Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1092207 |
06/30/2021 |
OEV |
TPH as Motor Oil Maximum Daily (MDEL) limit is 100 ug/L and reported value was 150 ug/L. |
The discharger states that breakthrough is unlikely as the media had been replaced two weeks before the June 30, 2021, sampling event. Influent TPH concentrations were lower than effluent concentrations on June 30, 2021. The source of the TPH diesel and motor oil in the effluent is unknown. Because presence of TPH diesel and motor oil in the effluent were not confirmed, discharge resumed on July 16, 2021. |
Violation |
B |
Report |
1092206 |
06/30/2021 |
CAT2 |
Diesel Oil Maximum Daily (MDEL) limit is 50 ug/L and reported value was 180 ug/L. |
The discharger states that breakthrough is unlikely as the media had been replaced two weeks before the June 30, 2021, sampling event. Influent TPH concentrations were lower than effluent concentrations on June 30, 2021. The source of the TPH diesel and motor oil in the effluent is unknown. Because presence of TPH diesel and motor oil in the effluent were not confirmed, discharge resumed on July 16, 2021. |
Violation |
B |
Report |
1092190 |
06/30/2021 |
CAT2 |
Nickel, Total Monthly Average limit is 22.0 ug/L and reported value was 28.0 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092194 |
06/08/2021 |
OEV |
TPH as Motor Oil Maximum Daily (MDEL) limit is 100 ug/L and reported value was 160 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092192 |
06/08/2021 |
CAT2 |
Diesel Oil Maximum Daily (MDEL) limit is 50 ug/L and reported value was 160 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092189 |
05/31/2021 |
CAT2 |
Nickel, Total Monthly Average (Mean) limit is 22 ug/L and reported value was 47 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092193 |
05/28/2021 |
OEV |
TPH as Motor Oil Maximum Daily (MDEL) limit is 100 ug/L and reported value was 130 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092191 |
05/28/2021 |
CAT2 |
Diesel Oil Maximum Daily (MDEL) limit is 50 ug/L and reported value was 53 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1092188 |
05/28/2021 |
CAT2 |
Nickel, Total Daily Maximum limit is 44 ug/L and reported value was 47 ug/L. |
As preventive measures, the discharger ceased discharge to surface waters until the treatment system's effluent meets permit limits. The contractor ordered new filtration vessels and installed a new effluent sampling port with added protection to prevent contamination. |
Violation |
B |
Report |
1084154 |
12/04/2020 |
CAT2 |
Nickel, Total Recoverable Maximum Daily (MDEL) limit is 44 ug/L and reported value was 83 ug/L. |
The discharger installed additional filtering units to the treatment system before it resumed discharge. Effluent monitoring for nickel was performed again on December 28, 2020, indicating no presence of nickel. |
Violation |
B |
Report |