Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1131556 |
08/29/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 6428 gallons of sewage to spill from Manhole at 300 North Paseo Miramar to Other (specify below) |
Adjusted Schedule/Method of Preventive Maintenance. In an effort to prevent future incidents at this location the sewer will be placed in the Chemical Root Control Program and a quarterly cleaning schedule. |
Violation |
U |
SSO |
1133977 |
07/20/2024 |
SSOS |
Type: Category 1 Spill; Debris-General caused 15967 gallons of sewage to spill from Gravity Mainline at 2700 South Cresta Place to Other (specify below) |
Plan Rehabilitation or Replacement of Sewer. As part of our quality assurance program, this sewer was inspected by Closed Circuit Television (CCTV) to determine the exact cause of this event and the proper corrective actions to be taken. The CCTV inspection revealed some damage to the pipeline that caused by the Department of Water and Power water main failure. An Emergency On-Call Contractor was mobilized to make the necessary repairs. In addition, this sewer system will be placed on a semi-annual cleaning frequency. |
Violation |
A |
SSO |
1133971 |
05/19/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 259 gallons of sewage to spill from Manhole at 16421 West Pacific Coast Highway to Other (specify below), Paved Surface |
Adjusted Schedule/Method of Preventive Maintenance. The post-overflow Closed Circuit Television (CCTV) inspection revealed no defects. In an effort to prevent future incidents at this location the sewer will be placed on a quarterly cleaning schedule. |
Violation |
A |
SSO |
1133966 |
04/04/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 448 gallons of sewage to spill from Manhole at 1986 North Coldwater Canyon Road to Other (specify below) |
Adjusted Schedule/Method of Preventive Maintenance. As part of our quality assurance program, the sewer line servicing the incident location was inspected using Closed Circuit Television (CCTV). The post- overflow CCTV inspection revealed no defects. In an effort to prevent future incidents at this location the sewer will be placed on a quarterly cleaning schedule. |
Violation |
A |
SSO |
1133930 |
09/01/2023 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 656 gallons of sewage to spill from Manhole at 1484 North Doheny Drive to Drainage Conveyance System, Street/Curb and Gutter (2 3) |
Inspected Sewer Using CCTV to Determine Cause, Plan Rehabilitation or Replacement of Sewer, Repaired Facilities or Replaced Defect. Pipeline Repairs Were Completed On October 5, 2023. |
Violation |
A |
SSO |
1133920 |
07/05/2023 |
SSOS |
Type: Category 1 Spill; Debris-General caused 576 gallons of sewage to spill from Manhole at 2025 South Shenandoah Street to Other (specify below) |
Adjusted Schedule/Method of Preventive Maintenance. Adjusted Maintenance/Cleaning Schedule. |
Violation |
A |
SSO |
1108865 |
08/24/2021 |
Order Conditions |
The Enrollee is not properly maintaining all parts of the Collection System in violation of Provision D.8 of SSS WDRs. Corroded equipment and sewage debris above the walking grates over the wet well were visible at the Venice Pumping Station. Grease mat/foaming was visible in the wet well at Pumping Plant #610. Debris accumulation in the Coastal Interceptor upstream of the Hyperion wastewater treatment plant were apparent in CCTV footage provided by the Enrollee. Obstruction in the Coastal Outfall Sewer between Manholes 56313048 and 56314046 was visible in CCTV footage provided by the Enrollee. |
|
Violation |
B |
Inspection |
1108864 |
08/24/2021 |
Order Conditions |
The Enrollee lacks a substantive communication plan with tributary and/or satellite sewer systems in violation of Provision D.13(xi) of SSS WDRs. |
|
Violation |
B |
Inspection |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|