Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1142220 |
03/02/2025 |
SSOS |
Type: Category 1 Spill; Other (specify below) caused 61200 gallons of sewage to spill from Gravity Mainline at Behind 35197 Hogan Dr Beaumont CA 92223 to Drainage Conveyance System,Unpaved Surface |
Plan Rehabilitation or Replacement of Sewer. The city is in the process of redesigning and improving the area around the spill. The city has brought in engineers, both in-house and contracted for different ideas for the permanent repair. Until final evaluation and plans are submitted the line will continue to be bypassed and monitored numerous times daily by collections staff. There is an extra Standby bypass pump on site for the extra precaution. |
Violation |
A |
SSO |
1141335 |
03/02/2025 |
SSOS |
Type: Category 1 Spill; Other (specify below) caused 61200 gallons of sewage to spill from Gravity Mainline at Behind 35197 Hogan Dr Beaumont CA 92223 to Unpaved Surface,Drainage Conveyance System |
Plan Rehabilitation or Replacement of Sewer. The city is in the process of redesigning and improving the area around the spill. The city has brought in engineers, both in-house and contracted for different ideas for the permanent repair. Until final evaluation and plans are submitted the line will continue to be bypassed and monitored numerous times daily by collections staff. There is an extra Standby bypass pump on site for the extra precaution. |
Violation |
A |
SSO |
1137429 |
12/04/2024 |
SSOS |
Type: Category 1 Spill; Other (specify below),Vandalism (specify below) caused 100 gallons of sewage to spill from Manhole at Harmon Heights and Hagen Heights to Street/Curb and Gutter (2 3),Paved Surface,Drainage Conveyance System |
Inspected Sewer Using CCTV to Determine Cause,Post Spill CCTV,Other (specify below). More investigations on the 4 houses with pools. |
Violation |
A |
SSO |
1136408 |
11/10/2024 |
SSOS |
Type: Category 1 Spill; Other (specify below),Pump Station Failure - Controls caused 38250 gallons of sewage to spill from Manhole at Olivewood lift station to Unpaved Surface,Drainage Conveyance System,Drainage Conveyance System that discharges to surface water,Paved Surface |
Other (specify below). Please see attached spill report |
Violation |
A |
SSO |
1136533 |
11/10/2024 |
SSOS |
Type: Category 1 Spill; Pump Station Failure - Controls,Other (specify below) caused 38250 gallons of sewage to spill from Manhole at Olivewood lift station to Unpaved Surface,Drainage Conveyance System,Paved Surface,Drainage Conveyance System that discharges to surface water |
Other (specify below). Please see attached spill report |
Violation |
A |
SSO |
1133628 |
03/04/2024 |
SSOS |
Type: Category 1 Spill; Debris from Construction, Debris-Rags, Debris-wipes/Non-disposables, Fats, Oil and Grease (FOG) caused 12000 gallons of sewage to spill from Manhole at Castello LN and Florentina CT to Drainage Conveyance System, Paved Surface, Street/Curb and Gutter (2 3), Unpaved Surface |
Other (specify below). Area is under control of builder (Taylor Morrison) so the City put a stop work order in until then clean and video the system along with other punch list items. |
Violation |
A |
SSO |
1133625 |
07/10/2023 |
SSOS |
Type: Category 1 Spill; Air Relief Valve (ARV)/ Blow-Off Valve (BOV) Failure caused 110 gallons of sewage to spill from Force Main, Other Sewer System Structure at Oak Valley Pkwy to Unpaved Surface |
Repaired Facilities or Replaced Defect. switched to redundant force main, while repairs are being made on faulty air vac. |
Violation |
A |
SSO |