Facility At-A-Glance Report |
|
|
[VIEW PRINTER FRIENDLY VERSION]
[EXPORT THIS REPORT TO EXCEL]
|
|
|
[REFINE SEARCH]
[NEW SEARCH]
[GLOSSARY]
Place ID 267428
|
|
|
|
|
|
General Information
|
Region |
Place ID |
Place Name |
Place Type |
Place Address |
Place County |
4 |
267428 |
TFX Aviation, Inc. (Former Telair Site, Newbury Park) |
Manufacturing NEC |
3085 Old Conejo Newbury Park, CA, 91320 |
Ventura |
|
|
Related Parties
|
|
Total Related Parties: 11
|
|
|
Regulatory Measures
|
Reg Measure ID |
Reg Measure Type |
Region |
Program |
Order No. |
WDID |
Effective Date |
Expiration Date |
Status |
Amended? |
436207 |
NPDES Permit |
4 |
NPDNONMUNIPRCS |
R4-2021-0098 |
4A562397003 |
08/01/2021 |
07/31/2026 |
Active |
N |
396635 |
NPDES Permit |
4 |
NPDNONMUNIPRCS |
R4-2015-0106 |
4A562397003 |
07/01/2015 |
06/30/2020 |
Historical |
N |
366345 |
NPDES Permit |
4 |
NPDNONMUNIPRCS |
R4-2009-0096 |
4A562397003 |
10/05/2009 |
08/10/2014 |
Historical |
Y |
363183 |
NPDES Permit |
4 |
NPDESWW |
R4-2009-0031 |
4A562397002 |
03/07/2009 |
02/05/2014 |
Historical |
N |
310024 |
NPDES Permit |
4 |
NPDESWW |
R4-2003-0095 |
4A562397002 |
07/10/2003 |
06/10/2008 |
Historical |
N |
136749 |
NPDES Permit |
4 |
NPDESWW |
97-032 |
4A562397002 |
04/07/1997 |
02/10/2002 |
Historical |
N |
135520 |
NPDES Permit |
4 |
NPDESWW |
95-005 |
4A562397002 |
01/23/1995 |
12/10/1999 |
Historical |
N |
134633 |
NPDES Permit |
4 |
NPDESWW |
88-126 |
4A562397002 |
11/28/1988 |
11/10/1993 |
Historical |
N |
135221 |
NPDES Permit |
4 |
NPDESWW |
86-024 |
4A562397002 |
04/28/1986 |
04/10/1991 |
Historical |
N |
|
Total Reg Measures: 9
|
|
|
Violations
|
Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1134926 |
07/31/2024 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 29.1 mg/L and reported value was 31.0 mg/L at EFF-001. |
Treatment system does not treat for copper. No changes were implemented. |
Violation |
B |
eSMR |
1134925 |
07/30/2024 |
CAT1 |
Total Dissolved Solids (TDS) Daily Maximum limit is 850 mg/L and reported value was 860 mg/L at EFF-001. |
Re-sample took place on September 16, 2024 and the result was 780 mg/L which is below the MDEL. No changes were implemented. |
Violation |
B |
eSMR |
1102001 |
08/03/2021 |
CAT1 |
Total Dissolved Solids (TDS) Daily Maximum limit is 850 mg/L and reported value was 900 mg/L at EFF-001. |
|
Violation |
B |
Report |
1085163 |
10/07/2020 |
DMON |
In preparing the 4th quarter report, it was noted that the October 27, 2020 analytical report from BC Laboratories, Inc, showed a code that indicated the sample was analyzed outside of the holding time for hexavalent chromium. Although the October 7, 2020 sample taken indicates a result of 2.8 ppb, the results cannot be relied upon since holding times were exceeded |
Since the lab did not bring this to our attention (at the time), another sample to be analyzed for CR6 for the month of October was not taken. |
Violation |
B |
eSMR |
1085162 |
10/07/2020 |
CAT1 |
Total Dissolved Solids (TDS) Daily Maximum limit is 850 mg/L and reported value was 890 mg/L at EFF-001. |
Since July 2020, activities have been initiated (flow sensor replacements, electrical upgrades, flow reductions from certain wells) in order to mitigate further TDS issues in the effluent discharges..
Individual well flow sensors and flow meters were taken off line and replaced/repaired over the last two weeks of October and in November. By early December the well flow sensors and meters were returned to service. Well field balancing included slightly reducing the flow rates from extraction wells with higher TDS and increasing the flow rates from extraction wells with lower TDS. The well field balancing kept the overall system flow rate approximately the same. The effluent was re-sampled on December 1, 2020. The TDS result was 820 mg/L, below the allowable discharge permit limit |
Violation |
B |
eSMR |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|
|
Total Violations: 5
|
Priority Violations: 0
|
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.
|
Violation Types |
CAT1 = Category 1 Pollutant (Effluent Violation for Group 1 Pollutant)
|
CAT2 = Category 2 Pollutant (Effluent Violation for Group 2 Pollutant)
|
DMON = Deficient Monitoring
|
|
|
|
Enforcement Actions
|
|
Total Enf Actions: 6
|
|
|
Inspections
|
Inspection ID |
Inspection Type |
Lead Inspector |
Actual End Date |
Planned |
Violations |
Attachment |
54983526 |
B Type compliance inspection |
Kristie Kao |
02/27/2024 |
N |
0 |
Download |
36780267 |
B Type compliance inspection |
Jose Morales |
12/30/2019 |
Y |
0 |
Download |
26400019 |
B Type compliance inspection |
Jose Morales |
01/12/2017 |
Y |
0 |
Download |
19860034 |
Miscellaneous inspection |
Rosario Aston |
10/15/2014 |
N |
0 |
Download |
10050893 |
Prerequirement inspection |
Rosario Aston |
10/18/2012 |
Y |
0 |
Download |
8487129 |
B Type compliance inspection |
Jose Morales |
05/30/2012 |
Y |
0 |
Download |
1826664 |
Prerequirement inspection |
Rosario Aston |
08/06/2009 |
Y |
0 |
Download |
1781262 |
Prerequirement inspection |
Rosario Aston |
03/03/2009 |
Y |
0 |
Download |
1781261 |
Prerequirement inspection |
Cassandra Owens (Multiple) |
02/09/2009 |
Y |
0 |
[Attachments] |
1274900 |
B Type compliance inspection |
Tetra Tech Inspector |
11/05/2007 |
Y |
1 |
Download |
275262 |
B Type compliance inspection |
Cassandra Owens |
05/23/2000 |
Y |
0 |
N/A |
275260 |
B Type compliance inspection |
Veronica Cuevas-Alpuche |
05/13/1997 |
Y |
0 |
N/A |
275261 |
B Type compliance inspection |
Veronica Cuevas-Alpuche |
06/27/1996 |
Y |
0 |
N/A |
|
Total Inspections: 13 |
Last Inspection: 02/27/2024 |
|
|
|
|
 |
The current report was generated with data as of: 07/14/2025
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.
|
 |
Back to Main Page
|
Back to Top of Page
|
|
|
|
|