Place ID 631996
  
  
  
  
Hide All Show All
General Information
Region Place ID Place Name Place Type Place Address Place County
4 631996 Glendale City CS Collection_System 613 East Broadway Glendale, CA, 91206 Los Angeles

Expand/Contract Related Parties
Related Parties
Party Party Type Party Name Role Classification Relationship Start Date Relationship End Date
549951 Person Gary Harris Is Onsite Manager For 04/04/2024
633465 Person Vardan Tagesyan Is A Data Submitter For 06/07/2022
632866 Person Nery Villagran Is A Data Submitter For 05/03/2022
610903 Person Alfonso Herrera Is A Data Submitter For 07/13/2020
549285 Person Roubik Golanian Is Onsite Manager For 12/10/2014 06/13/2019
542852 Person David Martinez Is A Data Submitter For 09/04/2013 05/31/2019
537089 Person Rod Torres Is A Data Submitter For 10/02/2012
528022 Person Daniel Hardgrove Is Onsite Manager For 07/21/2011
354023 Person John Neal Hicks Is Onsite Manager For 12/06/2006 01/25/2024
354020 Person Bryan Ortega Is A Data Submitter For 12/06/2006 07/13/2020
354014 Person Robert Amar Is Onsite Manager For 12/06/2006 05/29/2012
354005 Person Maurice Oillataguerre Is Onsite Manager For 12/06/2006 07/01/2014
354035 Person Roy Rodriguez Is A Data Submitter For 12/06/2006
19188 Organization Glendale City Owner City Agency 04/07/2006
Total Related Parties: 14

Expand/Contract Regulatory Measures
Regulatory Measures
Reg Measure ID Reg Measure Type Region Program Order No. WDID Effective Date Expiration Date Status Amended?
301170 Enrollee 4 SSOMUNILRG 2022-0103-DWQ 4SSO10388 08/03/2006 12/31/2009 Active N
Total Reg Measures: 1

Expand/Contract Violations
Violations
Violation ID Occurred Date Violation Type (-) Violation Description Corrective Action Status Classification Source
1136554 11/12/2024 SSOS Type: Category 1 Spill; Root Intrusion caused 2340 gallons of sewage to spill from Inside Building or Structure,Lateral Clean Out (Private) at 1244 & 1246 Linden Ave. to Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3),Paved Surface,Building or Structure,Drainage Conveyance System,Unpaved Surface Adjusted Schedule/Method of Preventive Maintenance,Post Spill CCTV,Other (specify below). Will adjust scheduled frequency of cleaning from 18 months to (TBD) and will treat with Chemical Root Control (CRC). Violation A SSO
1136527 11/09/2024 SSOS Type: Category 1 Spill; Other (specify below) caused 2525 gallons of sewage to spill from Manhole at 1618 Ridgeway Drive to Street/Curb and Gutter (2 3),Drainage Conveyance System Inspected Sewer Using CCTV to Determine Cause. Spill may have been caused by upstream cleaning activities earlier in the week. These roots appear to have hung up on a protruding lateral but uncertain. Entering a work request to have the protruding lateral removed Violation A SSO
1133411 07/20/2024 SSOS Type: Category 1 Spill; Debris-wipes/Non-disposables, Pipe Structural Problem/Failure - Controls, Root Intrusion caused 3920 gallons of sewage to spill from Manhole at 1600 Ridgeview Dr. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3) Adjusted Schedule/Method of Preventive Maintenance, Inspected Sewer Using CCTV to Determine Cause, Plan Rehabilitation or Replacement of Sewer. Segment of sewer mainline cleaning frequency will be adjusted from every six (6) months to every four (4) months. CCTV post spill inspection found defects (cracks) with root intrusion, this has been communicated to City's Engineering Section for evaluation for repair. Violation A SSO
1133410 05/16/2024 SSOS Type: Category 1 Spill; Root Intrusion caused 1024 gallons of sewage to spill from Manhole at 1514 E. Garfield Ave. Glendale CA, 91205 to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3), Surface Water Added Sewer to Preventive Maintenance Program, Adjusted Schedule/Method of Preventive Maintenance, Inspected Sewer Using CCTV to Determine Cause, Other (specify below), Plan Rehabilitation or Replacement of Sewer. Adjust frequency of cleaning, apply CRC (Chemical Root Control) to mitigate root growth, CCTV report to Engineering for evaluation. Violation A SSO
1133409 02/13/2024 SSOS Type: Category 1 Spill; Collection System Maintenance Failure (specify below), Debris-Rags, Fats, Oil and Grease (FOG), Root Intrusion caused 1544 gallons of sewage to spill from Inside Building or Structure at 315 N. Louise St. Glendale, CA. 91206 to Building or Structure, Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) Inspected Sewer Using CCTV to Determine Cause, Other (specify below). See item 10 a. above. Violation A SSO
1133407 01/07/2024 SSOS Type: Category 1 Spill; Root Intrusion caused 382 gallons of sewage to spill from Manhole, Other (specify below) at 1600 Block of Thurber Pl. to Drainage Conveyance System, Street/Curb and Gutter (2 3), Surface Water Inspected Sewer Using CCTV to Determine Cause, Other (specify below). See item 10 a. above. Violation A SSO
1133406 12/17/2023 SSOS Type: Category 1 Spill; Debris-wipes/Non-disposables, Fats, Oil and Grease (FOG), Root Intrusion caused 3640 gallons of sewage to spill from Manhole at 300 N. Kenwood Street to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3), Surface Water Inspected Sewer Using CCTV to Determine Cause, Other (specify below). Possible increased frequency of preventive maintenance based on circumstances-pending review. Possible relocation of an existing SMART Cover based on fact that this is a repeat of the events of 9/22/22. CIWQS Event No. 883424 Violation A SSO
1133404 11/29/2023 SSOS Type: Category 1 Spill; Fats, Oil and Grease (FOG), Root Intrusion caused 2065 gallons of sewage to spill from Inside Building or Structure, Lateral Clean Out (Private) at 440 W. Myrtle St. to Building or Structure, Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3), Surface Water Inspected Sewer Using CCTV to Determine Cause. Possible increased frequency of preventive maintenance based on circumstances-pending review. Violation A SSO
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 8 Priority Violations: 0
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.

Violation Types
SSOS = Sanitary Sewer Overflow/Spill/

Expand/Contract Enforcement Actions
Enforcement Actions
Enf Id Enf Type Enf Order No. Effective Date Status
389510 Notice of Violation 01/25/2013 Historical
Total Enf Actions: 1

Expand/Contract Inspections
Inspections
Inspection ID Inspection Type Lead Inspector Actual End Date Planned Violations Attachment
11686186 B Type compliance inspection Craig Blett (Multiple) 04/30/2012 N 8 Download
Total Inspections: 1 Last Inspection: 04/30/2012
  
The current report was generated with data as of: 11/29/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.