Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1140016 |
01/27/2025 |
SSOS |
Type: Category 1 Spill; Debris-General caused 1350 gallons of sewage to spill from Manhole at NOT# 40201202560 10373 ROSELLE ST. to Surface Water,Drainage Conveyance System,Paved Surface,Street/Curb and Gutter (2 3),Unpaved Surface,Drainage Conveyance System that discharges to surface water |
Post Spill CCTV,Inspected Sewer Using CCTV to Determine Cause. THE CORRECTIVE ACTIONS OF THE SPILL WERE TO RELIEVE THE STOPPAGE USING A COMBINATION TRUCK (JETTER) AND TRAP THE DEBRIS. PLANS TO RECONSTUCT DUMP STATION ARE READY AND HAVE BEEN APPROVED. CHANGE FREQ TO 3 MONTHS. |
Violation |
A |
SSO |
1133857 |
06/25/2024 |
SSOS |
Type: Category 1 Spill; Fats, Oil and Grease (FOG) caused 850 gallons of sewage to spill from Manhole at NOT# 20200712809 500 HOTEL CIRCLE N. to Paved Surface, Street/Curb and Gutter (2 3), Surface Water |
Inspected Sewer Using CCTV to Determine Cause. THE SPILL CORRECTIVE ACTION- CREWS RELIEVED A GREASE BLOCKAGE 167' UPSTREAM OF EQ# 10869722. |
Violation |
B |
SSO |
1133849 |
03/27/2024 |
SSOS |
Type: Category 1 Spill; Debris-General caused 3240 gallons of sewage to spill from Manhole at NOT# 40201076335 312 EUCLID AVE. to Drainage Conveyance System that discharges to surface water |
Inspected Sewer Using CCTV to Determine Cause. CREWS RELIEVED SPILL, TRACKED FINAL DESTINATION, PERFORMED CONFINED SPACE ENTRY TO REMOVE DEBRIS DUMPED IN MANHOLE ILLEGALLY, RESECURED VANDALIZED MANHOLE CCTV SEWER MAINS. |
Violation |
B |
SSO |
1133846 |
03/06/2024 |
SSOS |
Type: Category 1 Spill; Vandalism (specify below) caused 21287 gallons of sewage to spill from Other (specify below), Other Sewer System Structure at NOT# 40201071073 AT 600 MISSOURI ST. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Unpaved Surface |
Inspected Sewer Using CCTV to Determine Cause. THE CREW RELIEVED A BLOCKAGE CAUSED BY VANDALISM IN THE SEWER MAIN. |
Violation |
A |
SSO |
1133843 |
03/01/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 1725 gallons of sewage to spill from Manhole at NOT-40201067909 - 5692 EASTGATE DR to Drainage Conveyance System, Unpaved Surface |
Adjusted Schedule/Method of Preventive Maintenance, Inspected Sewer Using CCTV to Determine Cause. REVIEW CURRENT MAINTENANCE SCHEDULE AND ADJUST ACCORDINGLY |
Violation |
B |
SSO |
1133842 |
02/10/2024 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance, Debris from Construction, Debris-General caused 420 gallons of sewage to spill from Gravity Mainline, Manhole at NOT-40201063414-711 51ST. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface |
Other (specify below), Repaired Facilities or Replaced Defect. LOWER MANHOLE TO BELOW STORM WATER DRAINAGE CHANNEL GRADE. |
Violation |
B |
SSO |
1133841 |
02/06/2024 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only), Natural Disaster (specify below), Rainfall Exceeded Design, I and I (Separate Collection System Only) caused 77050 gallons of sewage to spill from Inside Building or Structure, Manhole at NOT# 40201062246 AT 825 N. HARBOR DR. to Building or Structure, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3), Surface Water, Unpaved Surface |
Other (specify below). LIMIT SOURCES OF I & I TO PREVENT THE SYSTEM FROM BEING OVERWHELMED BY SEVERE RAIN EVENTS. |
Violation |
B |
SSO |
1133840 |
02/06/2024 |
SSOS |
Type: Category 1 Spill; Natural Disaster (specify below) caused 1350 gallons of sewage to spill from Gravity Mainline, Manhole at NOT-40201062244-3094 OLIVE ST. to Other (specify below) |
Plan Rehabilitation or Replacement of Sewer. N/A |
Violation |
B |
SSO |
1133839 |
01/27/2024 |
SSOS |
Type: Category 1 Spill; Natural Disaster (specify below) caused 25080 gallons of sewage to spill from Manhole at NOT-40201056924-IMPERIAL AVE & MARLIN DR. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Surface Water |
Other (specify below). CCTV, MAINS CLEANING CYCLE. REPLACE THE EXISTING FRAME AND COVER WITH A SEALED COMPOSITE COVER TO PREVENT I & I AND EXFILTRATION FROM THE MANHOLE STRUCTURE. |
Violation |
B |
SSO |
1133835 |
01/22/2024 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only), Natural Disaster (specify below), Rainfall Exceeded Design, I and I (Separate Collection System Only), Vandalism (specify below) caused 11400000 gallons of sewage to spill from Inside Building or Structure, Manhole, Other Sewer System Structure at NOT# 40201055600 337 W. 35TH ST. (SMO3) to Building or Structure, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3), Surface Water, Unpaved Surface |
Other (specify below). SEE TECHNICAL REPORT |
Violation |
A |
SSO |
1133836 |
01/22/2024 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only), Natural Disaster (specify below), Rainfall Exceeded Design, I and I (Separate Collection System Only) caused 2400 gallons of sewage to spill from Manhole at NOT# 40201055598 6655 ALVARADO RD. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3), Surface Water, Unpaved Surface |
Other (specify below). THERE IS NO SPILL CORRECTIVE ACTION TAKEN AT THIS TIME. |
Violation |
B |
SSO |
1133833 |
01/09/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 2520 gallons of sewage to spill from Manhole at NOT# 40201051560 18580 POLVERA DR. to Other (specify below), Unpaved Surface |
Adjusted Schedule/Method of Preventive Maintenance, Inspected Sewer Using CCTV to Determine Cause. RELIEVED ROOT BLOCKAGE FROM THE MANHOLE. MANAGEMENT AND PLANNERS WILL HAVE A MEETING TO DISCUSS A FREQUENCY CHANGE. |
Violation |
B |
SSO |
1133831 |
12/10/2023 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 1690 gallons of sewage to spill from Upper Lateral (Public) at NOT# 40201041731 3902 CLARK ST. to Surface Water, Unpaved Surface |
Inspected Sewer Using CCTV to Determine Cause. PIPE WAS REPLACED |
Violation |
B |
SSO |
1133828 |
11/13/2023 |
SSOS |
Type: Category 1 Spill; Debris from Construction, Vandalism (specify below) caused 410 gallons of sewage to spill from Manhole at NOT# 40201032460 10494 BROOKTREE TER. to Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3), Unpaved Surface |
Inspected Sewer Using CCTV to Determine Cause. THE SPILL CORRECTIVE ACTION WAS TO RELIEVE THE BLOCKAGE. IT APPEARS A CONSUMER REPLASTERD A POOL AND DISCARDED OLD PLASTER IN OUR SYSTEM. |
Violation |
B |
SSO |
1133827 |
11/03/2023 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance caused 3240 gallons of sewage to spill from Inside Building or Structure, Manhole at NOT# 40201026998 10401 ROSELLE ST. to Building or Structure, Drainage Conveyance System, Drainage Conveyance System that discharges to surface water, Paved Surface, Street/Curb and Gutter (2 3) |
Other (specify below). REMOVED HARDEND ASPHALT FROM THE COLLECTIONS SYSTEM. |
Violation |
B |
SSO |
1133822 |
08/23/2023 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation caused 13433 gallons of sewage to spill from Force Main at NOT# 40201001630 20278 LAKE DR. to Drainage Conveyance System, Paved Surface, Unpaved Surface |
Repaired Facilities or Replaced Defect. SPILL CORRECTIVE ACTION WAS CONSTRUCTION CREWS RESPONDED AND MADE REPAIRS TO THE FORCE MAIN AND ENCASED IT FOR ADDED PROTECTION. |
Violation |
A |
SSO |
1133821 |
08/23/2023 |
SSOS |
Type: Category 1 Spill; Debris-Rags, Fats, Oil and Grease (FOG) caused 975 gallons of sewage to spill from Manhole at 690 66th St. to Drainage Conveyance System |
Adjusted Schedule/Method of Preventive Maintenance, Inspected Sewer Using CCTV to Determine Cause. Adjust maintenance schedule evaluate pipe after cctv. |
Violation |
B |
SSO |
1133819 |
07/20/2023 |
SSOS |
Type: Category 1 Spill; Debris-General, Debris-Rags, Pump Station Failure - Mechanical caused 1950 gallons of sewage to spill from Other (specify below), Pump Station at NOT# 40200989988, 1740 EAST MISSION BAY DR. to Building or Structure, Other (specify below), Paved Surface, Unpaved Surface |
Repaired Facilities or Replaced Defect. Repaired defect. |
Violation |
A |
SSO |
1114856 |
03/24/2023 |
SSOS |
Type: Category 1. Pipe Structural Problem/Failure;CRACKED CAST IRON TEE caused 53168.0 gallons of sewage to spill from Force Main;N/A at NOT# 40200566690 - 18655 W.BERNARDO DR (SPS 77A SOUTH FORCE MAIN VAULT) to Building or Structure;Surface Water;Unpaved surface;LAKE HODGES. Surface water body affected (LAKE HODGES). |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Restored flow;Returned Portion of Spill to Sanitary Sewer System. ;CITY CREWS RESPONDED, ISOLATED THE SEWER FORCE MAIN, TO MITIGATE ACTIVE OVERFLOW. CITY CREWS THEN ATTEMPTED TO TRANSPORT CONTAINMENT DEVICES (VACTORS, WATER TRUCKS) TO DISCHARGE THE WASTEWATER INTO THAT WAS WITHIN THE VAULT TO IDENTIFY THE SOURCE OF THE FAILURE. DUE TO THE ENVIRONMENTALLY SENSITIVE AREA AND DAYS OF RAIN THAT PRECEDED THE SPILL, THE ACCESS ROAD WAS IMPASSABLE TO ANYTHING BUT LIGHT DUTY ATV¿S. AFTER TWO DAYS OF PUMP STATION SHUTDOWN AND TO AVOID SPILLING INTO LAKE HODGES, 27,871 GALLONS OF WASTEWATER WAS DISCHARGED TO LAND FROM THE FLOODED VAULT TO FACILITATE ENTRY TO IDENTIFY THE FORCEMAIN FAILURE WHICH WAS A CRACKED 20¿ CAST IRON TEE. PUMP STATION WAS BROUGHT BACK ON-LINE TO EMPTY THE CONTAINMENT POND AT THE PUMP STATION THAT WAS AT A CRITICAL LEVEL THAT COULD HAVE DISCHARGED UP TO 375,000/HR. INTO LAKE HODGES HAD IT NOT BEEN PUMPED DOWN. THE VAULT CONTAINED THE WASTEWATER THAT LEAKED FROM THE CRACKED TEE DURING PUMP STATION OPERATION. TO FACILITATE EMPTYING THE VAULT A SECOND TIME TO INSERT A TEMPORARY SPOOL IN PLACE OF THE CRACKED TEE THE CITY DEPLOYED BARGES ON LAKE HODGES TO PUMP THE WASTEWATER INTO CONTAINMENT VESSELS THAT TRANSPORTED THE WASTEWATER TO A BOAT RAMP WHERE IT WAS RETRIEVED BY VACTOR TRUCKS AND RETURNED TO THE COLLECTION SYSTEM. ALL AGENCIES WERE NOTIFIED, WATER QUALITY SAMPLES WERE TAKEN. |
Violation |
A |
SSO |
1112306 |
01/16/2023 |
SSOS |
Type: Category 1. Pump Station Failure-Controls;DCS SHUT DOWN PUMPS DUE TO PLC PROGRAMMING ERROR AT PUMP STATION 2 caused 9900000.0 gallons of sewage to spill from Inside Building or Structure;Manhole;Pump station;SPILL APPEARANCE POINT FROM MANHOLES
ADDRESS SAP EQUIP # FB PG MH #
4238 VENUS STREET 10139284 C18S 179
1431 PACIFIC HIGHWAY 10661889 F21S 626
WEST HARBOR & KETTNER BLVD. 10662199 F22S 543
MIDWAY DRIVE AND ROSECRANS 10167296 D19S 92
J STREET AND 3RD AVE 10302217 G22S 557
4114 WEST POINT LOMA BLVD 10141978 C18S 164
3109 SPORTS ARENA BLVD. 10165565 D18S 68
BARNETT AVE AND MIDWAY DRIVE 10475261 E19S 406
MIDWAY DRIVE AND RILEY STREET 10167005 D19S 70
BARNETT AND TRUXTON 10029913 D19S 627
ROSECRANS AND LYTTON STREET 10167495 D19S 121
2838 KEATS STREET 10075429 C21S 865
RILEY AND KURTZ STREET 10165462 D18S 76
4TH AVENUE AND K STREET 10296212 G22S 569
LOMA RIVERA DR & LOMA RIVERA LANE 10140570 C18S 196
1566 SCOTT STREET 10141694 C21S 295
SAN DIEGO RIVER UNDER JCT I-5 & I-8 10205121 E18S 1
2543 NORTH HARBOR DR 10255834 F21S 203
3936 JUPITER ST (SPS 40) 10163503 D18S 220
4098 LOMA RIVIERA CIRCLE 10140773 C18S 199
INSIDE BUILDINGS
4114 W. POINT LOMA BLVD.
2838 KEATS ST.
601 PACIFIC HWY.
1202 KETTNER BLVD.
700 W. HARBOR DR.
380 K ST.
4236 VENUS ST.
1431 PACIFIC HWY.
380 K St.
855 W. CEDAR ST. (FIRE STATION 2)
CONSTRUCTION AREA AT TERMINAL 1 SD INTNL AIRPORT at NOT# 40200919290 - 4077 North Harbor Drive, San Diego, CA (SPS #2) to Beach;Building or Structure;Paved Surface;Separate Storm Drain;Street/Curb and Gutter;Surface Water;Unpaved surface;N/A. Surface water body affected (SAN DIEGO BAY, SAN DIEGO RIVER, PACIFIC OCEAN.). |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Restored flow;Returned Portion of Spill to Sanitary Sewer System. ;N/A |
Violation |
A |
SSO |
1099129 |
01/18/2022 |
SSOS |
Type: Category 1. Other (specify below);SLUDGE caused 6000.0 gallons of sewage to spill from Other sewer system structure;BIOSOLIDS STORAGE TANK at NOT-40200767413 to Other (specify below);UNNAMED CREEK. Surface water body affected (UNNAMED CREEK). |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;CREWS RESPONDED, INVESTIGATED, RECOVERED PORTION OF SPILL, TRACK FINAL DESTINATION, CLEANED UP AREA. |
Violation |
B |
SSO |
1080361 |
10/17/2020 |
SSOS |
Type: Category 3. Other (specify below);Heavy root blockage. caused 120.0 gallons of sewage to spill from Gravity Mainline;Lateral Clean Out (Private);N/A at NOT#40200593310 to Building or Structure;Crawl space under building.. No surface water body affected. |
. |
Violation |
B |
SSO |
1079620 |
09/14/2020 |
SSOS |
Type: Category 3. Debris-Rags;GREASE AND RAG BLOCKAGE caused 274 gallons of sewage to spill from Inside Building or Structure;Manhole;N/A at NOT#40200581199 to Building or Structure;Drainage Channel;Paved Surface;Separate Storm Drain;Street/Curb and Gutter;N/A. No surface water body affected. |
. |
Violation |
B |
SSO |
1079459 |
09/13/2020 |
SSOS |
Type: Category 3. Debris-General;DEBRIS BLOCKAGE caused 182.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE at NOT# 40200580629 to Paved Surface;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1079323 |
09/10/2020 |
SSOS |
Type: Category 3. Grease Deposition (FOG);HEAVY GREASE BLOCKAGE caused 190.0 gallons of sewage to spill from Lateral Clean Out (Private);N/A at NOT# 40200579737 to Drainage Channel;Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;Unpaved surface;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1078121 |
08/12/2020 |
SSOS |
Type: Category 1. Root Intrusion;HEAVY ROOT BLOCKAGE. caused 3850.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200568058 to Beach;Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;Surface Water;Unpaved surface;PARTIALLY, CAPTURED, RECOVERED AND RETURNED TO SEWER SYSTEM, REMAINDER ENTERED INTO STORM DRAIN/PACIFIC OCEAN.. Surface water body affected (PACIFIC OCEAN.). |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Other (specify below);Restored flow;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;INVESTIGATED/PARTIALLY CONTAINED/RELIEVED BLOCKAGE/ TRACKED FINAL SPILL DESTINATION AND CLEANED UP AREA. |
Violation |
A |
SSO |
1077930 |
08/09/2020 |
SSOS |
Type: Category 2. Other (specify below);90* DEGREE 8" PVC ELBOW caused 2275.0 gallons of sewage to spill from Gravity Mainline;N/A at NOT#40200567138 to Other (specify below);SOAKED INTO SOIL OUTSIDE STORM DRAIN OUTLET. No surface water body affected. |
Cleaned-Up;Contained all or portion of spill;Restored flow;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;CITY CREWS RESPONDED,INVESTIGATED,RELIEVED,TRACKED FINAL DESTINATION AND CLEANED UP AREA |
Violation |
B |
SSO |
1076205 |
06/27/2020 |
SSOS |
Type: Category 2. Pump Station Failure-Mechanical;N/A caused 4500.0 gallons of sewage to spill from Gravity Mainline;Pump station;N/A at NOT#40200547686 to Other (specify below);CAPTURED RECOVERED AND RETURN BACK TO SEWER SYSTEM. No surface water body affected. |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Other (specify below);Restored flow;Returned All Spill to Sanitary Sewer System;Property Owner Notified;Other Enforcement Agency Notified. ;INVESTIGATE/ CONTAINED/ PUMP CREW RELIEVED / TRACK FINAL DESTINATION/ CLEANED UP AREA AND STORM DRAIN |
Violation |
B |
SSO |
1077136 |
06/27/2020 |
SSOS |
Type: Category 2. Pump Station Failure-Mechanical;N/A caused 4500.0 gallons of sewage to spill from Lateral Clean Out (Private);Pump station;PRIVATE CLEAN OUTS at NOT#40200547686 to Other (specify below);CAPTURED,RECOVERED,RETURNED BACK TO SEWER SYSTEM. No surface water body affected. |
Cleaned-Up;Contained all or portion of spill;Restored flow;Returned All Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;INVESTIGATE/CONTAINED/ PUMP CREW RELIEVED/TRACK FINAL DESTINATION, CLEANED UP AREA / STORM DRAIN. |
Violation |
B |
SSO |
1075832 |
06/17/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS caused 210.0 gallons of sewage to spill from Lateral Clean Out (Public);COMING OUT OF DRAIN PIPE ON PROPERTY at NOT#40200541673 to Drainage Channel;Paved Surface;Street/Curb and Gutter;Unpaved surface;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1075125 |
05/28/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS. caused 113.0 gallons of sewage to spill from Lateral Clean Out (Private);TWO OVERFLOWING CLEAN-OUTS. at NOT#40200527156 to Combined Storm Drain (Combined CS only);Other (specify below);Paved Surface;Street/Curb and Gutter;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1074167 |
05/14/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS AND DEBRIS. caused 66 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200521885 to Other (specify below);Unpaved surface;OVERFLOW SOAKED INTO EASEMENT AREA.. No surface water body affected. |
. |
Violation |
B |
SSO |
1073195 |
04/28/2020 |
SSOS |
Type: Category 3. Grease Deposition (FOG);GREASE BLOCKAGE caused 870.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE at NOT#40200515782 to Paved Surface;Street/Curb and Gutter;Unpaved surface;SETTLED IN CANYON AREA. No surface water body affected. |
. |
Violation |
B |
SSO |
1073205 |
04/27/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS. caused 232.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200515691 to Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1073125 |
04/26/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS caused 270.0 gallons of sewage to spill from Manhole;MANHOLE at NOT#40200515280 to Other (specify below);CAPTURED, RECOVERED AND RETURNED SEWAGE BACK TO SEWER SYSTEM FROM BACK YARDS.. No surface water body affected. |
. |
Violation |
B |
SSO |
1072868 |
04/19/2020 |
SSOS |
Type: Category 3. Grease Deposition (FOG);HEAVY GREASE caused 175.0 gallons of sewage to spill from Lateral Clean Out (Private);Manhole;PRIVATE LATERAL AND MANHOLE at NOT#40200513284 to Other (specify below);Separate Storm Drain;PARTIALLY RECAPTURED, RECOVERED AND RETURNED TO SEWER SYSTEM - REMAINDER SETTLED IN SOIL AREA. No surface water body affected. |
. |
Violation |
B |
SSO |
1072867 |
04/18/2020 |
SSOS |
Type: Category 3. Debris-General;ROPE caused 540.0 gallons of sewage to spill from Manhole;UNDOCUMENTED MANHOLE at NOT#40200513279 to Other (specify below);PARTIALLY CAPTURED, RECOVERED AND RETURNED TO SEWER SYSTEM - REMAINDER SETTLED IN SOIL AREA. No surface water body affected. |
. |
Violation |
B |
SSO |
1072571 |
04/13/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOT BLOCKAGE. caused 28.0 gallons of sewage to spill from Manhole;OVER FLOWING MANHOLE. at NOT#40200510432 to Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1072567 |
04/10/2020 |
SSOS |
Type: Category 1. Flow Exceeded Capacity (Separate CS Only);PUMP STATION 64 - SYSTEM OVERLOAD DUE TO RAIN STORM. caused 12600.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200509525 to Other (specify below);Paved Surface;Separate Storm Drain;Surface Water;PARTIALLY CAPTURED, RECOVERED AND RETURNED DILUTED SEWAGE TO SEWER SYSTEM-REMAINDER SETTLED IN THE STORM DRAIN SYSTEM.. Surface water body affected (LOS PENASQUITOS LAGOON.). |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Other (specify below);Restored flow;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;CREWS RESPONDED, INVESTIGATED, STOPPAGE RELIEVED ITSELF (PS#64), INVESTIGATED OVERFLOW FINAL DESTINATION, CLEANED-UP AREA AND PARTIALLY RECOVERED SEWAGE FROM STORM DRAIN SYSTEM. |
Violation |
B |
SSO |
1072860 |
04/10/2020 |
SSOS |
Type: Category 1. Flow Exceeded Capacity (Separate CS Only);SYSTEM OVER CAPACITY DUE TO SEWAGE AND RAIN SURCHARGES CAUSING THE SYSTEM TO OVERFLOW caused 1.123E7 gallons of sewage to spill from Other sewer system structure;METER MONITORING STATION - JUNCTION STATION (FLAPPER VALVE RELEASE) at NOT#40200511275 to Surface Water;ENTERED THE SWEETWATER RIVER WHICH FLOWS INTO THE SAN DIEGO BAY. Surface water body affected (SWEETWATER RIVER AND SAN DIEGO BAY). |
Other (specify below). ;CREWS RESPONDED AFTER NOTIFICATION, INVESTIGATED AREA, NO SPILL UPON ARRIVAL, REVIEW DATA HISTORY FOR SITE IN QUESTION, GATHER INFORMATION FROM OTHER AGENCY, INVESTIGATED OVERFLOW FINAL DESTINATION AND TOOK WATER SAMPLES OF THE AREA IN QUESTION. |
Violation |
B |
SSO |
1072546 |
04/10/2020 |
SSOS |
Type: Category 1. Operator Error;STOPPAGE CAUSE UNKNOWN - SYSTEM CAPACITY OVERLOAD caused 28500.0 gallons of sewage to spill from Manhole;MANHOLE OVERFLOW DUE TO RAIN SURCHARGE at NOT#40200509426 to Paved Surface;Separate Storm Drain;Street/Curb and Gutter;Surface Water;PARTIALLY CAPTURED, RECOVERED AND RETURNED TO THE SEWER SYSTEM - THE REMAINDER UNCLEAR OF FINAL DESTINATION - POSSIBLY THE SAN DIEGO BAY.. Surface water body affected (POSSIBLY - THE SAN DIEGO BAY). |
Cleaned-Up;Contained all or portion of spill;Restored flow;Returned Portion of Spill to Sanitary Sewer System;Other Enforcement Agency Notified. ;CREWS RESPONDED, INVESTIGATED, RELIEVED STOPPAGE, INVESTIGATED OVERFLOW FINAL DESTINATION, CCTV MAIN AND CLEANED UP AREA UPON DEPARTURE. |
Violation |
B |
SSO |
1072550 |
04/10/2020 |
SSOS |
Type: Category 2. Flow Exceeded Capacity (Separate CS Only);SYSTEM OVER CAPACITY DUE TO HEAVY RAIN. caused 30615 gallons of sewage to spill from Inside Building or Structure;Manhole;VARIOUS LOCATIONS BACK UP - ;3115 LOMA RIVIERA DR., 2234 LYTTON ST., 423 VENUS ST., 4114 WEST POINT LOMA BL., 875 WEST CEDAR ST., 1431 PACIFIC HWY., 700 WEST HARBOR DR. AND 601 PACIFIC HWY. at NOT#40200509578 to Other (specify below);PARTIALLY CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM, REMAINDER SOAKED INTO THE AREAS.. No surface water body affected. |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Other (specify below);Restored flow;Returned Portion of Spill to Sanitary Sewer System;Property Owner Notified;Other Enforcement Agency Notified. ;CREWS RESPONDED, INVESTIGATED, SET-UP CONTAINMENT, NOTIFIED PUMP STATION, SYSTEM RESTORED FLOW CAPACITY, INVESTIGATED OVERFLOW FINAL DESTINATIONS, CLEANED-UP AREA AND STORM DRAINS. |
Violation |
B |
SSO |
1071907 |
03/20/2020 |
SSOS |
Type: Category 3. Debris from Construction;CONTRACTOR. caused 35.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200499109 to Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1071811 |
03/18/2020 |
SSOS |
Type: Category 3. Debris-General;DEBRIS caused 55.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE at NOT#40200498810 to Paved Surface;Separate Storm Drain;Street/Curb and Gutter;RECOVERED FROM STORM DRAIN. No surface water body affected. |
. |
Violation |
B |
SSO |
1071702 |
03/12/2020 |
SSOS |
Type: Category 3. Debris-General;ROOTS AND GREASE caused 29.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE at NOT#40200496330 to Paved Surface;Street/Curb and Gutter;RECOVERED IN DRIVEWAY AT ADDRESS. No surface water body affected. |
. |
Violation |
B |
SSO |
1071569 |
03/06/2020 |
SSOS |
Type: Category 3. Root Intrusion;HEAVY ROOTS. caused 85.0 gallons of sewage to spill from Manhole;OVERFLOWING MANHOLE. at NOT#40200493300 to Other (specify below);Paved Surface;Separate Storm Drain;Street/Curb and Gutter;CAPTURED, RECOVERED AND RETURNED SEWAGE TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
1072909 |
02/28/2020 |
SSOS |
Type: Category 3. Grease Deposition (FOG);HEAVY GREASE caused 600.0 gallons of sewage to spill from Lateral Clean Out (Private);INSIDE MULTIPLE HOMES at NOT#40200488603 to Building or Structure;Other (specify below);CAPTURED, RECOVERED AND RETURNED TO SEWER SYSTEM.. No surface water body affected. |
. |
Violation |
B |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|