| 1147677 |
09/20/2025 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 545 gallons of sewage to spill from Manhole at Spring Meadow Park/Olsen Road to Drainage Conveyance System that discharges to surface water,Paved Surface,Street/Curb and Gutter (2 3) |
Repaired Facilities or Replaced Defect,Plan Rehabilitation or Replacement of Sewer,Post Spill CCTV. - Location has been added to the 6-month hot spot hydro cleaning list.
- Added to annual root in manhole inspection list until lining rehab completed. |
Violation |
A |
SSO |
| 1141583 |
03/15/2025 |
SSOS |
Type: Category 1 Spill; Debris from Construction,Debris-General,Inappropriate Discharge to Collection System caused 250000 gallons of sewage to spill from Manhole,Other (specify below) at 726 Flaming Star Avenue-Hiking Trail Easement Behind Property to Surface Water |
Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause,Repaired Facilities or Replaced Defect,Post Spill CCTV. - Increased visual inspections of manhole A27 where 18" pipe reduces to 12". Schedule for monthly inspection.
- Manhole A27 was replaced with a locking manhole cover to prevent access.
- Visual manhole inspections conducted throughout Unit A and Y interceptor. Long term goal of replacing all manholes through easement with locking lids.
- Planned CCTV inspections of the 2012/2013 CIPP CIP project in Unit A and Y to check on lining condition and to look for any debris. |
Violation |
A |
SSO |
| 1135964 |
11/08/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 590 gallons of sewage to spill from Lateral Clean Out (Private) at 3303 Kimber Drive, Newbury Park Ca 91320 to Drainage Conveyance System,Other (specify below),Drainage Conveyance System that discharges to surface water |
Post Spill CCTV,Enforcement action against Fats, Oil, and Grease (FOG) source,Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause. We are moving the cleaning maintenance schedule from 2-years to a 3-month schedule.
Water Quality Department monitoring restaurant grease interceptors. |
Violation |
A |
SSO |
| 1133366 |
04/13/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG), Siphon Failure caused 5200 gallons of sewage to spill from Manhole at Combes Avenue/Paige Ln. Siphon to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3) |
Adjusted Schedule/Method of Preventive Maintenance. Cleaned siphon's thoroughly. Could not inspect siphon's with CCTV equipment. Moving cleaning to a 1-month schedule to clear FOG more regularly. |
Violation |
A |
SSO |
| 1133365 |
10/24/2023 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance, Debris from Construction caused 832 gallons of sewage to spill from Manhole at Janss Road and Lynn Road to Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3) |
Inspected Sewer Using CCTV to Determine Cause, Plan Rehabilitation or Replacement of Sewer, Repaired Facilities or Replaced Defect. Removed asphalt lodged in the gravity main and manhole. Scheduled crew to remove remaining asphalt on side walls of pipe and manhole on 10/30/2023. Scheduled traffic control for high traffic areas to do confined space entry to rehab back to normal with the removal of remaining asphalt. |
Violation |