1142245 |
04/11/2025 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 160 gallons of sewage to spill from Force Main at 23016 Pheasant Dr to Drainage Conveyance System |
Repaired Facilities or Replaced Defect. When arrived on-site Berm and GapVax was set up to capture sewage that was seeping out, called in emergency USA, began to break asphalt, exposed force main, identified leak at the bell and spigot. removed bell and spliced in a new piece of pipe. |
Violation |
A |
SSO |
1141248 |
03/05/2025 |
SSOS |
Type: Category 1 Spill; Debris-General,Other (specify below),Debris from Lateral,Root Intrusion caused 425 gallons of sewage to spill from Manhole at 22216 San Joaquin Dr W Canyon lake to Surface Water |
Inspected Sewer Using CCTV to Determine Cause,Post Spill CCTV. Restored flow by removing debris, cleaning for the area may need more frequency due to blue stone coming from homes |
Violation |
A |
SSO |
1134752 |
10/16/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 360 gallons of sewage to spill from Gravity Mainline at Village Pkwy to Drainage Conveyance System,Street/Curb and Gutter (2 3) |
Adjusted Schedule/Method of Preventive Maintenance,Post Spill CCTV. Recleaned gravity main and adjusted schedule of maintenance. |
Violation |
A |
SSO |
1133493 |
03/20/2024 |
SSOS |
Type: Category 1 Spill; Debris from Construction, Debris-General caused 750 gallons of sewage to spill from Lateral Clean Out (Private), Manhole at Winward Dr. to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Adjusted Schedule/Method of Preventive Maintenance. Recleaned gravity main and need to investigate
|
Violation |
A |
SSO |
1133492 |
12/18/2023 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation, Pump Station Failure - Mechanical caused 9762 gallons of sewage to spill from Force Main, Pump Station at Village Way Lift Station to Surface Water |
Repaired Facilities or Replaced Defect. Construction crews got to Lift station to locate and dig up the broken force main at 11:30 pm. Construction Crew and Wastewater Collection Crew worked through the night to uncover the broken section of force main. Repairs were done and a new piece of 10” PVC pipe was installed. On 12/19/23 at 8:57am the force main was tested and put back into service. After that construction crew and Collection crew began the process of back filling the excavated areas. |
Violation |
A |
SSO |
1133490 |
06/11/2023 |
SSOS |
Type: Category 1 Spill; Other (specify below) caused 100 gallons of sewage to spill from Force Main at Gray Fox dr to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3) |
Repaired Facilities or Replaced Defect. Repaired force main |
Violation |
A |
SSO |