| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1150063 |
12/21/2025 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 9375 gallons of sewage to spill from Manhole,Gravity Mainline at Pickwick LS - Old Arcata Road - MHU10A to Surface Water |
Added Sewer to Preventive Maintenance Program. CIP Project |
Violation |
B |
SSO |
| 1150038 |
12/21/2025 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only) caused 96000 gallons of sewage to spill from Manhole,Gravity Mainline at West End Road MH OO20 to Surface Water |
Plan Rehabilitation or Replacement of Sewer. CIP project |
Violation |
B |
SSO |
| 1150047 |
12/21/2025 |
SSOS |
Type: Category 1 Spill; Pump Station Failure - Mechanical,Flow Exceeded Capacity (Separate Collection System Only) caused 57675 gallons of sewage to spill from Manhole at MH O7 - 5th & D St to Paved Surface,Street/Curb and Gutter (2 3) |
Plan Rehabilitation or Replacement of Sewer. Upgrade project in planning stage for new pumps at lift station |
Violation |
B |
SSO |
| 1138370 |
12/29/2024 |
SSOS |
Type: Category 1 Spill; Other (specify below),Flow Exceeded Capacity (Separate Collection System Only) caused 2100 gallons of sewage to spill from Manhole at South I Street to Other (specify below) |
Plan Rehabilitation or Replacement of Sewer. Once the headworks is in service, larger pumps will be responsible for pumping to the WWTP |
Violation |
B |
SSO |
| 1158064 |
11/05/2024 |
Order Conditions |
While the Enrollee adopted an updated SSMP in 2023, staff are unaware of when the last SSMP audit may have occurred. The inspection found that while the Enrollee’s collection system was visually inspected in the 1990s and again around 2009, relatively minimal CCTV5 has taken place since. The Enrollee stated that while they can perform CCTV, they do not have sufficient personnel to take on more than a block or two as needed for trouble shooting. Additionally, in the lower areas of Arcata, the water table is fairly high and there can be large portions of the year where the pipes are underwater, and they are unable to perform CCTV inspections. The Enrollee performs minimal CCTV, and they do not grade CCTV footage from their push camera. As such, they cannot plan/prioritize capital improvement projects based upon graded pipe defects or pipe conditions. The inspection found that contractors working on the Enrollee’s collection system do not currently receive training on the Enrollee’s SERP. Despite I/I being the Enrollee’s largest concern, the Enrollee does not know whether a system wide capacity study has ever been completed. A draft Sea Level Rise Risk Assessment Plan from April 2018 identified the Enrollee’s collection system as being one of the most critical and vulnerable assets. However, this plan was never finalized and additional steps to identify which assets within the collection system were most vulnerable were never taken. |
|
Violation |
B |
Inspection |
| 1158063 |
01/13/2024 |
Deficient Reporting |
Review of spill reporting by the Enrollee revealed that the Enrollee failed to notify CalOES within two hours for the following Category 1 spill over 1,000 gallons: CIWQS Spill ID 892078. |
|
Violation |
B |
Inspection |
| 1133122 |
01/13/2024 |
SSOS |
Type: Category 1 Spill; Flow Exceeded Capacity (Separate Collection System Only), Rainfall Exceeded Design, I and I (Separate Collection System Only) caused 1275 gallons of sewage to spill from Manhole at West End Road MH0020 to Surface Water |
Inspected Sewer Using CCTV to Determine Cause. CCTV is planned in the general area to ascertain why the flow did not continue normally downstream |
Violation |
B |
SSO |
|
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|