Welcome to California
 California Home
Welcome to California - images of Golden Gate Bridge, ocean sunset, waterfall, flowers, and city skyline California Home Welcome to the California Environmental Protection Agency
 California Integrated Water Quality System Project (CIWQS)
   Facility At-A-Glance Report

  
   [VIEW PRINTER FRIENDLY VERSION] [EXPORT THIS REPORT TO EXCEL]

  
   SEARCH CRITERIA:      [REFINE SEARCH] [NEW SEARCH] [GLOSSARY]
Place ID 241842
  
  
  
  
Hide All Show All
General Information
Region Place ID Place Name Place Type Place Address Place County
5S 241842 CDCR - Mule Creek State Prison WWTP Prison 4001 State Hwy 104 Ione, CA, 95640 Amador

Expand/Contract Related Parties
Related Parties
Party Party Type Party Name Role Classification Relationship Start Date Relationship End Date
502020 Person Michael Williams Contact 12/11/2015
562221 Organization Ca Dept of Forestry Fire Academy Owner and Operator State Agency 12/11/2015
535911 Organization Ca Dept of Corrections & Rehabilitation Owner and Operator State Agency 12/11/2015
Total Related Parties: 3

Expand/Contract Regulatory Measures
Regulatory Measures
Reg Measure ID Reg Measure Type Region Program Order No. WDID Effective Date Expiration Date Status Amended?
368766 WDR 5S WDRMUNILRG R5-2015-0129 5B030802002 12/11/2015 12/11/2025 Active N
147747 WDR 5S WDRMUNILRG R5-2000-0088 5B030802002 04/28/2000 04/28/2010 Historical N
139905 WDR 5S WDR 87-166 5B030802002 09/25/1987 09/22/1997 Historical N
Total Reg Measures: 3

Expand/Contract Violations
Violations
Violation ID Occurred Date Violation Type (-) Violation Description Corrective Action Status Classification Source
1106653 07/22/2022 UAUTHDISC On 23 July 2022 Board staff received a Spill Report #22-4181 from the Office of Emergency Services (OES) describing a spill that occurred between the hours of 6 PM Friday 22 July 2022 and 6 AM Saturday 23 July 2022. CDCR staff submitted a Spill Notification Report on 25 July 2022 with further details, pictures, and a map of the spill. CDCR staff stated in that report that a power failure/surge tripped the uninterruptible power supply (UPS) to enter alarm mode and then fail to reset. This caused the Supervisory Control and Data Acquisition (SCADA) system to crash, halting operation of the wastewater treatment plant. However as wastewater continued to flow into the plant causing the effluent basin to fill, eventually tripping a secondary high level alarm. Although the alarm called out it was not relayed to an operator by the Main Control group so the issue was not discovered until an operator arrived onsite following morning. CDCR reports that the effluent basin was spilling for 12 consecutive hour. Using historical SCADA data for the time frame of 6 PM to 6 AM from the prior 5 days the CDCR operator estimated 160,830 gallons was released. This is value does not include any discharges of stormwater or comingled stormwater from the stormwater collection system of the Old Prison facility, which are currently being addressed through other enforcement actions. Because the treatment plant was no operating during this time and the volume exceeds that of the chlorine contact channel the discharged water consisted of partially treated wastewater. No samples were collected. The spill overtopped the effluent basin, flowed approximately 120 feet east to a culvert which leads under the road to a surface water drainage course that leads to Mule Creek. This is release of treated and partially treated wastewater is a violation of the WDRs. Relevant WDR Discharge Prohibitions and Discharge Specifications are cited below. On the morning of 23 July when the spill was discovered CDCR staff used a trailer mounted vacuum excavator to recover 8,500 gallons from the drainage. The operator provided a map showing the path and location of the spill as well as pictures prior to and after the cleanup effort in the Spill Notification Report. That map and the pictures are attached. All pictures were taken from the location designated as “End of Spill” on the map. The Discharger states in the Spill Notification Report that CDCR intends to implement training procedures for their Main Control group to ensure the proper staff are notified when wastewater treatment and conveyance related alarms are triggered. Violation B Report
1087760 03/18/2021 LREP Report late, 2019 AMR Violation B Report
1087764 03/18/2021 LREP Report not submitted, 2020 AMR Violation B Report
1087765 03/18/2021 LREP Report not submitted, November 2020 Violation B Report
1087761 03/18/2021 LREP Report not submitted, Q2 2020 Violation B Report
1087758 03/18/2021 LREP Report not submitted, Q3 2019 Violation B Report
1087762 03/18/2021 LREP Report not submitted, Q3 2020 Violation B Report
1087759 03/18/2021 LREP Report not submitted, Q4 2019 Violation B Report
1087763 03/18/2021 LREP Report not submitted, Q4 2020 Violation B Report
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 9 Priority Violations: 0
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.

Violation Types
LREP = Late Report UAUTHDISC = Unauthorized Discharge

Expand/Contract Enforcement Actions
Enforcement Actions
Enf Id Enf Type Enf Order No. Effective Date Status
430153 Notice of Violation null 08/13/2018 Historical
422345 13267 Letter null 06/21/2018 Active
422986 Notice of Violation 05/24/2018 Historical
421221 Notice of Violation 04/04/2018 Historical
420340 13267 Letter null 02/14/2018 Historical
411975 Notice of Violation 02/16/2017 Historical
410840 Notice of Violation 12/05/2016 Historical
321867 Admin Civil Liability R5-2007-0518 08/21/2007 Historical
317741 Cease and Desist Order R5-2006-0130 12/08/2006 Historical
314116 Notice of Violation null 10/23/2006 Historical
311480 Notice of Violation null 09/05/2006 Historical
245601 Notice of Violation 12/03/2002 Historical
247920 Notice of Violation 06/17/2002 Historical
239776 Staff Enforcement Letter 01/17/2002 Historical
238568 Notice of Violation 10/22/2001 Historical
231692 Notice of Violation 11/15/2000 Historical
231525 Notice of Violation 10/17/2000 Historical
Total Enf Actions: 17

Expand/Contract Inspections
Inspections
Inspection ID Inspection Type Lead Inspector Actual End Date Planned Violations Attachment
55901692 B Type compliance inspection Kenny Croyle 09/26/2023 N 0 N/A
48146777 B Type compliance inspection Kenny Croyle 06/07/2022 N 0 N/A
47029517 B Type compliance inspection Kenny Croyle 03/07/2022 N 0 N/A
38769919 B Type compliance inspection Kenny Croyle 12/23/2019 N 0 N/A
37157985 Prerequirement inspection Scott Armstrong 07/25/2019 N 0 [Attachments]
36755625 B Type compliance inspection Kenny Croyle 06/24/2019 N 0 N/A
35712701 B Type compliance inspection Kenny Croyle 01/16/2019 N 0 N/A
34483129 Prerequirement inspection Lixin Fu 11/16/2018 N 0 N/A
34057059 B Type compliance inspection Kenny Croyle 10/05/2018 N 0 N/A
32352150 B Type compliance inspection Kenny Croyle 04/23/2018 N 0 N/A
32176142 B Type compliance inspection Kenny Croyle 03/13/2018 N 0 N/A
32175467 B Type compliance inspection Kenny Croyle 03/12/2018 N 0 N/A
32177271 B Type compliance inspection Kenny Croyle 03/06/2018 N 0 N/A
32175451 B Type compliance inspection Kenny Croyle 02/22/2018 N 0 N/A
31460185 B Type compliance inspection Kenny Croyle 01/04/2018 N 1 N/A
29967216 Prerequirement inspection Scott Armstrong 09/15/2017 N 0 [Attachments]
31460181 B Type compliance inspection Kenny Croyle 09/15/2017 N 0 N/A
26117645 B Type compliance inspection Kenny Croyle 08/23/2016 N 0 N/A
9773572 B Type compliance inspection Mary Boyd 09/21/2012 Y 0 Download
7918953 B Type compliance inspection Mary Boyd 04/12/2012 Y 0 Download
845403 B Type compliance inspection Scott Kranhold (Multiple) 09/29/2006 N 3 Download
721691 B Type compliance inspection Melissa Hall (Multiple) 08/16/2006 N 2 N/A
325845 B Type compliance inspection Alex Baillie 08/29/2002 Y 0 N/A
321394 B Type compliance inspection Alex Baillie 06/13/2002 Y 0 N/A
321396 Follow-up inspection (noncompliance) Alex Baillie 02/02/2001 Y 0 N/A
321398 B Type compliance inspection Alex Baillie 10/25/2000 Y 0 N/A
321397 Miscellaneous inspection Alex Baillie 10/04/2000 Y 0 N/A
321395 B Type compliance inspection David L Melendrez 05/10/2000 Y 0 N/A
321401 B Type compliance inspection David L Melendrez 11/15/1999 Y 0 N/A
321399 B Type compliance inspection Jim Maughan 01/26/1995 Y 0 N/A
321400 B Type compliance inspection Jim Maughan 01/18/1994 Y 0 N/A
321402 B Type compliance inspection Jim Maughan 02/24/1993 Y 0 N/A
Total Inspections: 32 Last Inspection: 09/26/2023
  
The current report was generated with data as of: 05/15/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
Back to Main Page  |  Back to Top of Page