Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1136832 |
11/18/2024 |
SSOS |
Type: Category 1 Spill; Debris-General,Inappropriate Discharge to Collection System,Debris-Rags,Debris-wipes/Non-disposables,Vandalism (specify below) caused 30258 gallons of sewage to spill from Manhole,Lateral Clean Out (Private) at 4080 Lime St. to Drainage Conveyance System that discharges to surface water |
Other (specify below). Install remote monitoring system in location of spill and in the area of clustered county and local government buildings. |
Violation |
A |
SSO |
1136858 |
11/18/2024 |
SSOS |
Type: Category 1 Spill; Debris-wipes/Non-disposables,Debris-Rags,Debris-General,Inappropriate Discharge to Collection System,Vandalism (specify below) caused 30258 gallons of sewage to spill from Manhole,Lateral Clean Out (Private) at 4080 Lime St. to Drainage Conveyance System that discharges to surface water |
Other (specify below). Install remote monitoring system in location of spill and in the area of clustered county and local government buildings. |
Violation |
A |
SSO |
1134435 |
09/26/2024 |
SSOS |
Type: Category 1 Spill; Construction Diversion Failure caused 20615 gallons of sewage to spill from Manhole at 4646 Brockton Ave x Tequesquite Ave to Drainage Conveyance System that discharges to surface water |
Other (specify below). City will procure equipment and supplies to for additional spill response readiness beyond current capabilities, including additional portable pumping and spill containment capabilities. |
Violation |
A |
SSO |
1131253 |
08/14/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 90 gallons of sewage to spill from Manhole at Sunbeam Dr & Natalie Lane to Drainage Conveyance System |
Other (specify below),Post Spill CCTV,Inspected Sewer Using CCTV to Determine Cause. In 8 weeks will apply root control foaming agent. CCTV inspection in 6 months with a follow-up cleaning/root removal if necessary. |
Violation |
U |
SSO |
1133316 |
06/29/2023 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation caused 7225 gallons of sewage to spill from Lower Lateral (Public) at Riverside City to Drainage Conveyance System that discharges to surface water |
Repaired Facilities or Replaced Defect. Stopped leak, repaired lateral. |
Violation |
A |
SSO |
1133315 |
06/29/2023 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Installation caused 7200 gallons of sewage to spill from Lower Lateral (Public) at Riverside City to Drainage Conveyance System that discharges to surface water |
Repaired Facilities or Replaced Defect. Stopped leak, repaired lateral. |
Violation |
A |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|