Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1147145 |
08/27/2025 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 12000 gallons of sewage to spill from Manhole at Terrace Blvd. x Lupine Rd. #2 to Paved Surface,Drainage Conveyance System that discharges to surface water,Street/Curb and Gutter (2 3) |
Repaired Facilities or Replaced Defect. Enabled a float switch in the neutralization tank to stop the plant by SCADA automatically. Reviewed procedures related to not having an operator direct a technician to start up the plant and check operational setpoints before and during startup and operation. Discussed adding the sewer improvements to an upcoming capital improvement project. |
Violation |
A |
SSO |
1141326 |
03/16/2025 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only),Other (specify below) caused 9642 gallons of sewage to spill from Gravity Mainline at 1406 Lupine Road to Drainage Conveyance System that discharges to surface water |
Repaired Facilities or Replaced Defect. Additional sensors to be installed at the drinking water treatment plant in the lateral system, to identify if there is excess flow due to a plant failure in the future. |
Violation |
A |
SSO |
1133126 |
05/28/2024 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 110 gallons of sewage to spill from Gravity Mainline, Other Sewer System Structure at Piper St at Rec Park to Drainage Conveyance System that discharges to surface water |
Plan Rehabilitation or Replacement of Sewer, Repaired Facilities or Replaced Defect. Future project to include replacement of sewer line from culvert to nearest manhole, for proper fall. |
Violation |
B |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|