Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1133170 |
01/07/2024 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance caused 146580 gallons of sewage to spill from Manhole at 11603 Donner Pass Rd. to Drainage Conveyance System that discharges to surface water, Surface Water |
Added Sewer to Preventive Maintenance Program, Inspected Sewer Using CCTV to Determine Cause, Repaired Facilities or Replaced Defect. Please See Attached Initial SSR and Spill Memo |
Violation |
B |
SSO |
1133169 |
09/12/2023 |
SSOS |
Type: Category 1 Spill; Damage by Others Not Related to Collection System Construction/Maintenance caused 43220 gallons of sewage to spill from Manhole at Truckee High School to Drainage Conveyance System that discharges to surface water, Surface Water, Unpaved Surface |
Inspected Sewer Using CCTV to Determine Cause, Repaired Facilities or Replaced Defect. Update 10-25-23 See attached email update. TSD is working with a consultant to install a flow monitor at the spill site to come to a final spill volume. TSD will update when study is complete, and include a Technical report if over 50,000 gallons. |
Violation |
B |
SSO |
1115489 |
04/03/2023 |
SSOS |
Type: Category 1. Air Relief Valve (ARV)/Blow-Off Valve (BOV) Failure caused 108000.0 gallons of sewage to spill from Force Main at Pine Forest Lift Station ARV Vault 11093 Comstock Drive to Paved Surface;Separate Storm Drain;Street/Curb and Gutter;Surface Water;Unpaved surface. Surface water body affected (Final water quality sampling results are pending. See attached WQ Sampling Results-Map-Photos Summary.). |
Cleaned-Up;Mitigated Effects of Spill;Restored flow;Other Enforcement Agency Notified. ;Update 4/28/23 please see attached update documents. Technical Report will be submitted by 5/28/23 with detailed information. |
Violation |
B |
SSO |
1111018 |
12/03/2022 |
SSOS |
Type: Category 2. Debris-Wipes/Non-Dispersables;Please see attached TSD Sewer Service Request (SSR) caused 34381.0 gallons of sewage to spill from Manhole;Main spill appearance point was a manhole next to the lift station, the second appearance point was a manhole on the lift station overflow vault. The manhole on the overflow vault stopped spilling when the manhole lid next to the lift station was removed to try to clear stoppage. at Alder Creek Lift Station 13797 Alder Creek . to Unpaved surface;SSO ran out into an unpaved wooded area approximately 270 feet away from the lift station. Please see attached TSD Sewer Service Request (SSR). No surface water body affected. |
Cleaned-Up;Mitigated Effects of Spill;Contained all or portion of spill;Restored flow;Other Enforcement Agency Notified. ;Please see attached TSD Sewer Service Request (SSR) |
Violation |
B |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|