Place ID 630953
|
|
|
|
|
|
General Information
|
Region |
Place ID |
Place Name |
Place Type |
Place Address |
Place County |
2 |
630953 |
Novato And Ignacio CS |
Collection_System |
500 Davidson Novato, CA, 94945 |
Marin |
|
|
Related Parties
|
|
Total Related Parties: 11
|
|
|
Regulatory Measures
|
|
Total Reg Measures: 1
|
|
|
Violations
|
Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1141043 |
02/21/2025 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 960 gallons of sewage to spill from Force Main at 498 Canyon Rd. to Drainage Conveyance System that discharges to surface water |
Repaired Facilities or Replaced Defect. Hired a contractor same day, dug up and located the leak. repaired the leak, tested for any other leaks, and backfilled and temp paved in the same day. |
Violation |
A |
SSO |
1140504 |
02/04/2025 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 2700 gallons of sewage to spill from Manhole at 854 Wilson Ave. Novato, CA to Drainage Conveyance System that discharges to surface water |
Plan Rehabilitation or Replacement of Sewer. Set alerts of surcharging using Smartcover systems. mandatory set up of bypass pump with known wet weather events. Downstream sections of pipeline in design for replacement and upsizing. |
Violation |
A |
SSO |
1133214 |
01/27/2024 |
SSOS |
Type: Category 1 Spill; Debris-wipes/Non-disposables, Fats, Oil and Grease (FOG) caused 1455 gallons of sewage to spill from Lateral Clean Out (Private) at 23 Cowbarn Ln. Novato, CA 94947 to Surface Water, Unpaved Surface |
Adjusted Schedule/Method of Preventive Maintenance, Enforcement action against Fats, Oil, and Grease (FOG) source, Inspected Sewer Using CCTV to Determine Cause. This line was on a 6 month cleaning frequency due the heavy use from apartments. After having the line surveyed with CCTV equipment, there was still grease stuck in the line downstream of the lateral connection. The flusher was used to remove the remainder of grease. this has been adjusted in the CMMS program to a 3 month cleaning frequency and have a follow up CCTV survey to determine if any further adjustments are needed. |
Violation |
A |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|
|
Total Violations: 3
|
Priority Violations: 0
|
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.
|
Violation Types |
SSOS = Sanitary Sewer Overflow/Spill/
|
|
|
|
Enforcement Actions
|
|
Total Enf Actions: 3
|
|
|
Inspections
|
|
Total Inspections: 4 |
Last Inspection: 02/21/2018 |
|
|
|
|
 |
The current report was generated with data as of: 04/16/2025
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
|
 |