Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1147878 |
08/25/2025 |
DMON |
Analyst Error for Sample M002 CBOD 8-25-2025 |
A chemist cross-contaminated a chlorinated sample with the M002 CBOD, resulting in a lack of depletion. The chemist was retrained on proper techniques to avoid cross-contamination. The laboratory manager reviewed subsequent BOD and CBOD data to ensure the effectiveness of the training. |
Violation |
U |
eSMR |
1147877 |
08/25/2025 |
DMON |
Analyst error for site M002 CBOD resulting in less than 7 consecutive CBOD samples for 7-day monitoring per page E-6 of order R9-2018-0059 permit. |
A chemist cross-contaminated a chlorinated sample with the M002 CBOD, resulting in a lack of depletion. The chemist was retrained on proper techniques to avoid cross-contamination. The laboratory manager reviewed subsequent BOD and CBOD data to ensure the effectiveness of the training. |
Violation |
U |
eSMR |
1126510 |
01/19/2024 |
UAUTHDISC |
Failsafe line break released 200 gallons of tertiary treated, reclaimed water with no chlorine residual into San Marcos Creek. Although the water was treated to Title 22 standards; the plant was not reclaiming, and the water was routed to the failsafe pipe-location M002. |
Failsafe flow was lowered and diverted to Mahr Reservoir when release was first noticed. Ten minutes later flow to line M002 was shut off completely. The pipe was repaired with a stainless-steel repair clamp and backfilled per District specs. |
Violation |
B |
eSMR |
1119447 |
04/08/2023 |
DMON |
From April 1 to 14, 2023, Encina reported flow from M-002. During the week of April 2 to 8, the report appears to only include four monitoring results for CBOD at M-002. During the week of April 9 to 15, the report includes the required five monitoring results for CBOD at M-002. |
|
Violation |
B |
Report |
1119423 |
07/11/2022 |
UAUTHDISC |
2 W Hydropneumatic Tank drain is not alligned with the drain in the ground/concrete pad causing drain 2W water to overflow to adjacened ground which was draining via a french drain directly to the brow ditch, which ultimatly trickled to the storm channel (estimated 20 gallons).
|
The small volume drained from 2 W tank reached the storm channel before it was noticed. The spill was 300 gallons, 280 was recovered, and 20 gallons was released to the environment. |
Violation |
B |
Report |
1119422 |
05/23/2022 |
UAUTHDISC |
The contractor broke an airvac on the discharge pipe, spilling 1,750 gallons of secondary-treated wastewater at the Leucadia Pump Station discharge pipe. Encina reported recovering 1,300 gallons of the spill. The spill reached flood control channel/receiving water. |
Shut down pumps, notified Leucadia. Drained back the discharge pipe to the wetwell. Pumped recovered water back to plant treatment. |
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|