1143807 |
03/06/2025 |
SSOS |
Type: Category 1 Spill; Other (specify below) caused 670 gallons of sewage to spill from Lateral Clean Out (Private) at 16244 Kennedy Rd. Los Gatos, CA 95032 to Surface Water,Unpaved Surface |
Inspected Sewer Using CCTV to Determine Cause. Spill was caused by foreign object entering system from upstream and becoming lodged in pipe segment. Maintenance history report shows no previous issues and that current maintenance schedule is effective. |
Violation |
A |
SSO |
1141545 |
03/06/2025 |
SSOS |
Type: Category 1 Spill; Other (specify below) caused 675 gallons of sewage to spill from Lateral Clean Out (Private) at 16244 Kennedy Rd. Los Gatos, CA 95032 to Unpaved Surface,Surface Water |
Inspected Sewer Using CCTV to Determine Cause. Spill was caused by foreign object entering system from upstream and becoming lodged in pipe segment. Maintenance history report shows no previous issues and that current maintenance schedule is effective. |
Violation |
A |
SSO |
1138665 |
12/17/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG),Root Intrusion caused 5812 gallons of sewage to spill from Manhole at Happy Acres/Shannon Rd MH# 9-024-82 to Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3),Surface Water,Unpaved Surface |
Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause. Frequency Changed from 24 month to 12 month 12/20/2024
Upstream mainlines CCTV to inspect for fog 12/23/2024
CCTV in 6 month to see grease accumulation 6/25/2025 |
Violation |
A |
SSO |
1138591 |
12/17/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG),Root Intrusion caused 7454 gallons of sewage to spill from Manhole at Happy Acres/Shannon Rd MH# 9-024-82 to Unpaved Surface,Street/Curb and Gutter (2 3),Drainage Conveyance System that discharges to surface water,Surface Water |
Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause. Frequency Changed from 24 month to 12 month 12/20/2024
Upstream mainlines CCTV to inspect for fog 12/23/2024
CCTV in 6 month to see grease accumulation 6/25/2025 |
Violation |
A |
SSO |
1138263 |
12/11/2024 |
SSOS |
Type: Category 1 Spill; Other (specify below),Fats, Oil and Grease (FOG),Debris-Rags,Root Intrusion caused 16068 gallons of sewage to spill from Manhole at Vineland/ Smith Creek to Unpaved Surface,Surface Water,Drainage Conveyance System that discharges to surface water |
Inspected Sewer Using CCTV to Determine Cause,Adjusted Schedule/Method of Preventive Maintenance,Repaired Facilities or Replaced Defect. Repair of mainline was done on 12/13/2024. Reduction of cleaning frequency. CCTV of upstream and downstream pipes. All steps completed by 12/23/2024. |
Violation |