Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1140606 |
01/05/2025 |
OEV |
Total Coliform Single Sample Maximum limit is 240 ml/L and reported value was 300 ml/L at EFF-001. |
No reason was determined. |
Violation |
B |
eSMR |
1142045 |
12/31/2024 |
Deficient Reporting |
Discharger did not include all required monitoring data in some SMRs submitted for reporting periods during January through December 2024, in violation of section VIII.B.1 of the MRP. |
|
Violation |
B |
Report |
1142041 |
12/31/2024 |
GWAT |
Discharger exceeded agronomic hydraulic loading rates identified by the Discharger for some crop types on various fields during various months between January and December 2024, in violation of Land Discharge Specification IV.A.1 |
|
Violation |
B |
Report |
1142042 |
12/31/2024 |
GWAT |
Discharger exceeded the BOD cycle loading rate identified in Land Discharge Specification IV.A.3 on various fields during various months between January and December 2024. |
|
Violation |
B |
Report |
1142044 |
12/31/2024 |
Order Conditions |
Discharger exceeded the upper and lower limitations for pH in the storage ponds at various times during January through December 2024, in violation of Construction, Operation, and Maintenance Specification VI.C.2.a.iv. |
|
Violation |
B |
Report |
1142043 |
12/31/2024 |
Order Conditions |
Discharger exceeded total coliform limitations for disinfected tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2024, in violation of Reclamation Specification IV.B.4.b. |
|
Violation |
B |
Report |
1140445 |
12/23/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6.0 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1138287 |
11/20/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
'Nano Bubble Generator' discharge was moved to a location. Staff cleaned the UV Channel as an extra measure. |
Violation |
B |
eSMR |
1138288 |
11/19/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
'Nano Bubble Generator' discharge was moved to a location. Staff cleaned the UV Channel as an extra measure. |
Violation |
B |
eSMR |
1136536 |
10/10/2024 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23 MPN/100 mL and reported value was 30 MPN/100 mL at EFF-001. |
Once accidental change was realized, staff switched to correct dosing calculation. |
Violation |
B |
eSMR |
1128450 |
03/31/2024 |
Deficient Reporting |
Discharger did not report pH at RSW-001 during the week ending 3/30/2024. |
|
Violation |
B |
Report |
1125180 |
12/31/2023 |
Deficient Reporting |
Discharger did not include all required monitoring data in some SMRs submitted for reporting periods during January through December 2023, in violation of section VIII.B.1 of the MRP. |
|
Violation |
B |
Report |
1125175 |
12/31/2023 |
GWAT |
Discharger exceeded agronomic hydraulic loading rates identified by the Discharger for some crop types on various fields during various months between January and December 2023, in violation of Land Discharge Specification IV.A.1 |
|
Violation |
B |
Report |
1125176 |
12/31/2023 |
GWAT |
Discharger exceeded settleable solids limitations identified at Land Discharge Specification IV.A.5 during the period between January and December 2023. |
|
Violation |
B |
Report |
1125179 |
12/31/2023 |
Order Conditions |
Discharger exceeded the upper limitation for pH in the storage ponds at various times during January through December 2023, in violation of Construction, Operation, and Maintenance Specification VI.C.2.a.iv. |
|
Violation |
B |
Report |
1125177 |
12/31/2023 |
Order Conditions |
Discharger exceeded total coliform limitations for disinfected tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2023, in violation of Reclamation Specification IV.B.4.b. |
|
Violation |
B |
Report |
1125178 |
12/31/2023 |
Order Conditions |
Discharger exceeded turbidity limitations for tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2023, in violation of Reclamation Specification IV.B.4.c. |
|
Violation |
B |
Report |
1123403 |
12/31/2023 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 3.1 mg/L and reported value was 4.9 mg/L at EFF-001. |
Staff diverted the flow for the remainder of the reporting period. |
Violation |
B |
eSMR |
1123404 |
12/23/2023 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 6.4 mg/L and reported value was 11.0 mg/L at EFF-001. |
Staff diverted the discharge. |
Violation |
B |
eSMR |
1124357 |
12/02/2023 |
Deficient Reporting |
The Discharger did not report the pH at RSW-001, temperature at RSW-003, or pH at RSW-005 during the week ending 12/2/2023. |
|
Violation |
B |
Report |
1122887 |
11/30/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8.0 MPN/100 mL at EFF-001. |
Operations temporarily increased UV Dose 0n 11-18, and finally increased the high pressure set point on the hydraulic wiping system on 11-25 |
Violation |
B |
eSMR |
1122889 |
11/29/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8.0 MPN/100 mL at EFF-001. |
Operations temporarily increased UV Dose 0n 11-18, and finally increased the high pressure set point on the hydraulic wiping system on 11-25 |
Violation |
B |
eSMR |
1122890 |
11/28/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8.0 MPN/100 mL at EFF-001. |
Operations temporarily increased UV Dose 0n 11-18, and finally increased the high pressure set point on the hydraulic wiping system on 11-25. |
Violation |
B |
eSMR |
1122888 |
11/27/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8.0 MPN/100 mL at EFF-001. |
Operations temporarily increased UV Dose 0n 11-18, and finally increased the high pressure set point on the hydraulic wiping system on 11-25. |
Violation |
B |
eSMR |
1124354 |
11/26/2023 |
Order Conditions |
Filter effluent turbidity exceeded the limitation on 11/26/2023. The limitation is 10 NTU, and the daily maximum turbidity on 11/26/2023 was 15 NTU.
In addition, filter effluent turbidity exceeded 5 NTU for more than 5% of the day on 11/26/2023. |
|
Violation |
B |
Report |
1124355 |
11/18/2023 |
Deficient Reporting |
The Discharger did not report temperature at RSW-005 for the week ending 11/4/2023, or pH and temperature at RSW-003 for the week ending 11/18/2023 |
|
Violation |
B |
Report |
1124356 |
10/08/2023 |
Deficient Reporting |
The Discharger did not report daily minimum UV dose on 10/8/2023. |
|
Violation |
B |
Report |
1117496 |
04/16/2023 |
OEV |
Total Coliform Single Sample Maximum limit is 240 mg/L and reported value was 300 mg/L at EFF-001. |
N/A |
Violation |
B |
eSMR |
1117421 |
03/31/2023 |
CAT1 |
BOD5 @ 20 Deg. C, Percent Removal Monthly Average limit is 10.0 mg/L and reported value was 11.0 mg/L at EFF-001. |
Chemical dosing to reduce the Quaternary Ammonia, and process modifications. |
Violation |
B |
eSMR |
1115917 |
03/27/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115905 |
03/26/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115904 |
03/25/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115908 |
03/24/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115903 |
03/23/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115919 |
03/22/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115915 |
03/21/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115911 |
03/20/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115910 |
03/19/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115906 |
03/18/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance |
Violation |
B |
eSMR |
1115909 |
03/16/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115907 |
03/15/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115902 |
03/14/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance |
Violation |
B |
eSMR |
1115918 |
03/13/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1115916 |
03/12/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
Staff worked many hours on the UV system to ensure that we continued to have enough banks online to achieve full compliance. |
Violation |
B |
eSMR |
1117602 |
03/11/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1117601 |
03/10/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1113958 |
01/31/2023 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 220 lbs and reported value was 578 lbs at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113960 |
01/31/2023 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 3.1 mg/L and reported value was 14 mg/L at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1117599 |
01/31/2023 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10 mg/L and reported value was 17 mg/L at EFF-001. |
|
Violation |
B |
Report |
1117604 |
01/28/2023 |
Deficient Reporting |
Discharger did not report influent TSS for week ending 1/28/2023. |
|
Violation |
B |
Report |
1113961 |
01/28/2023 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 6.4 mg/L and reported value was 12 mg/L at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1117598 |
01/28/2023 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 15 mg/L and reported value was 19 mg/L at EFF-001. |
|
Violation |
B |
Report |
1113834 |
01/22/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113832 |
01/21/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113959 |
01/21/2023 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 454 lbs and reported value was 717 lbs at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113962 |
01/21/2023 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 6.4 mg/L and reported value was 16 mg/L at EFF-001. |
.The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113831 |
01/20/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1117603 |
01/19/2023 |
Order Conditions |
Daily maximum turbidity limitation at UVS-001 is 10 NTU, and discharger reported 13 NTU on 1/25/23 and 15 NTU on 1/26/2023. In addition, daily average turbidity limitation at UVS-001 is 2 NTU, and discharger reported 3 NTU on 1/19/23 and 4 NTU on 1/25/23. |
|
Violation |
B |
Report |
1113830 |
01/19/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113829 |
01/17/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113828 |
01/16/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1113833 |
01/15/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The flow was diverted to the ponds, as soon as it was possible. The City has started treating for Quaternary Ammonia, to regain our nitrifier population. |
Violation |
B |
eSMR |
1114598 |
12/31/2022 |
Deficient Reporting |
Discharger did not include all required monitoring data in some SMRs submitted for reporting periods during January through December 2022, in violation of section VIII.B.1 of the MRP. |
|
Violation |
B |
Report |
1114591 |
12/31/2022 |
GWAT |
Discharger exceeded agronomic hydraulic loading rates identified by the Discharger for some crop types on various fields during various months between January and December 2022, in violation of Land Discharge Specification IV.A.1 |
|
Violation |
B |
Report |
1114592 |
12/31/2022 |
GWAT |
Discharger exceeded agronomic nitrogen loading rates identified by the Discharger on Fields 6B-D during July 2022, in violation of Land Discharge Specification IV.A.2. |
|
Violation |
B |
Report |
1114593 |
12/31/2022 |
GWAT |
Discharger exceeded the cycle average loading rate of 200 lbs/acre/day for biochemical oxygen demand (BOD) on Field 6C during September 2022, in violation of Land Discharge Specification IV.A.3.a. |
|
Violation |
B |
Report |
1114594 |
12/31/2022 |
GWAT |
Monthly average BOD was 41 mg/L at EFF-001 in December 2022, and limit is 40 mg/L. |
|
Violation |
B |
Report |
1114597 |
12/31/2022 |
Order Conditions |
Discharger exceeded the upper limitation for pH in the storage ponds at various times during January through December 2022, in violation of Construction, Operation, and Maintenance Specification VI.C.2.a.iv. |
|
Violation |
B |
Report |
1114595 |
12/31/2022 |
Order Conditions |
Discharger exceeded total coliform limitations for disinfected tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2022, in violation of Reclamation Specification IV.B.4.b. |
|
Violation |
B |
Report |
1114596 |
12/31/2022 |
Order Conditions |
Discharger exceeded turbidity limitations for tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2022, in violation of Reclamation Specification IV.B.4.c. |
|
Violation |
B |
Report |
1112835 |
12/31/2022 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 3.1 mg/L and reported value was 3.9 mg/L at EFF-001. |
Stopped discharge upon discovery (12-5-2022). |
Violation |
B |
eSMR |
1113521 |
11/21/2022 |
Order Conditions |
Daily maximum filter effluent turbidity was 11 NTU on 11/21/2022, and the limit is 10 NTU. |
|
Violation |
B |
Report |
1113520 |
10/03/2022 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 50 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1109917 |
09/30/2022 |
DMON |
Discharger did not monitor biosolids at BIO-001 during Q3 2022 as required in the WDRs. |
|
Violation |
B |
Report |
1104187 |
02/09/2022 |
Order Conditions |
The daily minimum hourly average UV dose is 100 mJ/cm2, and the measured minimum hourly average UV dose was 85 mJ/cm2 on 2/1 and 95 mJ/cm2 on 2/9. |
|
Violation |
B |
Report |
1104059 |
01/23/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 70 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1104058 |
01/21/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 97 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101237 |
01/18/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 99 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101236 |
01/17/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 95 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101235 |
01/16/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 98 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101234 |
01/15/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 98 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1104057 |
01/14/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 98 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101238 |
01/13/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 97 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101241 |
01/12/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 11 mJ/cm2 and reported value was 88 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement in May of 2022. |
Violation |
B |
eSMR |
1101240 |
01/11/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 91 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement in May of 2022. |
Violation |
B |
eSMR |
1101233 |
01/10/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 97 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement will be in May of 2022. |
Violation |
B |
eSMR |
1101239 |
01/09/2022 |
Order Conditions |
UV Dose 1-Hour Average (Mean) limit is 100 mJ/cm2 and reported value was 99 mJ/cm2 at UVS-001. |
Replaced disinfection Hardware. Processor replacement in May of 2022. |
Violation |
B |
eSMR |
1101279 |
12/31/2021 |
Deficient Reporting |
Discharger did not include all required monitoring data in some SMRs submitted for reporting periods during January through December 2021, in violation of section VIII.B.1 of the MRP. |
|
Violation |
B |
Report |
1101273 |
12/31/2021 |
GWAT |
Discharger exceeded agronomic hydraulic loading rates identified by the Discharger for some crop types on various fields during various months between January and December 2021, in violation of Land Discharge Specification IV.A.1 |
|
Violation |
B |
Report |
1101274 |
12/31/2021 |
GWAT |
Discharger exceeded agronomic nitrogen loading rates identified by the Discharger for some crop types on various fields during January through December 2021, in violation of Land Discharge Specification IV.A.2. |
|
Violation |
B |
Report |
1101275 |
12/31/2021 |
GWAT |
Discharger exceeded the cycle average loading rate of 200 lbs/acre/day for biochemical oxygen demand (BOD) on various fields during various months during April 2019 and December 2020, in violation of Land Discharge Specification IV.A.3.a. |
|
Violation |
B |
Report |
1101278 |
12/31/2021 |
GWAT |
Discharger exceeded the upper limitation for pH in the storage ponds at various times during January through December 2021, in violation of Construction, Operation, and Maintenance Specification VI.C.2.a.iv. |
|
Violation |
B |
Report |
1101280 |
12/31/2021 |
LREP |
Discharger submitted some of the SMRs for reporting periods during January through December 2021 after the required submittal date. |
|
Violation |
B |
Report |
1101276 |
12/31/2021 |
Order Conditions |
Discharger exceeded total coliform limitations for disinfected tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2021, in violation of Reclamation Specification IV.B.4.b. |
|
Violation |
B |
Report |
1101277 |
12/31/2021 |
Order Conditions |
Discharger exceeded turbidity limitations for tertiary recycled water at reclaimed water monitoring location REC-001 at various times during January through December 2021, in violation of Reclamation Specification IV.B.4.c. |
|
Violation |
B |
Report |
1097012 |
09/30/2021 |
Deficient Reporting |
Discharger did not monitor biosolids at the required frequency. WDRs require biosolids monitoring once per quarter, and the discharger did not monitor biosolids during the third quarter of 2021. |
|
Violation |
B |
Report |
1088220 |
02/28/2021 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Monthly Average limit is 10 mg/L and reported value was 11 mg/L at EFF-001. |
Discharge was discontinued on 2/23, following the prescribed 5 day analysis, of the first high BOD. |
Violation |
B |
eSMR |
1090606 |
02/27/2021 |
DMON |
Discharger did not monitor Ammonia at the required frequency during all weeks in February. In addition, the effluent BOD result reported by the Discharger for 20 February was ¿exceeds 27 mg/L¿ because the dilutions used in the analysis were not capable of determining a more precise result. Therefore the discharger was not able to report the results of monitoring as required in section I.I of the MRP. Nor could the weekly average effluent BOD be calculated and reported accurately for the week ending 20 February. |
|
Violation |
B |
Report |
1090605 |
02/27/2021 |
CAT1 |
Biochemical Oxygen Demand (BOD) (5-day @ 20 Deg. C) Weekly Average limit is 15 mg/L and reported value was 20 mg/L at EFF-001. |
|
Violation |
B |
Report |
1090607 |
01/30/2021 |
DMON |
Discharger did not monitor effluent ammonia at the required frequency during all weeks in January. Discharger did not monitor flow, turbidity, dose, or transmittance at UVS-001 at the required frequency during 17-19 January |
|
Violation |
B |
Report |
1088891 |
12/31/2020 |
Deficient Reporting |
Discharger did not include all required monitoring data in some SMRs submitted for reporting periods during April 2019 through December 2020, in violation of section VIII.B.1 of the MRP. |
|
Violation |
B |
Report |
1088884 |
12/31/2020 |
GWAT |
Discharger exceeded agronomic hydraulic loading rates identified by the Discharger for some crop types on various fields during various months between April 2019 and December 2020, in violation of Land Discharge Specification IV.A.1 |
|
Violation |
B |
Report |
1088885 |
12/31/2020 |
GWAT |
Discharger exceeded agronomic nitrogen loading rates identified by the Discharger for some crop types on various fields during the 2019 and 2020 growing seasons, in violation of Land Discharge Specification IV.A.2. |
|
Violation |
B |
Report |
1088886 |
12/31/2020 |
GWAT |
Discharger exceeded the cycle average loading rate of 200 lbs/acre/day for biochemical oxygen demand (BOD) on various fields during various months during April 2019 and December 2020, in violation of Land Discharge Specification IV.A.3.a. |
|
Violation |
B |
Report |
1088889 |
12/31/2020 |
GWAT |
Discharger exceeded the upper limitation for pH in the storage ponds at various times during April 2019 through December 2020, in violation of Construction, Operation, and Maintenance Specification VI.C.2.a.iv. |
|
Violation |
B |
Report |
1088890 |
12/31/2020 |
LREP |
Discharger submitted some of the SMRs for reporting periods during April 2019 through December 2020 after the required submittal date. |
|
Violation |
B |
Report |
1088887 |
12/31/2020 |
Order Conditions |
Discharger exceeded total coliform limitations for disinfected tertiary recycled water at reclaimed water monitoring location REC-001 at various times during April 2019 through December 2020, in violation of Reclamation Specification IV.B.4.b. |
|
Violation |
B |
Report |
1088888 |
12/31/2020 |
Order Conditions |
Discharger exceeded turbidity limitations for tertiary recycled water at reclaimed water monitoring location REC-001 at various times during April 2019 through 2020, in violation of Reclamation Specification IV.B.4.c. |
|
Violation |
B |
Report |
1081506 |
10/07/2020 |
Surface Water |
On 10/7/20, 10,000 gal spilled from the irrigation ditch to a canal leading to White Slough, in violation of Discharge Prohibition III.F. |
Staff collapsed the tunnel with a backhoe. |
Violation |
B |
eSMR |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|