multiple) 06/26/2013 N 0 Download
11040836 A Type compliance inspection Lucio Orellana 12/28/2012 N 0 N/A
1770051 B Type compliance inspection Betsy Richert 05/22/2009 N 6 N/A
1478466 B Type compliance inspection Oscar Biondi 06/12/2008 Y 0 [Attachments]
1476693 B Type compliance inspection Oscar Biondi 06/12/2008 Y 0 N/A
329491 B Type compliance inspection Renan Jauregui 02/19/2003 Y 0 N/A
322192 B Type compliance inspection Renan Jauregui 12/12/2001 Y 0 N/A
322195 B Type compliance inspection Renan Jauregui 11/08/2000 Y 0 N/A
322193 A Type compliance inspection Renan Jauregui 05/10/2000 Y 0 N/A
322191 B Type compliance inspection Jim Maughan 05/21/1998 Y 0 N/A
322194 A Type compliance inspection Isaac Kaing 12/06/1994 Y 0 N/A
Total Inspections: 16 Last Inspection: 01/11/2022
  
The current report was generated with data as of: 05/03/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
Back to Main Page  |  Back to Top of Page