Violations
|
Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1134737 |
08/24/2024 |
SSOS |
Type: Category 1 Spill; Debris-Rags caused 500 gallons of sewage to spill from Inside Building or Structure,Manhole at 1529-0393 (8814 Betty Way, West Hollywood) to Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3),Building or Structure |
Added Sewer to Preventive Maintenance Program,Inspected Sewer Using CCTV to Determine Cause. Mainline placed on a 90-day Hydro Rootsaw periodic. |
Violation |
A |
SSO |
1133427 |
05/08/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 31763 gallons of sewage to spill from Manhole at 1529-0003 (9255 Doheny Road, West Hollywood) to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Added Sewer to Preventive Maintenance Program, Inspected Sewer Using CCTV to Determine Cause. Inspected sewer using CCTV and added sewer to preventive maintenance program. |
Violation |
A |
SSO |
1133426 |
03/11/2024 |
SSOS |
Type: Category 1 Spill; Debris-Rags, Root Intrusion caused 1520 gallons of sewage to spill from Gravity Mainline, Lateral Clean Out (Private), Manhole at 1583-0182 (1016 North Stanley Avenue, West Hollywood) to Building or Structure, Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Adjusted Schedule/Method of Preventive Maintenance. It is recommended that Stanley Avenue from Manhole 183 to 181 be placed on a 90-day hydro PM schedule. |
Violation |
A |
SSO |
1133425 |
02/21/2024 |
SSOS |
Type: Category 1 Spill; Debris-Rags caused 4125 gallons of sewage to spill from Gravity Mainline, Manhole at 1529-0218 (8455 West Fountain Avenue, West Hollywood) to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Adjusted Schedule/Method of Preventive Maintenance, Other (specify below). Recommended to place sewer on a 120-day Hydro preventive maintenance program (S09SS761). Also, to inspect and monitor the condition. |
Violation |
A |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|
|
Total Violations: 4
|
Priority Violations: 0
|
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.
|
Violation Types |
SSOS = Sanitary Sewer Overflow/Spill/
|
|
|