| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1153774 |
03/04/2026 |
DMON |
Due to a communication lapse between the HSC personnel responsible for monitoring the flow meter at M-014 and the designated sampler, the sampler was unaware that flow had occurred via M-014 on 3/4, and 3/25-3/31/26. Therefore, the sampler was unaware that discharge to the CSD pond may have occurred during the month of March, and samples were not collected for laboratory analysis of total chromium and total zinc at monitoring location M-014, or for TSS and O&G at monitoring location M-017. The sampler checked for discharge at location M-017 on 3/27/26, and no flow was observed. It is unknown if the low flow observed at M-014 resulted in a discharge to the CSD pond during the month of March. |
The monitoring requirements of the permit have been clarified with HSC personnel. |
Violation |
U |
eSMR |
| 1153775 |
03/04/2026 |
DMON |
Due to a communication lapse between the HSC personnel responsible for monitoring the flow meter at M-014 and the designated sampler, the sampler was unaware that flow had occurred via M-014 on 3/4, and 3/25-3/31/26. Therefore, the sampler was unaware that discharge to the CSD pond may have occurred during the month of March, and samples were not collected for laboratory analysis of total chromium and total zinc at monitoring location M-014, or for TSS and O&G at monitoring location M-017. The sampler checked for discharge at location M-017 on 3/27/26, and no flow was observed. It is unknown if the low flow observed at M-014 resulted in a discharge to the CSD pond during the month of March. |
The monitoring requirements of the permit have been clarified with HSC personnel. |
Violation |
U |
eSMR |
| 1152779 |
03/02/2026 |
LREP |
Annual SMR ( MONNPDES ) report for 2025 (2935938) was due on 02-MARCH-26 |
|
Violation |
B |
Report |
| 1153002 |
03/02/2026 |
LREP |
Monthly SMR ( MONNPDES ) report for January 2026 (3063240) was due on 01-MAR-26 |
|
Violation |
B |
Report |
| 1153160 |
02/26/2026 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average (Mean) limit is 30 mg/L and reported value was 47 mg/L at M-017. |
Source unknown for high TSS level, filter media was replaced and visual inspections to continue. |
Violation |
U |
eSMR |
| 1153000 |
02/02/2026 |
LREP |
Monthly SMR (MONNPDES ) report for December 2025 (3032348) was due on 01-FEB-26 |
|
Violation |
B |
Report |
| 1151808 |
01/01/2026 |
LREP |
Monthly SMR ( MONNPDES ) report for November 2025 (3025754) was due on 01-JAN-26. |
|
Violation |
B |
Report |
| 1151807 |
12/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for October 2025 (3018603) was due on 01-DEC-25. |
|
Violation |
B |
Report |
| 1151806 |
11/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for September 2025 (3002973) was due on 01-NOV-25. |
|
Violation |
B |
Report |
| 1153532 |
10/01/2025 |
Deficient Reporting |
Monthly discharge samples were collected on 8/11/2025 and submitted to Microbac Analytical Laboratory of Arcata, California. However, the Microbac misplaced the samples. Therefore, no analytical results for total chromium, total zinc, TSS, or O&G are available for the month of August 2025. Submittal of this report was delayed during the search for the August 2025 analytical results. HSC was unaware of the option to use NODI code "P" to report a laboratory error until recently. The report has now been submitted using NODI code "P." |
HSC has requested sample receipt confirmation notifications from the analytical laboratory to improve sample tracking. |
Violation |
U |
eSMR |
| 1153533 |
10/01/2025 |
Deficient Reporting |
Monthly discharge samples were collected on 8/11/2025 and submitted to Microbac Analytical Laboratory of Arcata, California. However, the Microbac misplaced the samples. Therefore, no analytical results for total chromium, total zinc, TSS, or O&G are available for the month of August 2025. Submittal of this report was delayed during the search for the August 2025 analytical results. HSC was unaware of the option to use NODI code "P" to report a laboratory error until recently. The report has now been submitted using NODI code "P." |
HSC has requested sample receipt confirmation notifications from the analytical laboratory to improve sample tracking. |
Violation |
U |
eSMR |
| 1153534 |
10/01/2025 |
Deficient Reporting |
Monthly discharge samples were collected on 8/11/2025 and submitted to Microbac Analytical Laboratory of Arcata, California. However, the Microbac misplaced the samples. Therefore, no analytical results for total chromium, total zinc, TSS, or O&G are available for the month of August 2025. Submittal of this report was delayed during the search for the August 2025 analytical results. HSC was unaware of the option to use NODI code "P" to report a laboratory error until recently. The report has now been submitted using NODI code "P." |
HSC has requested sample receipt confirmation notifications from the analytical laboratory to improve sample tracking. |
Violation |
U |
eSMR |
| 1151805 |
10/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for August 2025 (2995458) was due on 01-OCT-25. |
|
Violation |
B |
Report |
| 1151804 |
09/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for July 2025 (2987546) was due on 01-SEP-25. |
|
Violation |
B |
Report |
| 1151803 |
08/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for June 2025 (2975679) was due on 01-AUG-25. |
|
Violation |
B |
Report |
| 1149287 |
07/30/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 70 mg/L at M-015A. |
We continue to monitor as this is an unusual spike for this internal monitoring point. |
Violation |
B |
eSMR |
| 1151802 |
07/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for May 2025 (2964524) was due on 01-JUL-25. |
|
Violation |
B |
Report |
| 1151801 |
06/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for April 2025 (2953287) was due on 01-JUN-25. |
|
Violation |
B |
Report |
| 1151800 |
05/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for March 2025 (2935937) was due on 01-MAY-25. |
|
Violation |
B |
Report |
| 1151799 |
04/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for February 2025 (2935936) was due on 01-APR-25. |
|
Violation |
B |
Report |
| 1152782 |
03/03/2025 |
LREP |
Annual SMR ( MONNPDES ) report for 2025 (2787852) was due on 03-MARCH-26. |
|
Violation |
B |
Report |
| 1151798 |
03/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for January 2025 (2935935) was due on 01-MAR-25. |
|
Violation |
B |
Report |
| 1149286 |
02/25/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 42 mg/L at M-017. |
We continue to monitor and are working through implementing a new filter system. |
Violation |
B |
eSMR |
| 1151797 |
02/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for December 2024 (2903754) was due on 01-FEB-25. |
|
Violation |
B |
Report |
| 1149285 |
01/28/2025 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 59 mg/L at M-017. |
Source unknown for high TSS level, filter media was replaced and visual inspections to continue. |
Violation |
B |
eSMR |
| 1151796 |
01/01/2025 |
LREP |
Monthly SMR ( MONNPDES ) report for November 2024 (2896065) was due on 01-JAN-25. |
|
Violation |
B |
Report |
| 1151795 |
12/01/2024 |
LREP |
Monthly SMR ( MONNPDES ) report for October 2024 (2869080) was due on 01-DEC-24. |
|
Violation |
B |
Report |
| 1143766 |
11/29/2024 |
DMON |
Unable to pull a sample for the monthly monitoring report |
Plant was black last week of November, with no sample being pulled. Once operational in December, operations went back to normal. |
Violation |
B |
eSMR |
| 1151794 |
11/01/2024 |
LREP |
Monthly SMR ( MONNPDES ) report for September 2024 (2858470) was due on 01-NOV-24. |
|
Violation |
B |
Report |
| 1151793 |
10/01/2024 |
LREP |
Monthly SMR ( MONNPDES ) report for August 2024 (2850276) was due on 01-OCT-24. |
|
Violation |
B |
Report |
| 1143752 |
08/21/2024 |
CAT1 |
Total Suspended Solids (TSS) Daily Maximum limit is 100 mg/L and reported value was 2200 mg/L at M-015A. |
HSC will continue to monitor TSS; Visual observations from sampling point showed higher turbidity during the time of sample. Upon returning throughout the month, the visual observations returned to a normal status. |
Violation |
B |
eSMR |
| 1129055 |
05/31/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.0 mg/L and reported value was 41.0 mg/L at M-017. |
HSC will continue to monitor TSS; during the month of May, we noticed an increase in TSS due to an unknown issue which prompted HSC to purchase a new type of filter which will be installed. |
Violation |
B |
eSMR |
| 1128216 |
04/29/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 38 mg/L at M-017. |
HSC will continue to monitor TSS; during the month of March, we noticed an increase in TSS due to an unknown issue which prompted HSC to purchase a new type of filter which will be installed. |
Violation |
B |
eSMR |
| 1126789 |
03/20/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.0 mg/L and reported value was 34.0 mg/L at M-015A. |
HSC will continue to monitor TSS; during the month of March, we noticed an increase in TSS due to an unknown issue which prompted HSC to purchase a new type of filter which will be installed. |
Violation |
B |
eSMR |
| 1125391 |
02/09/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.0 mg/L and reported value was 40.0 mg/L at M-017. |
HSC will continue to monitor TSS; during the month of February, we noticed an increase in TSS due to an unknown issue which prompted HSC looking into different filter options as a possible resolution. |
Violation |
B |
eSMR |
| 1124740 |
01/30/2024 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30.0 mg/L and reported value was 33.4 mg/L at M-017. |
HSC will continue to monitor TSS; during the month of January, we noticed an increase in TSS due to an unknown issue. If the issue persists, we will look at additional corrective actions. |
Violation |
B |
eSMR |
| 1116964 |
04/19/2023 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 30 mg/L and reported value was 32 mg/L at M-017. |
Persistent elevated TSS over the last roughly half year is thought to be a result of higher TSS in raw water used for the cooling towers. A bag filter was installed into the discharge line prior to the mixing tank in May 2023. |
Violation |
B |
eSMR |
| 1113924 |
01/03/2023 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average (Mean) limit is 30 mg/L and reported value was 49.3 mg/L at M-017. |
HSC will continue to monitor TSS; it is speculated that following high volume rainfall in January 2023, a higher than normal sediment load may have existed in the Eel River, which supplies the raw water used in our cooling towers. If the issue persists we will look at additional corrective action. |
Violation |
B |
eSMR |
| 1093887 |
08/22/2021 |
PRE |
Following plant re-start, daily discharge rate on 8/22/21 at boiler blowdown (M015A) prior to mixing tank was 0.014 MGD, which exceeded the permit daily discharge maximum at that location of 0.011 MGD. However, total discharge to effluent discharge point (M017) was well below allowable limit. |
Startup often has higher than usual discharges; the boiler blowdown (M015A) exceeded the daily discharge limit of 0.011 MGD following restart on 8/22/21. However, it is a pretreatment location and the combined discharge at M017 (pond) on was 0.014 MGD (permit allows 0.048 MGD at M017) because there was no discharge from the cooling towers (M014). |
Violation |
B |
eSMR |
|