Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1119738 |
07/23/2023 |
OEV |
Total Coliform 1-Hour Average (Mean) limit is 240 CFU/100 mL and reported value was 2419.6 CFU/100 mL at EFF-001. |
On July 23, 2023, at 0845, a bact sample was taken at the plant pipeline. At that time the operator noticed the total chlorine residual was below normal for that location. The operator increased the chlorine dose and resampled the pipeline for bact at 1000. The bact results came back the next day with a >2419.6 CFU/mL for the 0845 sample and <1 CFU/mL for the 1000 sample. The LOWRF was below <1 CFU/mL for the rest of the month. |
Violation |
U |
eSMR |
1112771 |
01/26/2023 |
OEV |
Turbidity 1-Hour Average (Mean) limit is 2 NTU and reported value was 02.27 NTU at EFF-001. |
All agricultural users were turned off during this excursion. The plant never exceeded 5 NTU at any time. Oxidation weir was raised and second clarifier was put online to increase detention time at the plant. |
Violation |
U |
eSMR |
1112913 |
12/26/2022 |
OEV |
Turbidity 1-Hour Average (Mean) limit is 2 NTU and reported value was 2.27 NTU at EFF-001. |
All agricultural users were turned off during this excursion. The plant never exceeded 5 NTU at any time. The Oxidation weir was raised and a second clarifier was put online to increase detention time at the plant. |
Violation |
B |
eSMR |
1112914 |
12/26/2022 |
OEV |
Turbidity 1-Hour Average (Mean) limit is 2 NTU and reported value was 2.27 NTU at EFF-001. |
All agricultural users were turned off during this excursion. The plant never exceeded 5 NTU at any time. The Oxidation weir was raised and a second clarifier was put online to increase detention time at the plant. |
Violation |
U |
eSMR |
1112773 |
12/26/2022 |
OEV |
Turbidity 1-Hour Average (Mean) limit is 2 NTU and reported value was 2.3 NTU at EFF-001. |
. All agricultural users were turned off during this excursion. The plant never exceeded 5 NTU at any time. Oxidation weir was raised and second clarifier was put online to increase detention time at the plant. |
Violation |
B |
eSMR |
1112772 |
12/26/2022 |
OEV |
Turbidity 24-hour Average limit is 2 NTU and reported value was 0 NTU at EFF-001. |
Oxidation weir gate to retain more volume and increase detention time. We also have been adding polymer to the MLSS at the Oxidation weir gate into the secondary clarifier to aid in settleability. |
Violation |
B |
eSMR |
1108768 |
09/06/2022 |
Deficient Reporting |
Missed Influent BOD and TSS monitoring in September 2022. |
We will use a monthly checklist to catch missed samples. |
Violation |
B |
eSMR |
1078733 |
07/07/2020 |
DMON |
Deficient Monitoring: Sample was not collected in July for the monthly influent BOD due to an error in our LIMS. Averaged operational TSS data from weekly grabs for the required monthly Influent composite TSS. |
Paperwork changes were made so that sampling errors can be caught in the future. |
Violation |
B |
eSMR |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|