Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1139876 |
01/23/2025 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance,Fats, Oil and Grease (FOG) caused 10 gallons of sewage to spill from Manhole at 2305-0656 (1100 Coiner Court, Industry, CA) to Drainage Conveyance System,Street/Curb and Gutter (2 3) |
Other (specify below). There is an ongoing issue with Santa Fe Railroad and the Division is aware of breached mainline. Mainline will be repaired by San Gabriel Valley Counsil of Governments at 1333 Mayflower Ave #360, Monrovia, CA 91016. |
Violation |
A |
SSO |
1139218 |
01/14/2025 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls,Damage by Others Not Related to Collection System Construction/Maintenance,Fats, Oil and Grease (FOG) caused 700 gallons of sewage to spill from Manhole at 2305-0656 (1100 Coiner Court, Industry, CA) to Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3) |
Other (specify below). N/A |
Violation |
A |
SSO |
1114987 |
03/27/2023 |
SSOS |
Type: Category 1. Grease Deposition (FOG) caused 100.0 gallons of sewage to spill from Manhole;Manhole No. 383 at 2124-0383 (13007 Crossroads Parkway, Industry) to Other (specify below);Separate Storm Drain;Street/Curb and Gutter;Sewage spill discharged from Manhole No. 383 into storm drain, which leads to natural streams and minor channels that eventually reaches to San Gabriel River.. Surface water body affected (Natural streams and minor channels that eventually reaches to San Gabriel River). |
Cleaned-Up;Contained all or portion of spill;Other (specify below);Restored flow;Other Enforcement Agency Notified. ;Upon arrival, Manhole No. 383 was overflowing, used absorbent socks to contain gray water from entering storm drain in front of 13007 Crossroads Parkway. Hydro jet equipment was used to break down the mainline grease blockage, contained portion of spill and cleaned up spill area. Notified all required agencies. |
Violation |
B |
SSO |
1103799 |
04/27/2022 |
SSOS |
Type: Category 1. Other (specify below);Possible plaster and concrete caused 1100.0 gallons of sewage to spill from Manhole at 2262-0513 (Gale Avenue/Stone Creek Road, Industry) to Other (specify below);Street/Curb and Gutter;Sewage discharged from Manhole No. 513 into Caltrans Wash Way.. Surface water body affected (Caltrans wash way). |
Other (specify below);Restored flow;Other Enforcement Agency Notified. ;Hydro jet equipment was used to break down the mainline blockage. Notified agencies. |
Violation |
B |
SSO |
1097994 |
12/12/2021 |
SSOS |
Type: Category 1. Grease Deposition (FOG) caused 500.0 gallons of sewage to spill from Manhole;Manhole No. 383 at 2124-0383 (13027 Crossroads Parkway South, Industry) to Drainage Channel;Other (specify below);Separate Storm Drain;Street/Curb and Gutter;Sewage discharged from Manhole No. 383 into storm drain, which leads to San Gabriel River.. Surface water body affected (Sewage discharged from Manhole No. 383 into storm drain, which leads to San Gabriel River.). |
Cleaned-Up;Contained all or portion of spill;Restored flow;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;Rodder and Hydro equipment's were used to break down a grease blockage in the mainline. Contained portion of sewage discharge with vactor truck and returned to the sewer system. Cleaned-up spill area. Notified all required agencies. |
Violation |
B |
SSO |
1092803 |
07/27/2021 |
SSOS |
Type: Category 1. Other (specify below);Bricks caused 600.0 gallons of sewage to spill from Manhole at 2262-0559 (18219 Gale Avenue, Industry) to Drainage Channel;Other (specify below);Separate Storm Drain;Street/Curb and Gutter;Sewage discharged from Manhole No. 559 into storm drain behind Home Depot at 18219 Gale Avenue, which leads to San Jose Creek - Thompson Creek to U/S San Gabriel River.. Surface water body affected (San Jose Creek - Thompson Creek to U/S San Gabriel River). |
Cleaned-Up;Contained all or portion of spill;Other (specify below);Restored flow;Other Enforcement Agency Notified. ;Rodder and hydro jet equipment's were used to break down the mainline blockage. Contained portion of gray water with absorbent socks and cleaned up spill area. Notified all required agencies. |
Violation |
B |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|