Welcome to California
 California Home
Welcome to California - images of Golden Gate Bridge, ocean sunset, waterfall, flowers, and city skyline California Home Welcome to the California Environmental Protection Agency
 California Integrated Water Quality System Project (CIWQS)
   Facility At-A-Glance Report

  
   [VIEW PRINTER FRIENDLY VERSION] [EXPORT THIS REPORT TO EXCEL]

  
   SEARCH CRITERIA:      [REFINE SEARCH] [NEW SEARCH] [GLOSSARY]
Place ID 271858
  
  
  
  
Hide All Show All
General Information
Region Place ID Place Name Place Type Place Address Place County
2 271858 West-Side Aquifers Treatment System (WATS) Service/Commercial Site, NEC North Akron Road near Bldg. 045A Moffett Field, CA, 94035 Santa Clara

Expand/Contract Related Parties
Related Parties
Party Party Type Party Name Role Classification Relationship Start Date Relationship End Date
554849 Person Marcos De la Cruz Case Worker 10/19/2016
137758 Organization San Francisco Bay Regional Water Quality Control Board Regulating Waterboard 10/19/2016
560054 Person Donald M Chuck Contact 10/19/2016
322449 Organization NASA Ames Research Center Owner and Operator Federal Agency 08/19/2016
29061 Organization US Navy (WATS) Owner Federal Agency 10/14/1998 10/01/2016
Total Related Parties: 5

Expand/Contract Regulatory Measures
Regulatory Measures
Reg Measure ID Reg Measure Type Region Program Order No. WDID Effective Date Expiration Date Status Amended?
182989 Enrollee 2 DODNPDESWW R2-2004-0055 2 438009002 Historical N
397922 Enrollee - NPDES 2 DODNPDESWW R2-2017-0048 2 438009003 08/25/2014 09/01/2022 Active N
372522 Enrollee 2 DODNPDESWW R2-2009-0059 2 438009002 11/17/2010 09/30/2014 Historical N
Total Reg Measures: 3

Expand/Contract Violations
Violations
Violation ID Occurred Date Violation Type (-) Violation Description Corrective Action Status Classification Source
1105145 04/27/2022 CAT2 Diesel Oil Maximum Daily (MDEL) limit is 50 ug/L and reported value was 52 ug/L. Violation B Report
1078529 08/10/2020 DMON Violation of Attachment E section V.E - missing daily bioassay water monitoring for alkalinity, hardness, and ammonia. The analytical laboratory caused this violation as they didn't monitor for the parameters as requested by the Discharger. The laboratory apologized for the oversight. Violation B Report
1077989 09/13/2019 CAT2 1,1-Dichloroethane Daily Maximum limit is 0.50 ug/L and reported value was 0.71 ug/L. The Discharger suspects lag GAC vessels were replaced with contaminated media on 7-11-19, after which the system remained shutdown through the end of July 2019 due to unscheduled maintenance. The Discharger resumed discharge in August and monitored the treatment system on August 28, 2019. The Discharger will replace the GAC media in all vessels on 9-27-19 with virgin coconut GAC. Certificate of analysis will be required for all GAC media changeouts to avoid similar events. GAC changeouts will be done jointly with scheduled monitoring events. Violation B Report
1077988 09/13/2019 CAT2 cis-1,2-Dichloroethene Daily Maximum limit is 0.50 ug/L and reported value was 6.6 ug/L. The Discharger suspects lag GAC vessels were replaced with contaminated media on 7-11-19, after which the system remained shutdown through the end of July 2019 due to unscheduled maintenance. The Discharger resumed discharge in August and monitored the treatment system on August 28, 2019. The Discharger will replace the GAC media in all vessels on 9-27-19 with virgin coconut GAC. Certificate of analysis will be required for all GAC media changeouts to avoid similar events. GAC changeouts will be done jointly with scheduled monitoring events. Violation B Report
1077987 08/28/2019 CAT2 cis-1,2-Dichloroethene Daily Maximum limit is 0.50 ug/L and reported value was 9.4 ug/L. The Discharger suspects lag GAC vessels were replaced with contaminated media on 7-11-19, after which the system remained shutdown through the end of July 2019 due to unscheduled maintenance. The Discharger resumed discharge in August and monitored the treatment system on August 28, 2019. The Discharger will replace the GAC media in all vessels on 9-27-19 with virgin coconut GAC. Certificate of analysis will be required for all GAC media changeouts to avoid similar events. GAC changeouts will be done jointly with scheduled monitoring events. Violation B Report
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 5 Priority Violations: 0
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.

Violation Types
CAT2 = Category 2 Pollutant (Effluent Violation for Group 2 Pollutant) DMON = Deficient Monitoring

Expand/Contract Enforcement Actions
Enforcement Actions
Enf Id Enf Type Enf Order No. Effective Date Status
Total Enf Actions: 0

Expand/Contract Inspections
Inspections
Inspection ID Inspection Type Lead Inspector Actual End Date Planned Violations Attachment
334983 B Type compliance inspection Farhad Azimzadeh 06/17/2004 Y 0 N/A
Total Inspections: 1 Last Inspection: 06/17/2004
  
The current report was generated with data as of: 06/06/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
Back to Main Page  |  Back to Top of Page