| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1153228 |
03/17/2026 |
Order Conditions |
03/17/2026 Site inspection revealed the following violations: 1) sample preservation; 2) malfunctioning chlorine analyzer; 3) discharge of treated wastewater at undesignated disposal areas; 4) ponding of wastewater; 5) vegetation growth at ponds; 6) leakage at chlorine injection point |
|
Violation |
B |
Inspection |
| 1145627 |
03/25/2025 |
Other Water Code Sections |
Staff observed the chlorine analyzer to be broken at the recycled water tank. At the time of the inspection Staff noticed that the effluent sampling point, which is a pipe connected to the recycled water tank, was leaking and dripping onto the
surface. The pipe appeared to be completely covered in black tape to prevent leaks, but this did not stop the flow. At the time of the inspection the screw press at the headworks, which is described in finding 8 of the Order R7-2016-0032 as a compactor, was found to be broken and non-operational. |
|
Violation |
B |
Inspection |
| 1145626 |
06/17/2024 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 240 MPN/100 mL and reported value was 1600 MPN/100 mL. |
|
Violation |
B |
Report |
| 1106126 |
03/25/2022 |
OEV |
Dissolved Oxygen Daily Minimum limit is 1.0 mg/L and reported value was 0.3 mg/L. |
|
Violation |
B |
Report |
| 1106134 |
03/02/2022 |
Order Conditions |
Order requires that “Weeds shall be minimized through control of water depth, harvesting, or herbicides.” However, during the March 2, 2022, compliance evaluation inspection, staff observed that Pond G was overrun with weeds.
The Order also requires that “the Discharger shall at all times properly operate and maintain all systems and components of collection, treatment and control, installed or used by the Discharger to achieve compliance with this Board Order.” During the March 2, 2022, compliance evaluation, staff observed several areas that were not properly maintained, including inoperable pumps at Lift Stations No. 13 and 5; a bar screen at the headworks in disrepair; pooling water in the headworks building; and leaks in the building housing the chlorine generation system. |
|
Violation |
B |
Inspection |
| 1106133 |
02/28/2022 |
DMON |
pH, DO, and freeboard were not measured weekly for Pond 1. |
|
Violation |
B |
Report |
| 1106127 |
01/06/2022 |
Order Conditions |
Order requires a minimum of 2 feet of freeboard be maintained at all times and in all basins. The discharger reported a value of 1.6 feet for Pond 1. |
|
Violation |
B |
Report |
| 1106131 |
12/31/2021 |
DMON |
pH, DO, and freeboard were not measured weekly for Pond 1. |
|
Violation |
B |
Report |
| 1106128 |
12/10/2021 |
Order Conditions |
Order requires a minimum of 2 feet of freeboard be maintained at all times and in all basins. The discharger reported a value of 0.3 feet for both Pond A and Pond 1. |
|
Violation |
B |
Report |
| 1106132 |
10/31/2021 |
DMON |
pH and DO were not reported weekly for Pond 1. |
|
Violation |
B |
Report |
| 1106129 |
09/30/2021 |
DMON |
In September 2021, BOD and TSS samples were not collected once every two weeks (or as frequently as possible based on effluent flow). |
|
Violation |
B |
Report |
| 1106124 |
08/06/2021 |
OEV |
Total Coliform 7-Day Median limit is 23 mg/L and reported value was 540 mg/L. |
|
Violation |
B |
Report |
| 1106125 |
08/06/2021 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 240 mg/L and reported value was 1600 mg/L. |
|
Violation |
B |
Report |
| 1106123 |
08/05/2021 |
CAT1 |
Total Suspended Solids (TSS) Monthly Average limit is 95 mg/L and reported value was 120 mg/L. |
|
Violation |
B |
Report |
|