Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1137759 |
12/04/2024 |
SSOS |
Type: Category 1 Spill; Root Intrusion caused 527 gallons of sewage to spill from Gravity Mainline,Manhole at Buri Buri Park to Drainage Conveyance System,Drainage Conveyance System that discharges to surface water,Surface Water |
Inspected Sewer Using CCTV to Determine Cause,Adjusted Schedule/Method of Preventive Maintenance. Corrective actions planned to reduce to possibility for the spill to occur again are that the segments have been added to the quarterly flushing schedule as well as a sewer check periodically in between flushing intervals |
Violation |
A |
SSO |
1136639 |
11/10/2024 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls,Debris from Lateral caused 116 gallons of sewage to spill from Gravity Mainline,Manhole,Lower Lateral (Private) at 161 Longford Dr to Drainage Conveyance System that discharges to surface water,Drainage Conveyance System,Paved Surface |
Post Spill CCTV,Adjusted Schedule/Method of Preventive Maintenance. Steps that are being implemented are as follows:
1. will be CCTV on 11/25/24 and if any failures are found they will be addressed immediately.
2. if no pipe failures are found then moving forward this mainline will be put on the six-month flushing schedule instead of the yearly.
3. ongoing and continuous spill response training for all crew with emphasis on training for our after-hours standby members. |
Violation |
A |
SSO |
1135012 |
09/09/2024 |
SSOS |
Type: Category 1 Spill; Debris-Rags,Debris-General caused 27 gallons of sewage to spill from Gravity Mainline at 618 West Orange Ave. to Paved Surface,Drainage Conveyance System that discharges to surface water,Drainage Conveyance System,Street/Curb and Gutter (2 3),Surface Water |
Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause. Preventative maintenance schedule was adjusted and the sewer line that was plugged was inspected with a CCTV camera. |
Violation |
A |
SSO |
1133173 |
08/09/2023 |
SSOS |
Type: Category 1 Spill; Debris-General caused 1919 gallons of sewage to spill from Manhole at Junipero Serra Blvd - Behind 141 Longford to Drainage Conveyance System |
Adjusted Schedule/Method of Preventive Maintenance. This sanitary sewer segment will be moved from an annual schedule to a 6 month schedule in an effort to prevent future spills. |
Violation |
A |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|